Emerson Mass Flow Transmitter 00825-0100-4716 user manual

User manual for the device Emerson Mass Flow Transmitter 00825-0100-4716

Device: Emerson Mass Flow Transmitter 00825-0100-4716
Category: Marine Instruments
Manufacturer: Emerson
Size: 1.89 MB
Added : 3/28/2014
Number of pages: 32
Print the manual

Download

How to use this site?

Our goal is to provide you with a quick access to the content of the user manual for Emerson Mass Flow Transmitter 00825-0100-4716. Using the online preview, you can quickly view the contents and go to the page where you will find the solution to your problem with Emerson Mass Flow Transmitter 00825-0100-4716.

For your convenience

If looking through the Emerson Mass Flow Transmitter 00825-0100-4716 user manual directly on this website is not convenient for you, there are two possible solutions:

  • Full Screen Viewing - to easily view the user manual (without downloading it to your computer), you can use full-screen viewing mode. To start viewing the user manual Emerson Mass Flow Transmitter 00825-0100-4716 on full screen, use the button Fullscreen.
  • Downloading to your computer - You can also download the user manual Emerson Mass Flow Transmitter 00825-0100-4716 to your computer and keep it in your files. However, if you do not want to take up too much of your disk space, you can always download it in the future from ManualsBase.
Emerson Mass Flow Transmitter 00825-0100-4716 User manual - Online PDF
Advertisement
« Page 1 of 32 »
Advertisement
Print version

Many people prefer to read the documents not on the screen, but in the printed version. The option to print the manual has also been provided, and you can use it by clicking the link above - Print the manual. You do not have to print the entire manual Emerson Mass Flow Transmitter 00825-0100-4716 but the selected pages only. paper.

Summaries

Below you will find previews of the content of the user manuals presented on the following pages to Emerson Mass Flow Transmitter 00825-0100-4716. If you want to quickly view the content of pages found on the following pages of the manual, you can use them.

Abstracts of contents
Summary of the content on the page No. 1

Quick Installation Guide
00825-0100-4716, Rev DA
October 2009 Rosemount 3095 MultiVariable

Rosemount 3095 MultiVariable Mass Flow
® ™
Transmitter with HART or FOUNDATION
Fieldbus Protocol
Rosemount 3095MF Series Flowmeter Transmitter
Product Discontinued
Start
Step 1: Mount the Transmitter
Step 2: Transmitter Installation
Step 3: Software Installation
Step 4: Connect the Wiring and Power Up (HART or Fieldbus)
Step 5: Configure the Transmitter (HART or Fieldbus)
Step 6: Trim the Transmitter
P

Summary of the content on the page No. 2

Quick Installation Guide 00825-0100-4716, Rev DA Rosemount 3095 MultiVariable October 2009 © 2009 Rosemount Inc. All rights reserved. All marks property of owner. Rosemount and the Rosemount logotype are registered trademarks of Rosemount Inc. Rosemount Inc. Emerson Process Management GmbH & Co. OHG 8200 Market Boulevard Argelsrieder Feld 3 Chanhassen, MN USA 55317 82234 Wessling T (US) (800) 999-9307, F (952) 949-7001 Germany T (International) (952) 906-8888 T 49 (8153) 9390, F49 (8153) 9391

Summary of the content on the page No. 3

Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiVariable TRANSMITTER EXPLODED VIEW Certification Label Housing Terminal Block (HART) O-ring Cover Electronics Board Nameplate Module O-ring Sensor Module Housing Locking Screw RTD Connector Process Adapter O-ring Drain/Vent Valve Coplanar Flange Flange Adapter O-ring Optional Flange Adapters LCD Display Assembly LCD Display Cover Bolts Terminal Block (Fieldbus) 3

Summary of the content on the page No. 4

Quick Installation Guide 00825-0100-4716, Rev DA Rosemount 3095 MultiVariable October 2009 STEP 1: MOUNT THE TRANSMITTER Liquid Flow Applications 1. Place taps to the side of the line. 2. Mount beside or below the taps. 3. Mount the transmitter so that the drain/vent valves are oriented upward. Flow Gas Flow Applications 1. Place taps in the top or side of the line. 2. Mount beside or above the taps. Flow Flow Steam Flow Applications 1. Place taps to the side of the line. 2. Mount beside or bel

Summary of the content on the page No. 5

Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiVariable STEP 2: TRANSMITTER INSTALLATION Consider Housing Rotation To improve field access or to better view the optional LCD display: 1. Loosen the housing rotation set screw. 2. Rotate the housing clockwise to the desired position – up to 180° from its original position. Over rotating will damage the transmitter. 3. If the desired position is attained, tighten the housing rotation set screw. 4. If the desired

Summary of the content on the page No. 6

Quick Installation Guide 00825-0100-4716, Rev DA Rosemount 3095 MultiVariable October 2009 STEP 2 CONTINUED... 3. Set the Failure Mode Alarm (HART devices), which is located on the front of the electronics board inside the electronics housing cover. The Alarm Jumper position determines if the output is driven high or low when a failure is detected. The transmitter operates normally if the jumpers are not installed and the Alarm default fail is HI. Figure 2. Alarm Jumper Location Security Jum

Summary of the content on the page No. 7

Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiVariable STEP 2 CONTINUED... • Installing a Shielded 3095 RTD Cable (See Figure 4) Note: Shielded cable is intended for use in a conduit. a.Fully engage the black cable connector to the 3095 RTD Connector. b.Tighten the cable adapter until metal contacts metal. Figure 4. Shielded RTD Cable 1 Cable Adapter /2–14 NPT Black Cable Connector • Installing a ATEX/IECEx Flameproof 3095 RTD Cable (See Figure 5) a.Fully eng

Summary of the content on the page No. 8

Quick Installation Guide 00825-0100-4716, Rev DA Rosemount 3095 MultiVariable October 2009 STEP 2 CONTINUED... Bolting Considerations If the transmitter installation requires assembly of the process flanges, manifolds, or flange adapters, follow these assembly guidelines to ensure a tight seal for optimal performance characteristics of the transmitters. Use only bolts supplied with the transmitter or sold by Emerson as spare parts. Figure 6 illustrates common transmitter assemblies with the b

Summary of the content on the page No. 9

Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiVariable STEP 2 CONTINUED... Figure 7. Torque values for the flange and flange adapter bolts Bolt Material Head Markings Initial Torque Final Torque Carbon Steel (CS) 300 in.-lbs. 650 in.-lbs. B7M Stainless Steel (SST) 150 in.-lbs. 300 in.-lbs. 316 B8M 316 STM SW 316 316 316 R O-rings with Flange Adapters WARNING Failure to install proper flange adapter O-rings may cause process leaks, which can result in death or

Summary of the content on the page No. 10

Quick Installation Guide 00825-0100-4716, Rev DA Rosemount 3095 MultiVariable October 2009 STEP 3: SOFTWARE INSTALLATION The 3095 Engineering Assistant (EA) for HART and 3095 Engineering Assistant (EA) for FOUNDATION Fieldbus software programs can be installed on the same computer. The applications cannot be open simultaneously. 3095 Engineering Assistant (EA) for HART Software Installation 1. Install the Program a.Place the CD-ROM in the drive and run setup.exe from Windows NT, 2000, or XP. b

Summary of the content on the page No. 11

Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiVariable STEP 3 CONTINUED... Installing the HART Modem After installing the 3095 Engineering Assistant, the HART modem configuration window automatically appears when the 3095 Engineering Assistant is opened. If this window is canceled, the HART modem may be installed manually with the following procedure. 1. Close AMS. From the Start Menu select Programs > 3095 Engineering Assistant > AMS Network. 2. Select Add

Summary of the content on the page No. 12

Quick Installation Guide 00825-0100-4716, Rev DA Rosemount 3095 MultiVariable October 2009 S STE TEP P 4: C 4: CON ONNE NECT CT W WIR IRIN ING G AN AND D P POWER OWER U UP P (HART) (HART) Use the following steps to wire the transmitter: 1. Remove the housing cover on the side marked FIELD TERMINALS. 2. Connect the signal leads to the terminals. NOTE Do not connect the powered signal wiring to the test terminals. Power could damage the test diode in the test connection. Shielded twisted pair c

Summary of the content on the page No. 13

Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiVariable STEP 4: CONNECT WIRING AND POWER UP (FIELDBUS) Use the following steps to wire the transmitter: 1. Remove the housing cover labeled “Field Terminals.” Terminals are not polarity sensitive. 2. Connect the signal leads to the terminals labeled “Fieldbus Wiring”. 3. Plug and seal unused conduit connections. 4. Install wiring with a drip loop. Arrange the drip loop so the bottom is lower than the conduit conn

Summary of the content on the page No. 14

Quick Installation Guide 00825-0100-4716, Rev DA Rosemount 3095 MultiVariable October 2009 STEP 5: CONFIGURE THE TRANSMITTER (HART) Setting the Loop to Manual Set the process application loop to manual when preparing to send or request data that would disrupt the loop or change the output of the transmitter. A prompt will appear reminding the user to set the loop to manual when necessary. Acknowledging this prompter does not set the loop to manual. Send the Configuration to the Transmitter Us

Summary of the content on the page No. 15

Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiVariable Function/Variable Fast Key Sequence DP Sens Trim 1, 2, 2, 1, 1 DP Snsr Range 1, 3, 5, 1 DP URV 5 DP units 1, 3, 2, 1 Date 1, 3, 4, 4 Descriptor 1, 3, 4, 2 Diff pres damp 1, 4, 2, 4 Diff pres 1, 1, 1 Diff pres 2 Fld dev rev 1, 3, 4, 9, 2 Flo rate 1, 1, 4, 5 Flow Rate Special Units 1, 4, 5, 1 ✓ Flow Units 1, 3, 2, 5 GP Damping 1, 4, 2, 5, 4 GP Sens Trim 1, 2, 2, 1, 3 GP Units 1, 3, 2, 4 Gage (GP) 1, 1, 4, 4

Summary of the content on the page No. 16

Quick Installation Guide 00825-0100-4716, Rev DA Rosemount 3095 MultiVariable October 2009 STEP 5: CONFIGURE THE TRANSMITTER (FIELDBUS) Each FOUNDATION fieldbus host or configuration tool has a different way of displaying and performing configurations. Some use Device Descriptions (DD) or DD methods for configuration and to display data consistently across platforms. There is no requirement that a host or configuration tool support these features. Use the following block examples to do basic

Summary of the content on the page No. 17

Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiVariable STEP 6: TRIM THE TRANSMITTER NOTE Transmitters are shipped from Emerson Process Management fully calibrated and configured for the application when C2 Option is ordered. Without C2 Option, configuration will be by the factory default (span = upper range limit for FOUNDATION fieldbus transmitters). Zero Trim A zero trim is a single-point adjustment used for compensating mounting position effects and line

Summary of the content on the page No. 18

Quick Installation Guide 00825-0100-4716, Rev DA Rosemount 3095 MultiVariable October 2009 PRODUCT CERTIFICATIONS Rosemount 3095 with HART Approved Manufacturing Locations Rosemount Inc. — Chanhassen, Minnesota USA Emerson Process Management GmbH & Co. — Wessling, Germany Emerson Process Management Asia Pacific Private Limited — Singapore Beijing Rosemount Far East Instrument Co., Limited – Beijing, China European Directive Information The EC declaration of conformity for all applicable European

Summary of the content on the page No. 19

Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiVariable Canadian Standards Association (CSA) C Explosion Proof for Class I, Division 1, Groups B, C, and D. Dust-Ignition Proof for Class II/Class III, Division 1, Groups E, F, and G. CSA enclosure Type 4X suitable for indoor and outdoor hazardous locations. Provides nonincendive RTD connection for Class I, Division 2, Groups A, B, C, and D.Factory Sealed. Install in accordance with Rosemount Drawing 03095-10

Summary of the content on the page No. 20

Quick Installation Guide 00825-0100-4716, Rev DA Rosemount 3095 MultiVariable October 2009 G ATEX Type n Certificate Number: BAS98ATEX3360X II 3 G Ex nL IIC T5 (T = –45 °C to 40 °C) amb Ex nL IIC T4 (T = –45 °C to 70 °C) amb U = 55V i The apparatus is designed for connection to a remote temperature sensor such as a resistance temperature detection (RTD) Special Conditions for Safe Use The 3095, when fitted with the transient terminal block (order code B), are not capable of withstanding the


Alternative user manuals
# User manual Category Download
1 Emerson Digital Controller Valves 788 DVC User manual Marine Instruments 31
2 Emerson Four-electrode Conductivity Sensor 410VP User manual Marine Instruments 0
3 Emerson FCL with 1050 Analyzer 1056 User manual Marine Instruments 149
4 Emerson Four-electrode Conductivity Sensor PN 51A-410VP User manual Marine Instruments 0
5 Emerson ENDURANCE Conductivity Sensor 404 User manual Marine Instruments 1
6 Emerson ENDURANCE Conductivity Sensor PN 51A-404 User manual Marine Instruments 1
7 Emerson FCL with 1050 Analyzer PN 51-FCL-1056 User manual Marine Instruments 12
8 Emerson Mass Flow Transmitter 3095 User manual Marine Instruments 34
9 Emerson Multiport Flow Selector I-0168 User manual Marine Instruments 6
10 Emerson pH/ORP Analyzer/Controller 54e User manual Marine Instruments 3
11 Emerson pH/ORP Analyzer/Controller PN 51A-54epH User manual Marine Instruments 3
12 Emerson Rosemount Pressure Transmitter 3051S User manual Marine Instruments 58
13 Emerson pH/ORP Analyzer/Controller 54e pH User manual Marine Instruments 18
14 Emerson Tank Contents Transmitter MAS 2600 User manual Marine Instruments 115
15 Emerson turbine meter 1500 User manual Marine Instruments 8
16 Sony SSM-930 User manual Marine Instruments 3
17 Sony SSM-175A User manual Marine Instruments 0
18 Attwood 8M004689 User manual Marine Instruments 0
19 Attwood 99515-1 User manual Marine Instruments 0
20 Attwood 99510-1 User manual Marine Instruments 0