Summary of the content on the page No. 1
E6581830
TOSVERT VF-S15 series
®
option unit Function Manual
CCL003Z
NOTICE
1. Read this manual before installing or operating. Keep this instruction manual on
hand of the end user, and make use of this manual in maintenance and inspection.
2. All information contained in this manual will be changed without notice. Please
contact your Toshiba distributor to confirm the latest information.
Summary of the content on the page No. 2
E658130 Introduction ® Thank you for purchasing the “CC-Link option (CCL003Z)” for TOSVERT VF-S15 drive. This option can connect with open field network CC-Link and data communications with the CC-Link master through installing this option in the VF-S15 and using it. Besides this instruction manual, the “CC-Link option Instruction Manual” is required to develop software communicating with VF-S15. This option needs the option adaptor to connect VF-S15 which type form is SBP009Z. Please m
Summary of the content on the page No. 3
E658130 Handling in general Warning Do not connect or disconnect a network cable while the drive power is on. It may lead to electric shocks or fire. Prohibited See the instruction manual attached with the option unit for cautions the handling. Otherwise, it may lead to electric shocks, fire, injuries or damage to product. Mandatory Network control Warning Do not send the value out of the valid range to objects and attributes. Otherwise, the motor may suddenly start/
Summary of the content on the page No. 4
E658130 Table of Contents 1. OVERVIEW ............................................................................................................................................ - 4 - 2. BASIC SPECIFICATIONS..................................................................................................................... - 4 - 2.1. CC-Link Version.............................................................................................................................. - 5 - 2.1.1.
Summary of the content on the page No. 5
E658130 1. Overview The option allows the VF-S15 drive to be connected into a CC-Link network. CC-Link supports a maximum of 42 nodes, allowing for the Master and this option is based on CC-Link V1.1 and V2.0. The CCL-003Z is able to operate RUN/STOP, monitor the status of the drive, set the drive’s parameter and etc. by the CC-Link master through installing the VF-S15. And it can use various applications. 2. Basic specifications Item Specification Ope
Summary of the content on the page No. 6
E658130 2.1. CC-Link Version 2.1.1. CC-Link Ver. 1.10 The conventional CC-Link products, whose inter-station cable lengths have equally been changed to 20cm (7.87 inch) or more to improve the inter-station cable length restriction, are defined as CC-Link Ver. 1.10. In comparison the conventional products are defined as CC-link Ver. 1.00. Refer to the CC-link Master Module Manual for the maximum overall cable lengths and inter-station cable lengths of CC-Link Ver. 1.00 and Ver. 1.10 C
Summary of the content on the page No. 7
E658130 3. Names and functions The drawing below shows names and functions of main parts. 3.1. Outline Connector to the inverter Release tab LED indicator (See 4.5) CC-Link Connector DA DB DG SLD FG - 6 -
Summary of the content on the page No. 8
E658130 4. Installation on inverter Refer to VF-S15 option adapter instruction manual (E6581838) for the installation on the inverter. The following steps must be performed before installing. 1. Shut off all input power. Mandatory 2. Wait at least 15 minutes and check to make sure that the charge lamp is no longer lit. 4.1. Connection cable In the CC-Link system, use CC-Link dedicated cables. If the cable used is other than the CC-Link dedicated cable, the performance of the
Summary of the content on the page No. 9
E658130 4.3. Connection of CC-Link master unit and inverter The example of the connection of the CC-Link master unit and the inverter is shown.。 Motor R/L1 U/T1 S/L2 V/T2 Inverter I M T/L3 VF-S15 W/T3 DA DA CC-Link DB DB Master CCL003Z DG DG Unit SLD SLD FG FG *Connection of Several Inverters Factory Automation can be applied to several inverters which share a link system as CC-Link remote device stations and are controlled and monitored by PLC user pr
Summary of the content on the page No. 10
E658130 4.4. The maximum connection number of units 1. Maximum number of units connected to one master station (CC-Link Ver.1.10) 42 units (when only inverters are connected) If any other units are included, the number of stations occupied depends on the unit and therefore the following conditions must be satisfied: {(1 × a) + (2 × b) + (3 × c) + (4 × d)} ≦ 64 a: Number of units occupying 1 station b: Number of units occupying 2 stations c: Number of units occupying 3 stations d: Num
Summary of the content on the page No. 11
E658130 2. Maximum number of units connected to one master station (CC-Link Ver.2.00) 42 units (when connections are inverter only) If any other units are included, the number of stations occupied depends on the unit and therefore the following conditions must be satisfied: {(a + a2 + a4 + a8) + (b + b2 + b4 + b8) × 2 + (c + c2 + c4 + c8) × 3 + (d + d2 + d4 + d8) × 4} ≦ 64 {(a × 32 + a2 × 32 + a4 × 64 + a8 × 128) + (b × 64 + b2 × 96 + b4 × 192 + b8 × 384) + (c × 96 + c2 × 160 + c4 × 3
Summary of the content on the page No. 12
E658130 4.5. LED indicator The LEDs shows the present status of the network and module Refer to 7.3 for detail. L.RUN SD RD L.ERR ■ Layout of LED L.RUN Light on during communication. SD Light on during send the data of CC-Link. RD Light on during receive the data of CC-Link. L.ERR Light on during communication error. - 11 -
Summary of the content on the page No. 13
E658130 5. Functions This option is a communication interface unit that allows the PLC program to operate, monitor and set the parameter of the inverter as a remote station of CC-Link. It is able to communicate with a maximum speed of 10Mbps not only transmitting bit data but also by word data. Moreover, more data transmissions are possible by the use of CC-Link V2.0. 5.1. Initial setting Set the following parameters of the inverter. Factory CC-Link Title Function Description se
Summary of the content on the page No. 14
E658130 5.2. Communication parameters for CCL003Z Title Function Description Communication error detection c100 0.0 - 100.0 sec. delay time 0: Stop and controlled by cmod, fmod c101 1: Operation continue Inverter operation at the 2: Deceleration stop communication loss action 3: Coast stop 4: Network error stop (err8 trip) 5: Preset speed operation (by c102 setting) Preset speed 0: None c102 operation selection 1 to 15: Preset speed 0: Disconnection detection c103 Commun
Summary of the content on the page No. 15
E658130 5.3. CC-Link function setting 5.3.1. Station number setting Use parameter c120 to set station number of the inverter. Set this parameter within the range of 1 to 64. Title Function Description CC-Link station c120 1 to 64 number selection *Use different station numbers for different devices. (If different devices have the same station number, the communication cannot be performed properly.) ・ Set consecutive numbers for the station numbers. (Do not skip a number in seq
Summary of the content on the page No. 16
E658130 5.3.3. CC-Link extended setting Remote register function can be extended. Title Function Description CC-Link extended selection * 0: Occupies one station (V1.10) c122 1: Occupies one station double (V2.0) 2: Occupies one station quadruple (V2.0) 3: Occupies one station octuple (V2.0) ・ When using double, quadruple and octuple settings of the CC-Link Ver.2, station data of the master station must be set to double, quadruple and octuple also. (If the master station is CC-
Summary of the content on the page No. 17
E658130 5.4. Basic functions This clause shows the basic function of this CC-Link option using by CC-Link communication. 5.4.1. Run and frequency operation command The PLC program can operate the inverter to run, stop, set the operation frequency and change the parameters. If the PLC controls these operations, select the command mode and the frequency setting mode. The parameter setting of the inverter Command mode selection cmod : 4[Communication option] (Factory setting: 1
Summary of the content on the page No. 18
E658130 5.5. I/O signal list 5.5.1. One station is occupied (CC-Link Ver.1) (c122=0) This option occupies one station area of the buffer memory of the PLC. In the case of c122 = 0, there are remote I/O (RX, RY both 32 bits) and the remote register (RWw, RWr both 4 word) in the communication data for one station area. Remote I/O (Default value = 0) Inverter (Slave) → PLC (Master) PLC (Master) → Inverter (Slave) Device No. Signal Device No. Signal RXn0 Forward running RYn0 Forward r
Summary of the content on the page No. 19
E658130 5.5.2. Double setting is selected (CC-Link Ver.2) (c122=1) This option occupies one station area of the buffer memory of the PLC. In the case of c122 = 1, there are remote I/O (RX, RY both 32 bits(same as CC-LINK Ver.1)) and the remote register (RWw, RWr both 8 word) in the communication data for one station area. * Default value of RY and RX is 0. Remote register (Default value = 0) RWr Inverter → PLC RWw PLC → Inverter Address Signal
Summary of the content on the page No. 20
E658130 5.5.4. Octuple setting is selected (CC-Link Ver.2) (c122=3) This option occupies one station area of the buffer memory of the PLC. In the case of c122 = 3, there are remote I/O (RX, RY both 32 bits(same as CC-LINK Ver.1)) and the remote register (RWw, RWr both 32 word) in the communication data for one station area. * Default value of RY and RX is 0. Remote register (Default value = 0) RWr Inverter → PLC RWw PLC → Inverter Address Signa