APC MGE 300 user manual

User manual for the device APC MGE 300

Device: APC MGE 300
Category: Battery Charger
Manufacturer: APC
Size: 1.25 MB
Added : 3/30/2014
Number of pages: 28
Print the manual

Download

How to use this site?

Our goal is to provide you with a quick access to the content of the user manual for APC MGE 300. Using the online preview, you can quickly view the contents and go to the page where you will find the solution to your problem with APC MGE 300.

For your convenience

If looking through the APC MGE 300 user manual directly on this website is not convenient for you, there are two possible solutions:

  • Full Screen Viewing - to easily view the user manual (without downloading it to your computer), you can use full-screen viewing mode. To start viewing the user manual APC MGE 300 on full screen, use the button Fullscreen.
  • Downloading to your computer - You can also download the user manual APC MGE 300 to your computer and keep it in your files. However, if you do not want to take up too much of your disk space, you can always download it in the future from ManualsBase.
APC MGE 300 User manual - Online PDF
Advertisement
« Page 1 of 28 »
Advertisement
Print version

Many people prefer to read the documents not on the screen, but in the printed version. The option to print the manual has also been provided, and you can use it by clicking the link above - Print the manual. You do not have to print the entire manual APC MGE 300 but the selected pages only. paper.

Summaries

Below you will find previews of the content of the user manuals presented on the following pages to APC MGE 300. If you want to quickly view the content of pages found on the following pages of the manual, you can use them.

Abstracts of contents
Summary of the content on the page No. 1

Battery
Installation
MGE™ Galaxy™ 300
10-40 kVA
380/400/415 V
10-40 kVA

Summary of the content on the page No. 2

Summary of the content on the page No. 3

Contents Overview .......................................................................... 1 IMPORTANT SAFETY INSTRUCTIONS - SAVE THESE INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Product Overview............................................................ 2 Cables and Batteries....................................................... 3 Prepare for Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Battery enclosure with pre-i

Summary of the content on the page No. 4

Checklist......................................................................... 15 Appendix ........................................................................ 16 One-line diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Battery cabling YUASA 15 kVA 60 min. . . . . . . . . . . . . . . . . . . . . . . 17 Battery cabling YUASA 20/30 kVA 60 min. . . . . . . . . . . . . . . . . . . . 18 Battery cabling YUASA 40 kVA 60 min. . . . . . . . . . . . . . .

Summary of the content on the page No. 5

Overview IMPORTANT SAFETY INSTRUCTIONS - SAVE THESE INSTRUCTIONS Warning: ALL safety instructions in the Safety Sheet (990-3620) must be read, understood and followed when installing the UPS and XR Battery enclsoure(s). Failure to do so could result in equipment damage, serious injury, or death. Warning: The maximum storage time of the UPS is limited to six months due to the need of recharging the integrated batteries. If the UPS remains de-energised for a long period, we recommend that you

Summary of the content on the page No. 6

Product Overview  Battery shelves  Battery circuit breaker  Ground cable connection (from the UPS)  Battery temperature sensor  (ATIZ)   Connection terminal       Front view 2 MGE™ Galaxy™ 300 10-40 kVA 3:3, 10-30 kVA 3:1 - 380/400/415 V Installation

Summary of the content on the page No. 7

Cables and Batteries Note: The battery enclosure must be installed on a non-inflammable, level and solid floor. Prepare for Cables 1. Open the front door.  Front view 2. Remove both side panels.   Front view MGE™ Galaxy™ 300 10-40 kVA 3:3, 10-30 kVA 3:1 - 380/400/415 V Installation 3

Summary of the content on the page No. 8

Battery enclosure with pre-installed batteries Warning: Remove all cardboard used to protect the batteries during transport. Make sure that cables and copper bars are separated. Note: A maximum of two battery enclosures can be connected to the UPS (one XR Battery enclosure with a circuit breaker plus one enclosure without a circuit breaker) by a batch cable between the UPS and the circuit breaker in the battery enclosure. 1. Remove the left and right plastic cover from the battery breaker by

Summary of the content on the page No. 9

+ N - 2. Connect the batteries to the battery breaker by running the cables from the battery breaker to each shelve. Note! Make sure to run the cables in this order.  Front view Battery enclosure without pre-installed batteries Warning: APC by Schneider is not responsible for the wiring of external non-APC batteries. Warning: Remove all cardboard used to protect the batteries during transport. Make sure that cables and copper bars are separated. Note: Before the installation of batt

Summary of the content on the page No. 10

+ N - Note: A maximum of two battery enclosures can be connected to the UPS (one XR Battery enclosure with a circuit breaker plus one enclosure without a circuit breaker) by a batch cable between the UPS and the circuit breaker in the battery enclosure. 1. Insert the batteries on the shelves starting from the bottom according to the relevant diagram for your configuration under “Appendix” on page 16. 2. Connect the batteries according to the chosen configuration diagram. 3. Install a bat

Summary of the content on the page No. 11

Connect Communication Cables between the UPS and Battery Enclosure External battery temperature (ATIZ) and external battery breaker signal Note: The ATIZ cable is for external battery temperature detection signal (cable is pre- installed). Note: The battery cable is for external battery breaker signal (cable is pre-installed). Note: The connection of communication cables is only applicable between the UPS and XR1. For the connection of XR2, follow step 2 only. 1. Run the combined battery brea

Summary of the content on the page No. 12

+ N - + N - Connect the Battery Cables between the UPS and Battery Enclosure Warning: This procedure describes how to connect the initial battery cables between the UPS and XR before start-up. If the UPS is up running, see “Connect an XR Battery Enclosure to a running UPS” on page 10. BAT+, BAT-, and N 1. Run the ground cable up through the bottom front hole of the XR and connect it to the Battery busbar. enclosure  2. Run the BAT+, N, and BAT- cables up through the bottom front

Summary of the content on the page No. 13

+, N, - Battery +, N, - +, N, - Battery 10-40 kVA 3:3 10 15 VA - k 3:1 20-30 kV :1 A 3 Battery  Rear view of the UPS   5. Connect the battery cables to the battery terminals in the UPS. See the UPS installation manual for information on how to remove the I/O sheet metal cover. 6. Re-install the UPS covers. See the UPS installation manual for more information. MGE™ Galaxy™ 300 10-40 kVA 3:3, 10-30 kVA 3:1 - 380/400/415 V Installation 9

Summary of the content on the page No. 14

Connect an XR Battery Enclosure to a running UPS Warning: Before connecting an XR battery enclosure, ALL safety instructions in the Safety Sheet (990-3620) must be read, understood and followed. Failure to do so could result in equipment damage, serious injury, or death. Note: This procedure describes how to connect an XR battery enclosure to a UPS running in normal operation. Note: A maximum of two battery enclosures can be connected to the UPS (one XR Battery enclosure with a circuit break

Summary of the content on the page No. 15

Electrical Hazard: Check the DC voltages with a DC voltage multimeter versus the battery voltage before continuing. 7. Turn the XR battery breaker (QFB) to the ON (closed) position. 8. Turn the UPS back into normal operation: a. Turn the static bypass breaker (QM2) to the ON (closed) position. b. Turn the output breaker (QOP) to the ON (closed) position. c. Turn the maintenance bypass breaker (Q3BP) to the OFF (opened) position. d. Turn the UPS battery breaker (QB) to the ON (closed) position.

Summary of the content on the page No. 16

Replace the Batteries Warning: Before battery replacement, ALL safety instructions in the Safety Sheet (990- 3620) must be read, understood and followed. Failure to do so could result in equipment damage, serious injury, or death. Caution: Batteries must be replaced by qualified electricians only. Note: For the replacement of batteries, please refer to the relevant diagram for your configuration under “Appendix” on page 16. Note: Before replacing batteries, make sure that the UPS is running in

Summary of the content on the page No. 17

Specifications Battery Output Battery Description Nom voltage (V) 12 v/block 1 I discharge See the battery input table in the UPS installation manual 990-3618 Nom 2 I discharge See the battery input table in the UPS installation guide 990-3618 Max End Voltage 9.9 v/block 1 Nominal battery discharge current based on rated load and nominal battery voltage. 2 Maximum battery discharge current based on rated load at the end of the discharge. Recommended Cable Sizes Caution: All wiring must compl

Summary of the content on the page No. 18

Recommended Bolt and Lug Size Torque specifications Battery Terminal Bolt size Torque CSB 910-0631 clip 910-0633 M6 5.4 NM (max 8.2 NM) YUASA 912-0001 M5 2.5 NM (max 6 NM) 910-0632 M6 4.8 NM (max 6 NM) 14 MGE™ Galaxy™ 300 10-40 kVA 3:3, 10-30 kVA 3:1 - 380/400/415 V Installation

Summary of the content on the page No. 19

Checklist Make sure that all cardboard and strappings have been removed.  Check that the power wiring is torqued as described in the torque specification table above.  Verify clockwise phase-rotation (BAT+, N and BAT-) and make sure that a neutral connection  is present. Leave a wiring diagram on site for service personnel.  Re-install all wiring access panels on the UPS.  For any optional equipment, refer to product-specific manuals.  Make sure that all battery breakers (on the UPS unit

Summary of the content on the page No. 20

Appendix One-line diagrams Note: Use the below table as a help to find the diagram that fits your system. YUASA CSB 15 KVA 20 KVA/ 40 KVA 15 KVA 30 KVA 40 KVA 60 min 30 KVA 60 min 60 min 60 min 60 min 60 min Part no. 885-4766B 885-4767B 885-4770B 885-4769A 885-4773A 885-4774A Name G3HTBAT1 G3HTBAT2 G3HTBAT3 G3HTBAT1 G3HTBAT2 G3HTBAT3 Battery 12 2 1 2 2 enclosure qty. Note: - marked cables are assembled by the manufacturer. - marked cables are assembled on site by APC by Schneider or a sub co


Alternative user manuals
# User manual Category Download
1 APC 230V User manual Battery Charger 27
2 APC RBC145J User manual Battery Charger 2
3 APC Back UPS 1500 User manual Battery Charger 287
4 APC AP9924 User manual Battery Charger 0
5 APC 865 W User manual Battery Charger 5
6 APC Back UPS 1400 VA User manual Battery Charger 644
7 APC 2200 VA User manual Battery Charger 1
8 APC AP9927 User manual Battery Charger 1
9 APC Back UPS 200 User manual Battery Charger 55
10 APC Back UPS 450 User manual Battery Charger 42
11 APC Back UPS BE325-FR/ User manual Battery Charger 66
12 APC Back UPS BE450G User manual Battery Charger 33
13 APC Back UPS 650 VA User manual Battery Charger 337
14 APC Back UPS BE325-UK User manual Battery Charger 19
15 APC Back UPS 420 VA User manual Battery Charger 38
16 Craftsman 950138 User manual Battery Charger 1
17 Sony AC-L200 User manual Battery Charger 23
18 Sony AC VQ800 User manual Battery Charger 11
19 Sony AC SQ950D User manual Battery Charger 9
20 Sony AC V700A User manual Battery Charger 11