TANDBERG Telepresence T3 119076.02 user manual

User manual for the device TANDBERG Telepresence T3 119076.02

Device: TANDBERG Telepresence T3 119076.02
Category: Home Theater System
Manufacturer: TANDBERG
Size: 7.25 MB
Added : 11/18/2013
Number of pages: 22
Print the manual

Download

How to use this site?

Our goal is to provide you with a quick access to the content of the user manual for TANDBERG Telepresence T3 119076.02. Using the online preview, you can quickly view the contents and go to the page where you will find the solution to your problem with TANDBERG Telepresence T3 119076.02.

For your convenience

If looking through the TANDBERG Telepresence T3 119076.02 user manual directly on this website is not convenient for you, there are two possible solutions:

  • Full Screen Viewing - to easily view the user manual (without downloading it to your computer), you can use full-screen viewing mode. To start viewing the user manual TANDBERG Telepresence T3 119076.02 on full screen, use the button Fullscreen.
  • Downloading to your computer - You can also download the user manual TANDBERG Telepresence T3 119076.02 to your computer and keep it in your files. However, if you do not want to take up too much of your disk space, you can always download it in the future from ManualsBase.
TANDBERG Telepresence T3 119076.02 User manual - Online PDF
Advertisement
« Page 1 of 22 »
Advertisement
Print version

Many people prefer to read the documents not on the screen, but in the printed version. The option to print the manual has also been provided, and you can use it by clicking the link above - Print the manual. You do not have to print the entire manual TANDBERG Telepresence T3 119076.02 but the selected pages only. paper.

Summaries

Below you will find previews of the content of the user manuals presented on the following pages to TANDBERG Telepresence T3 119076.02. If you want to quickly view the content of pages found on the following pages of the manual, you can use them.

Abstracts of contents
Summary of the content on the page No. 1

TANDBERG
Telepresence T3
ROOM REQUIREMENTS
The Room Requirements Description presents the room dimensions
requirements, weights, wall- and ceiling loads, power outlet requirements as
well as the heating, ventilation and air-conditioning (HVAC) requirements for the
TANDBERG Telepresence T3 system.
Independent of whether customers plan to install a TANDBERG Immersive
Room, or create their own, this document is important to read.
Note that the entrance door is not a part of the TANDBERG Immers

Summary of the content on the page No. 2

TANDBERG Telepresence T3 SYSTEM d IMENSIONS 120 3 4 4" 2500 2800 3 1 65 8" 110 " 4 1658 1 65 4" 724 1 28 2" 1650 1500 1650 5 65" 59 8 " 65" 4800 189" 119076.02 TELEPRESENCE T3 ROOM REQUIREMENTS 12.08 PAGE 2/22 T3 system dimensions TANDBERG Telepresence T3

Summary of the content on the page No. 3

TANDBERG ROOM d EPTH REQUIREMENTS Telepresence T3 OPTIMAl ANd MAx IMAl d EPTH Centerline 140 1 5 2" 500 3 19 " 4 2800 4880 4600 1 1 1 192 " 110 " 8 181 " 4 8 1000 3 39 " 8 The 1300 mm is vital and should not be exceeded. Otherwise the floor, the skirting 1300 boards and the wooden panels start to become 1 51 8" visible on the screen image. 1015 40" 140 Baseline 1 5 " 2 Optimal room depth Note! The door is not a part of the TANDBERG Immersive Room Package. The door should be mounted so tha

Summary of the content on the page No. 4

TANDBERG Telepresence T3 MINIMUM ROOM d EPTH REQUIREMENTS Centerline 140 1 5 " 20 2 3 " 4 4400 2800 4120 1 1 1 173 " 110 " 4 162 " 4 4 1000 3 39 " 8 1300 1 51 " 8 1015 40" 140 Baseline 1 5 " 2 Observe that if the room gets smaller, the space between the table and backwall will be tight Min. room depth Note! The door is not a part of the TANDBERG Immersive Room Package. The door should be mounted so that it opens outwards. 119076.02 TELEPRESENCE T3 ROOM REQUIREMENTS 12.08 PAGE 4/22 TANDBERG Tele

Summary of the content on the page No. 5

TANDBERG Telepresence T3 MINIMUM ROOM WId TH REQUIREMENTS 6815 1 268 " 4 Centerline 922,5 4800 922,5 3 3 36 " 189 " 36 " 8 8 85 6645 85 5 3 3 3 " 261 " 3 " 8 8 8 Observe that the room should not have a smaller width than shown since that will prevent a proper installation of the wooden corner panels. Min room width Note! The door is not a part of the TANDBERG Immersive Room Package. The door should be mounted so that it opens outwards. 119076.02 TELEPRESENCE T3 ROOM

Summary of the content on the page No. 6

TANDBERG Telepresence T3 OPTIMUM ANd MAx IMUM ROOM HEIGHT 190 1 7 " 2 2360 2550 7 3 92 " 100 " 8 8 Note that the room is shown with the Telepresence T3 system installed. optimal room height 119076.02 TELEPRESENCE T3 ROOM REQUIREMENTS 12.08 PAGE 6/22 TANDBERG Telepresence T3

Summary of the content on the page No. 7

TANDBERG Telepresence T3 MINIMUM ROOM HEIGHT REQUIREMENTS 40 5 18" 2360 2400 7 1 92 " 94 " 8 2 Note that the room is shown with the Telepresence T3 system installed. minimum room height 119076.02 TELEPRESENCE T3 ROOM REQUIREMENTS 12.08 PAGE 7/22

Summary of the content on the page No. 8

TANDBERG Telepresence T3 MAx IMUM ROOM HEIGHT 290 3 11 " 8 2360 2650 7 3 92 8" 104 8" Note that the room is shown with the Telepresence T3 system installed. maximum room height 119076.02 TELEPRESENCE T3 ROOM REQUIREMENTS 12.08 PAGE 8/22

Summary of the content on the page No. 9

TANDBERG HVAC REQUIREMENTS Telepresence T3 Tip! An average person emits approximately The following HVAC (heating, ventilation, air-conditioning) requirements apply to 65 W at rest. You may want to consider this the TANDBERG Telepresence T3: when calculating the HVAC requirements. • Power consumption System: 1725 W • Power consumption Table: 300 W • Power consumption Lighting: 1300 W • Noise from air -conditioning should be less or equal to 27 dB(A) measured at all seating positions. Not

Summary of the content on the page No. 10

TANDBERG Telepresence T3 HVAC REQUIREMENTS Centerline 675 5 26 " 8 2100 5 82 " 8 2025 3 794" 2247 1 88 " 2 320 5 12 " 8 150 7 58" Baseline Make sure that HVAC mounting neither conflicts with the ceiling lights positions nor the document camera position. The drawing 119082 on page 14 shows the position of the document camera. 2280 3 89 4" 119076.02 TELEPRESENCE T3 ROOM REQUIREMENTS 12.08 PAGE 10/22

Summary of the content on the page No. 11

TANDBERG Telepresence T3 ACOUSTICS REQUIREMENTS It is essential to have a good acoustic environment for the system to provide the true telepresence experience. This means that there should be sufficient sound insulation to minimize noise from adjacent rooms and to ensure that confidential information is kept within the meeting room. A good choice of acoustic materials for the surfaces and low background noise will ensure comfort in long meetings in addition to high speech intelligibility. Y

Summary of the content on the page No. 12

TANDBERG POWER OUTl ET f USE Telepresence T3 REQUIREMENTS Note! The table lists minimum fuse The following minimum power outlet fuse requirements apply to the TANDBERG requirements. All electrical work must Telepresence T3: be done by electricians with local knowledge. ITEM WATT PlACEMENT fUSE ON/Off SWITCH T1 Module × 3 2400 Back wall A 1 Presentation 60 Back wall A 1 splitter × 2 Table power outlet × 6 2400 Back wall B 2 Note! Outside the room—adjacent to the entrance—there shall be an

Summary of the content on the page No. 13

TANDBERG El ECTRONIC VERSIONS Of Telepresence T3 TECHNICAl d RAWINGS The technical drawings on the following pages are also available in electronic formats as pdf, dwg and dxf. To obtain copies of these drawings, send an e-mail to tandberg@tandberg.com The following drawings are available: • 119082 T3 Ceiling • 119083 T3 Electrical System • 119083-US T3 Electrical System US • 119084 T3 Furniture Plan • 119086 T3 Short Structure • 119087 T3 Long Structure • 119088 T3 Structural Elements

Summary of the content on the page No. 14

Centerline Installation area for ceiling mounted document camera (see separate installation guide) No air condition in this area. Area where installation of aircondition should be avoided 1000 1 39 " 2 675 1 26 " 2 2100 1000 1 2240 1 82 " 2025 2 39 " 88" 2 1 79 " 2 2247 150 1 88 " 2 6" 320 1 12 " 2 4930 194" www.tandberg.com TANDBERG Doc. Title: T3 Ceiling Related Tandberg Product - TANDBERG T3 Note! The door is not a part of the TANDBERG Immersive Room Drw. No.: 119082 Date: 04.11.08 Package.

Summary of the content on the page No. 15

140 1 Customers Lan Video Lan 5 " 2 5 4 Hardwire outlet for light, A A A B C A A B C mounted sideways on wood lattice. On floor Cable Routing On Floor Cable Routing - Transport cables from T3 - Transport cables from T3 Power / AV / Lan 85 3 Centerline 3 " Note that the fire 8 A sign informing about the emergency switch is a Fire emrgency switch should 400 control switch only. The 3 be put on the inside wall next 15 " 4 actual switching should to the door. For more on the take place i

Summary of the content on the page No. 16

140 1 Customers Lan Video Lan 5 " 2 8 8 Hardwire outlet for light, A A A A A A B C A A A A A A B C mounted sideways on wood lattice. On floor Cable Routing On Floor Cable Routing - Transport cables from T3 - Transport cables from T3 Power / AV / Lan 85 Centerline 3 3 " 8 400 3 15 " 4 1885 885 85 1 7 3 74 " 34 " 3 " 4 8 8 Fire Emergency switch Doc Cam Outlet (Controls fuse groups A,B and C) 4600 1 181 " 8 Master Panel Light 760 7 29 " 8 Doc Cam Capture Area Doc Cam location in Max. size 760 x

Summary of the content on the page No. 17

TANDBERG Telepresence T3 140 Centerline 1 5 " 2 3512,50 1 138 " 2 rear edge of foot plate 4098,50 1115 1 44" 161 " 2 2400 1112,50 1 94 " 44" 2 4600 181" 85 1 3 " 2 2250 1 88 " 2 10 740 Optional Second row 1 " 29" 2 20 140 1" 1 5 " 2 www.tandberg.com TANDBERG Doc. Title: T3 Funiture Plan Related Tandberg Product - TANDBERG T3 Drw. No.: 119084 Date: 04.11.08 Sign.: Revision: 01 Unit: mm / " Scale: 1:25 Sheet Size: A3 119076.02 TELEPRESENCE T3 ROOM REQUIREMENTS 12.08 PAG

Summary of the content on the page No. 18

2025 955 1900 TANDBERG 1 1 300 300 79 " 37 " 75" 2 2 12" 12" Telepresence T3 945 2360 37" 93" 625 1 24 " 2 Gap between the Frame around area for insulation boards vertical lattices 300 - approx. 600mm 1000 977 1026,5 Frame around area for insulation boards 1 1 1 39 " 38 " 40 " 300 2 2 2 300 12" 12" Distance of the first lattice from corner lattice - 300 (11,8) 945 37" 2311 91" 625 1 24 " 2 www.tandberg.com TANDBERG T3 Short Structure Doc. Title: Related Tandberg Prod

Summary of the content on the page No. 19

TANDBERG Telepresence T3 3596,70 1 141 " 2 3056,70 1 120 " 1485 Frame around area for insulation boards Centerline 2 1 58 " 2 2360 93" 2260 89" 2090 1 82 " 2 Area for mounting/changing Led www.tandberg.com TANDBERG Doc. Title: T3 Long Structure Related Tandberg Product - TANDBERG T3 Drw. No.: Date: 119087 04.11.08 Sign.: Revision: 01 Unit: mm / " Scale: 1:25 Sheet Size: A3 119076.02 TELEPRESENCE T3 ROOM REQUIREMENTS 12.08 PAGE 19/22

Summary of the content on the page No. 20

TANDBERG Telepresence T3 80 98,50 Floor power outlet 3" 4" recommended hole Structural element Base opening 1557 Base opening 1 61 " 2 615 Structual element 1193 24" 47" 75 3" Base openings Center line 3757 2132 3833 148" 84" 151" TANDBERG www.tandberg.com Doc. Title: T3 Structural Elements Related Tandberg Product - TANDBERG T3 A A Drw. No.: 119088 Date: 04.11.08 Sign.: Revision: 01 Unit: mm / " Scale: 1:25 Sheet Size: A3 119076.02 TELEPRESENCE T3 ROOM REQUIREMENTS


Alternative user manuals
# User manual Category Download
1 TANDBERG Edge D13922.06 User manual Home Theater System 2
2 Sony 3-285-995-11(1) User manual Home Theater System 36
3 Sony 3-298-611-11(1) User manual Home Theater System 4
4 Sony 3-299-549-12(1) User manual Home Theater System 11
5 Sony 3-283-036-11(3) User manual Home Theater System 5
6 Sony 3-094-057-22(1) User manual Home Theater System 4
7 Sony 3-295-947-01(1) User manual Home Theater System 1
8 Sony 3-283-375-11(2) User manual Home Theater System 4
9 Sony 3-299-549-11(1) User manual Home Theater System 0
10 Sony 4-130-029-13(1) User manual Home Theater System 1
11 Sony 4-178-254-11(1) User manual Home Theater System 3
12 Sony 4-147-228-12(1) User manual Home Theater System 1
13 Sony 4-178-247-11(1) User manual Home Theater System 2
14 Sony 5950DP User manual Home Theater System 0
15 Sony 490S User manual Home Theater System 5