Air Boss MP 600M
Vertical Air Flow Mist Precipitator
Installation
Operation
Service
Please read these instructions carefully for
trouble free operation and to get the most out of
your purchase. For further information
concerning this project, contact your local Trion
representative.
101 McNeill Road • Sanford, NC 27330
Phone: 800-884-0002 • Fax: 800-458-2379 • Email: sales@trioninc.com
www.trioninc.com
Manual Part No. 153632-001 • June 2002
Summary of the content on the page No. 2
DESCRIPTION POSITION AIR CLEANER CABINET The Trion MP 600M air cleaner is designed to capture machine tool fluids, metal dust and smoke for clean air To reduce weight for ease in handling, remove the pre- filtration. It can be mounted to a wall, frame, platform, or filters, main filters and place them safely aside. Position directly on the machine tool. Mist, dust, and smoke are the cabinet in the designated location giving drawn from each machine through an external duct into consideration to f
Summary of the content on the page No. 3
Figure 1 - MP 600M High Static SPECIFICATIONS STANDARD OPTIONAL MP600M and High Static MP 600M Voltage 115 208-230 208-230/460 575 115/230 Phase 1 1 3 3 1 HZ 60 60 60 60 60 AMPS 17 9.4-8.5 4.9-4.6/2.3 1.9 8.0-4.0 Motor ½ hp 1 ½ hp 1 ½ hp 1 ½ hp ½ hp CFM 600 600 600 600 600 Shipping Weight 175 lbs 225 lbs. 225 lbs. 225 lbs. 225 lbs. 3
Summary of the content on the page No. 4
Figure 2 – Dimension and Access Data GENERAL SAFETY INFORMATION INSTALLATION Prior to beginning installation, select the location for the WARNING: RISK OF ELECTRIC SHOCK air cleaner. The air cleaner should be located as close to These serving instructions are for use by qualified the contaminant source as possible. The air enters the personnel only, To reduce the risk of electric shock, do air cleaner from the bottom (or specified side with inlet not perform any servicing other than that contain
Summary of the content on the page No. 5
CAUTION: TRAPEZE MOUNT When using flex duct connections with other than straight runs of duct, 45 degree elbows should be used 1. Four (4) through holes are provided in the inlet to connect ducting to flanged collars to maximize air plenum bottom flange to which two (2) mounting flow. channels are affixed with 3/8” hardware (not provided). ENCLOSED MACHINING CENTER DIRECT MOUNT 2. The MP600M can be suspended from overhead with chains or 3/8” diameter (minimum) rods (not 1. When mounting directl
Summary of the content on the page No. 6
Figure 4 - MP 600M Inlet Plenum and Stand Options 6
Summary of the content on the page No. 7
Figure 5 – Wiring Diagrams for Model MP 600M 7
Summary of the content on the page No. 8
Figure 6 – Wiring Diagram 8
Summary of the content on the page No. 9
Figure 6A – Motor Wiring Diagram 9
Summary of the content on the page No. 10
The MP600M is wired directly from the power source the pressure reading when the pre-filter is replaced. At with 20 amps minimum, service utilizing 3 wire grounded that point, the unit would be allowed to run until 3.1” w.c. cable, (115-208-230-460-575/60/3) for single 208- and both filters replaced. 230/60/1, phase service and 4 wire grounded cable for 3 phase service, routed through appropriate conduit (See NOTE: figure 5 wiring diagram). All wiring must be connected in The unit can continue t
Summary of the content on the page No. 11
A. Thoroughly inspect the main and pre- F. Check rubber gasketing and adhesion of filter for holes, tears or any other gasketing to cabinet surfaces. condition that might allow air to leak through or around the filter. Replace the 6. When soaking of impinger is complete, rinse filters if any damage is found. with clean water and allow to dry. B. Inspect the cabinet. Remove all foreign 7. Reinstall impinger and filters into the unit. debris and dirt accumulation inside the 8. Switch unit on at th
Summary of the content on the page No. 12
Figure 7 – MP 600M Unit Assembly 12
Summary of the content on the page No. 13
Figure 7A – Unit Assembly Parts List MP 600M MP 600M HS Qty Qty Item Part No. Description Remarks 1 1 1 353613-001 Cabinet Assembly 1 1 2 354477-001 Access Door 1 1 3 253619-001 Blower Housing Cover 2 2 5 248956-002 Clamping Knob 2 2 6 321449-002 Nut Retainer 2 2 7 146442-002 Hinge 6’ 6’ 8 224779-015 Gasket ¼” x 1” 1 - 9 247350-101 Blower Motor Assembly 120/240/50-60/1 Feature & Option 1 - 10 253631-001 Adapter Plate Feature & Option - 1 11A 150825-001 Motor 115/208/-230/60/1 Feature & Option -
Summary of the content on the page No. 14
Figure 8 – Filter Locking Mechanism - Access opening increased 3.5” height - 16 GA tapered filter retainer welded in door and cabinet rear - As door closes, filter gasket is compressed and seal is made 14
Summary of the content on the page No. 15
Figure 9 – System Performance Curves (without Filters) Flow – CFM @ 60 Hz 3 Added Static @ Filter 600 CFM 1000 m /hr Filter Inches W.C. Pascals 99.97% DOP HEPA 1.00 250 95% DOP 0.35 87 90-95% ASHRAE 0.20 50 80-85% ASHRAE 0.15 37 60-65% ASHRAE 0.10 25 45-55% ASHRAE 0.05 13 Impinger 0.15 37 Aluminum Mesh Pre-Filter 0.05 13 Glass Pre-Filter 0.00 1 ** To determine performance with various filter combinations, add total static of filters (from table) 15
Summary of the content on the page No. 16
WARRANTY All Trion air cleaners are warranted for component failure and workmanship for a period of three years after purchase. Do not return defective parts without prior permission from the factory. Contact your local Trion Distributor or Trion Customer Service Department at 1-800-884-002 of Fax 1-800-458-2379 to obtain material return authorizations and service information. Corporate Office: 101 McNeill Road • Sanford, NC 27330 Form No. 153632-001 Phone: 800-884-0002 • Fax: 800-458-237