Installation Instructions for
Aga BF Gas Fired Cooker Models
GC, GCB, GE and GEB
Gas Fired Cookers
FOR USE IN GB & IE
PLEASE READ THESE INSTRUCTIONS BEFORE INSTALLING YOUR AGA
Consumer Protection
Firebricks, Fuel beds, Artificial Fuels - when handling use disposable
As responsible manufacturers we take care to make sure that our gloves.
products are designed and constructed to meet the required safety
Fire Cement - when handling use disposable gloves.
standards when properly installed and used.
ページ2に含まれる内容の要旨
V = VENT PIPE S = FLUE PIPE AB C D E F G H J K LM NP Q R S T U V mm 987 889 851 679 41 1330 756 1125 39 3 698 499 127 41 530 116 770 484 328 828 Models GC and GCB Balanced flue GC GCB NATURAL G20 MAXIMUM HEAT INPUT 5kW 5kW Thermostat Bypass 100 or 120 120 or 140 Main Burner Injector 285 285 Pilot Injector N35 N35 Inlet Pressure G20 20mbar 20mbar PROPANE G31 MAXIMUM HEAT INPUT 5kW (357g/h) 5kW (357g/h) Thermostat Bypass 60 or 80 80 or 100 Main Burner Injector 180 180 Pilot Injector L23 L23 Inlet
ページ3に含まれる内容の要旨
V = VENT PIPE S = FLUE PIPE AB C D E F G H J K LM NP Q R S T U V mm 1487 889 851 679 41 1330 756 1125 39 3 698 632 591 51 67 116 770 484 328 828 Models GE and GEB Balanced flue GE GEB NATURAL G20 MAXIMUM HEAT INPUT 5kW 5.8kW Thermostat Bypass 100 or 120 120 or 140 Main Burner Injector 285 330 Pilot Injector N35 N35 Inlet Pressure G20 20mbar 20mbar PROPANE G31 MAXIMUM HEAT INPUT 5kW (357g/h) 5.8kW (414g/h) Thermostat Bypass 60 or 80 80 or 100 Main Burner Injector 180 200 Pilot Injector L23 L23 In
ページ4に含まれる内容の要旨
FLUE SYSTEM The terminal is suitable for wall thicknesses from 228mm to 600mm cut size Should the installation of the appliance be in an unusual location or restricted space, special procedures may be necessary. Terminal Position The minimum acceptable spacings from the terminal to obstructions and ventilation openings are as shown in the diagram. Where the terminal is fitted within 600mm below plastic guttering an aluminium shield 1500mm long should be fitted to the underside and immediately be
ページ5に含まれる内容の要旨
AIR SUPPLY THE HOT WATER SYSTEM Kitchen or Internal Space Air Supply (Models GCB and GEB Only) Where the appliance is to be installed in a kitchen or In a domestic hot water system, the hot water storage internal space, it does not require the kitchen or internal vessel must be of the indirect cylinder of calorifier type. space containing it to have a permanent air vent. The hot water storage vessel should be insulated, preferably, with not less than 75mm thick mineral fibre, or its equivalent.
ページ6に含まれる内容の要旨
6 DESN 510252 ‘A’ 5 OFF ON COMMISSIONING LIGHTING THE BURNER - Fig. 2 CAUTION: NO SMOKING OR NAKED LIGHTS Open the outer burner door to expose the gas control OFF combination valve. CAUTION: BEFORE LIGHTING: ENSURE THAT THE GAS VALVE CONTROL KNOB 2 IS SET IN THE OFF POSITION (SEE FIG. A) AND COMBUSTION DISCHARGE SAFETY DEVICE BUTTON IS FIG A DEPRESSED. 1. Turn off union gas cock 1. Test the gas installation from the meter cock for soundness and purge. IGNITION 2. Turn on gas supply to cooker an
ページ7に含まれる内容の要旨
NOTE: AFTER SEVERAL HOURS THE HEAT INSTRUCTIONS INDICATOR SHOULD BE ON OR ABOUT THE BLACK LINE IN THE SILVER SECTION. IT MAY BE NECESSARY TO ADJUST THE CONTROL Hand these and the Operating Instructions to the User for KNOB SLIGHTLY IN THE GREEN BAND TO ACHIEVE retention and instruct in the safe operation of the THIS. appliance. Advise the User of the precautions necessary to prevent IF THE FLAME HAS EXTINGUISHED FOR WHATEVER damage to the Domestic Hot Water System and to be REASON, WAIT THREE MI
ページ8に含まれる内容の要旨
With Aga's policy of continuous product improvement, the Company reserves the right to change specifications and make modifications to the appliance described and illustrated at any time. Aga For further advice or information contact your Station Road local distributor/stockist. Ketley Telford Shropshire TF1 5AQ www.aga-web.co.uk www.agalinks.com England www.agacookshop.co.uk 8