SED2 Advanced Operator Panel (AOP)
Operating Instructions
ページ2に含まれる内容の要旨
ページ3に含まれる内容の要旨
SED2 AOP Operating Instructions 125-3206 Rev. 1, September, 2002
ページ4に含まれる内容の要旨
ページ5に含まれる内容の要旨
Rev. 1.0, September, 2002 NOTICE The information contained within this document is subject to change without notice and should not be construed as a commitment by Siemens Building Technologies, Inc. Siemens Building Technologies, Inc. assumes no responsibility for any errors that may appear in this document. All software described in this document is furnished under a license and may be used or copied only in accordance with the terms of such license. WARNING This equipment generat
ページ6に含まれる内容の要旨
European Low Voltage Directive The SED2 VFD product range complies with the requirements of the Low Voltage Directive 73/23/EEC as amended by Directive 98/68/EEC. The units are certified for compliance with the following standards: EN 60146-1-1 Semiconductor VFDs - General requirements and line commutated VFDs EN 60204-1 Safety of machinery - Electrical equipment of machine European Machinery Directive The SED2 VFD series does not fall under the scope of the Machinery Directive.
ページ7に含まれる内容の要旨
Table of Contents Table of Contents How to Use this Manual ...............................................................................................1 Manual Organization .................................................................................................1 Manual Notations.......................................................................................................2 Where To Send Comments ..........................................................................
ページ8に含まれる内容の要旨
SED2 AOP Operating Instructons AOP Setup & Configuration.........................................................................................24 Setup Menu ...............................................................................................................24 Backlighting ...............................................................................................................24 Screen Contrast.................................................................................
ページ9に含まれる内容の要旨
How to Use this Manual How to Use this Manual The Advanced Operator Panel (AOP) enhances the user interface and communications capability of the SED2 Variable Frequency Drives (“SED2 VFD”). Manual Organization This manual contains the following sections: − How to Use this Manual, describes the organization of this manual and symbols used throughout this manual. − AOP Overview, shows the AOP main menu and details the AOP function keys. − AOP Startup & Initialization, describes AOP powe
ページ10に含まれる内容の要旨
SED2 AOP Operating Instructons Manual Notations Notation Symbol Meaning DANGER: Indicates that personal injury or loss of life may occur if you do not perform a procedure as specified. WARNING: Indicates that equipment damage, or loss of data may occur if you do not perform a procedure as specified. CAUTION: Indicates that equipment damage, or loss of data may occur if you do not perform a procedure as specified. NOTES: (no symbol) Provides other important information or helpful
ページ11に含まれる内容の要旨
AOP Overview AOP Overview AOP Menu Structure The menus available on the AOP display depend on the currently active operating mode. The following diagram shows the menu structure when the AOP is in either the Local or Master operating mode. MAIN MENU (Local and Master Modes) OPERATE DIAGNOSTICS PARAMETERS SELECT GROUP: ALL PARAMETERS NOT DEFINED MODE LOCAL (1 Drive) INVERTER MASTER (>1 Drive) UPREAD MOTOR DOWNLOAD INTERNAL SPEED SENSOR SLAVE TECHNICAL APPLICATION/UNIT PC MODE NOT DEFINED
ページ12に含まれる内容の要旨
SED2 AOP Operating Instructions Key Functions NOTE: This symbol is used throughout this manual to indicate a special keypad function. Key/ Functional Description Function Stops the motor. OFF1 Press this button to stop the SED2 within the selected ramp-down time. As part of the factory setting, this function is enabled for manual mode. OFF2 Press this button twice (or once with sustained pressure) to cause the motor to coast freely to a standstill. This function is enabled in th
ページ13に含まれる内容の要旨
AOP Overview Key/ Functional Description Function Change Quickly change a single digit of a parameter value as follows: Single 1. Ensure you are in the parameter value changing level. Parameter Digit 2. Press and the right hand digit blinks. 3. If desired, press or to change the value of this digit. 4. Press again and the next digit blinks. 5. Perform steps 3 and 4 until the required value appears. 6. Press to leave the parameter value changing level. Siemens Building
ページ14に含まれる内容の要旨
SED2 AOP Operating Instructions AOP Start-Up & Initialization Important Notes CAUTION: • You can mount or remove the AOP while power is applied to the SED2 VFD. • You must set Command Source P0700[1]=4 (USS on BOP link or AOP) before the AOP can start or stop an attached SED2 VFD. • On setting the AOP as the command source, you must set USS Telegram Off Time for Serial Interface BOP Link P2014[1]=5000 (5 seconds) to prevent unexpected drive operation. In this mode, removal of the
ページ15に含まれる内容の要旨
AOP Start-Up & Initialization Language Selection 1. The AOP provides the capability to display information in five different languages. NOTE: Prior to language selection, the AOP has no control over the SED2 VFD. CAUTION: Memory Limitation: The delivered AOP supports five European languages: English, German, French, Spanish, and Italian. Due to internal memory limitations, you should delete one of these languages in order to upload the specified ten parameter sets that can be h
ページ16に含まれる内容の要旨
SED2 AOP Operating Instructions Quick Commissioning NOTE: Simultaneously press and , at any time, to display the main menu. The following table describes the main menu items. Menu Item Description Operate Displays the current status of the SED2 VFD/motor. Diagnostics Displays a recent fault history. Parameters Allows you to select a parameter group (similar to Parameter Filter P0004) and to configure individual parameters. Mode Allows you to select the AOP mode of operation as follow
ページ17に含まれる内容の要旨
AOP Start-Up & Initialization 4. Use and to scroll through the parameters and to highlight Command Source P0700. Press to confirm the selection and the cursor advances to the parameter index. Use and to scroll through the indexes for P0700 and to highlight P0700[1] (index 1). Press to confirm the selection and the cursor advances to the parameter value. Use and to set P0700[1]=4 (USS on BOP/AOP local link). Press to confirm the setting and the cursor returns to the paramet
ページ18に含まれる内容の要旨
SED2 AOP Operating Instructions The AOP display the current status of the SED2 and motor. The following table explains information on this display. STOPPED Fn r0000 F=0.00Hz P I=0.0A RPM=0 M=0% V=0.0V Table 1. Status Information of an AOP Display with an Operating SED2. Data Description STOPPED Indicates the motor connected to the SED2 is not running (pulses disabled). RUNNING Indicates the motor connected to the SED2 is running (pulses enabled). Indicates a fault condition has occ
ページ19に含まれる内容の要旨
AOP Applications AOP Applications NOTES: 1. If the AOP is the command source for the SED2, set USS Telegram Off Time for Serial Interface BOP Link P2014[1]=5000 (5 seconds). To do this, first set P0003=3. The P2014[1]=5000 setting causes the drive to trip if communications with the AOP control source is lost. 2. If you have problems connecting to the SED2 drives, set the Auto Baud to OFF and the default baud rate to the same as the SED2. Single Drive Control Using the AOP Per default
ページ20に含まれる内容の要旨
SED2 AOP Operating Instructions 2. Configure the SED2 VFDs for network use. a. Set the Command Source P0700[1]=5 (USS on Com link). This sets the control over the USS link on the communications port. b. Assign each drive a unique RS-485 USS address in the range of 0 to 30. To do this set User Access Level P0003=3 (expert) and use USS Address for Serial Interface Com Link P2011[0] to assign a unique address to each SED2 VFD. c. If using the AOP as the normal control means for the SED2 V