ページ1に含まれる内容の要旨
680210-YTG-B-0311
DESCRIPTION
The Air Handler line offers the ultimate in comfort, sound and
application flexibility. The air handler is shipped ready to be
installed in upflow, horizontal left or right position, with minor
adjustments. No special kits are required to install this deluxe
product.
All JCI Unitary Products air handlers and coils use a TXV to pro-
vide our customers with the optimum performance and refriger-
ant control. Air handlers are shipped with “Flex-coils” without a
TECHNICA
ページ2に含まれる内容の要旨
680210-YTG-B-0311 DIMENSIONS & DUCT CONNECTION DIMENSIONS F J 13” K Blower Compartment Top Outlet Dimensions A Circuit Breaker Panel Refrigerant D Drain Connections Connections for Upflow Applications 7-11/32” E 18-9/32” C Bottom Inlet 1-1/2” Dimensions B Filter Drain Pan Connections Access for Horizontal Applications Dimensions Dimensions Wiring Knockouts Refrigerant Connections Models ABC JK Line Size DE F Height Width Depth Power Control Liquid Vapor AHE18B3XH21 46” 17 1/2” 16 1/2” 13-29/32"
ページ3に含まれる内容の要旨
680210-YTG-B-0311 COOLING CAPACITY MBH@ Evaporator Temperature and Corresponding Pressure °F/PSIG Entering Air °F Models Rated CFM (Dry/Wet Bulb) 35/61.5 40/68.5 45/76.0 50/84.0 FULL-CASED “A” TYPE MULTI-POSITION 72 37.9 33.7 28.3 23.3 67 31.8 27.0 22.5 17.6 610 62 26.4 21.5 16.7 11.6 57 20.7 18.4 15.8 13.5 AHE18B3XH21 72 49.7 43.2 36.9 28.4 67 42.1 35.1 28.8 22.5 850 62 33.7 28.0 21.4 14.7 57 26.5 23.8 20.3 16.9 72 38.7 34.4 30.1 24.7 67 33.6 28.9 23.9 18.9 585 62 27.2 22.7 17.8 12.8
ページ4に含まれる内容の要旨
680210-YTG-B-0311 COOLING CAPACITY (Continued) MBH@ Evaporator Temperature and Corresponding Pressure °F/PSIG Entering Air °F Models Rated CFM (Dry/Wet Bulb) 35/61.5 40/68.5 45/76.0 50/84.0 FULL-CASED “A” TYPE MULTI-POSITION 72 56.6 51.1 42.8 35.6 67 48.6 41.1 34.8 27.6 820 62 39.4 33.0 26.0 18.3 57 30.5 26.6 23.1 19.6 72 65.7 61.0 52.7 42.9 67 58.0 49.6 41.1 32.1 1000 62 46.7 38.9 30.4 21.8 57 36.4 31.6 27.6 23.3 AHE42D3XH21 72 67.9 71.4 60.2 48.8 67 65.6 56.9 47.1 37.1 1180 62 53.8
ページ5に含まれる内容の要旨
680210-YTG-B-0311 APPLICATION FACTORS - RATED CFM VS. ACTUAL CFM 80% 90% 100% 110% 120% % Of Rated Airflow (CFM) 0.96 0.98 1.00 1.02 1.03 Capacity Factor PHYSICAL & ELECTRICAL DATA - COOLING ONLY (60 Hz) Models AHE18B AHE24B AHE30B AHE36C AHE42D AHE48D AHE60D Blower - Diameter x Width 10 x 8 10 x 8 10 x 8 11 x 10 11 x 10 11 x 10 11 x 10 HP 1/3 HP 1/3 HP 1/3 HP 1/2 HP 1/2 HP 3/4 HP 3/4 HP Motor Nominal RPM 1050 1050 1050 1050 1050 1050 1050 Voltage 208/230 208/230 208/230 208/230 208/230 208/230
ページ6に含まれる内容の要旨
680210-YTG-B-0311 ELECTRICAL DATA - 208/230-1-60 1 kW Staging Total Heat Heater Max. ECM Min. Models kW MBH W1 Only W1 + W2 Models* Static Speed Tap 208V 230V 208V 230V 208V 230V 208V 230V 6HK*6500206 0.3 Med Low #2 1.8 2.2 6.1 7.5 1.8 2.2 1.8 2.2 6HK*6500506 0.3 Med Low #2 3.6 4.4 12.3 15.0 3.6 4.4 3.6 4.4 AHE18B3XH21 6HK*6500806 0.3 Med High #4 5.8 7.0 19.7 24.0 5.8 7.0 5.8 7.0 6HK*6501006 0.3 Med High #4 7.2 8.8 24.6 29.9 7.2 8.8 7.2 8.8 6HK*6500206 0.3 Low #1 1.8 2.2 6.1 7.5 1.8 2.2 1.8 2.2
ページ7に含まれる内容の要旨
680210-YTG-B-0311 ELECTRICAL DATA - (FOR SINGLE SOURCE POWER SUPPLY) - COPPER WIRE - 208/230-1-60 Field Wiring Heater Heater 1 Models Amps Min. Circuit Ampacity 75°C Wire Size - AWG Max. O.C.P. Amps/Type Models* 240V 208V 230V 208V 230V 208V 230V 6HK*6500206 10.0 14.33 15.48 15 20 12 12 6HK*6500506 20.0 25.17 27.46 30 30 10 10 AHE18B3XH21 6HK*6500806 32.0 38.17 41.83 40 45 8 8 6HK*6501006 40.0 46.83 51.42 50 60 8 6 6HK*6500206 10.0 14.33 15.48 15 20 12 12 6HK*6500506 20.0 25.17 27.46 30 30 10
ページ8に含まれる内容の要旨
680210-YTG-B-0311 1 ELECTRICAL DATA - (FOR MULTI-SOURCE POWER SUPPLY) - COPPER WIRE - 208/230-1-60 2 Min. Circuit Ampacity 75°C Wire Size - AWG Max. O.C.P. Amps/Type Circuit Circuit Circuit Heater Models Models 1st 2nd 1st 2nd 1st 2nd 208/230 208/230 208/230 208/230 208/230 208/230 6HK16501306 37.5/41.3 22.3/24.2 40/45 25/25 8/8 12/12 AHE24B3XH21 6HK16501506 43.3/47.8 25.1/27.4 45/50 30/30 8/8 10/10 6HK16501306 37.5/41.3 22.3/24.2 40/45 25/25 8/8 12/12 AHE30B3XH21 6HK16501506 43.3/47.8 26.8/27.
ページ9に含まれる内容の要旨
HEAT 680210-YTG-B-0311 Electrical Data - (For Single Source Power Supply) - Copper Wire - 208/230-3-60 Field Wiring Heater Heat Kit - 1 Models Amps Min. Circuit Ampacity 75°C Wire Size - AWG Max. O.C.P. Amps/Type Three Phase 240V 208V 230V 208V 230V 208V 230V AHE24B3XH21 6HK06501525 34.6 41.0 44.95 45 50 8 8 AHE30B3XH21 6HK06501525 34.6 41.0 44.95 45 50 8 8 6HK06501525 34.6 42.6 46.57 45 50 8 8 AHE36C3XH21 6HK16502025 46.2 55.2 60.47 60 70 6 4 6HK06501525 34.6 42.6 46.57 45 50 8 8 AHE42D3XH21
ページ10に含まれる内容の要旨
680210-YTG-B-0311 TYPICAL THERMOSTAT CONNECTION 10 Johnson Controls Unitary Products
ページ11に含まれる内容の要旨
680210-YTG-B-0311 TYPICAL THERMOSTAT WIRING FOR 2-STAGE HEAT PUMP WITH ECM BLOWER MOTOR Johnson Controls Unitary Products 11
ページ12に含まれる内容の要旨
680210-YTG-B-0311 AIR FLOW AIR FLOW DATA - 60 Hz MODELS - 208 VOLT 1 Blower CFM @ External Static Pressure - IWC Models Motor Speed 0.10 0.20 0.30 0.40 0.50 0.60 0.70 208 Volt High #5 1074 1029 999 954 911 865 812 Med High #4 895 846 802 759 701 630 526 AHE18B3XH21 Med #3 663 610 556 482 334 219 173 Med Low #2 630 466 346 196 170 67 23 Low #1 630 466 346 196 170 67 23 High #5 1147 1107 1076 1040 992 942 861 Med High #4 1009 974 941 903 859 811 762 AHE24B3XH21 Med #3 826 785 744 690 639 566 501
ページ13に含まれる内容の要旨
680210-YTG-B-0311 AIR FLOW DATA - 60 Hz MODELS - 230 VOLT 1 Blower CFM @ External Static Pressure - IWC Models Motor Speed 0.10 0.20 0.30 0.40 0.50 0.60 0.70 230 Volt High #5 1075 1041 1003 970 930 885 842 Med High #4 895 845 808 767 709 647 561 AHE18B3XH21 Med #3 663 618 557 490 348 267 192 Med Low #2 629 468 356 197 175 68 23 Low #1 629 468 356 197 175 68 23 High #5 1156 1120 1093 1056 1014 951 862 Med High #4 1021 987 952 918 873 836 787 AHE24B3XH21 Med #3 829 789 754 698 654 585 532 Med Low
ページ14に含まれる内容の要旨
Subject to change without notice. Published in U.S.A. 680210-YTG-B-0311 Copyright © 2011 by Johnson Controls, Inc. All rights reserved. Supersedes: 680210-YTG-A-0211 Johnson Controls Unitary Products 5005 York Drive Norman, OK 73069