GENERAL
All Models 1/2 - 5 tons ship as factory-charged packages.
Horizontal units are designed for suspended ceiling mount-
ing. Horizontal models are shipped with ‘straight-through’
evaporator fan discharge as standard. Fan orientation is
field convertible to side discharge. Vertical units are
designed for free-standing floor mounting. All units are
TECHNICAL GUIDE
completely factory wired and pre-piped. Water supply,
water outlet, and condensate drain connections are via
HIG
ページ2に含まれる内容の要旨
359583-YTG-B-0208 ELECTRICAL/CONTROLS able, complete with an alarm output contact. An optional remote management package allows the unit All units are completely factory wired with all necessary to be controlled by an external source. operating controls. A 24 volt control circuit, with over- size transformer, is provided for field connection. Units FILTERS are designed to operate with conventional thermostat control interface. The reversing valve solenoid coil All models are shipped with 1 inch
ページ3に含まれる内容の要旨
359583-YTG-B-0208 TABLE 1: GENERAL DATA Model Series 007 009 012 018 024 030 036 048 060 Nominal Cooling (Ton) 0.5 0.75 1.0 1.5 2.0 2.5 3.0 4.0 5.0 Cooling Performance Cooling Capacity (BTUH) 7000 9000 12800 18100 24200 30800 36100 48200 59000 EER 12.4 13.0 12.6 14.4 14.4 13.5
ページ4に含まれる内容の要旨
359583-YTG-B-0208 TABLE 2: RP 007 @200 CFM NOMINAL AIRFLOW VERTICAL AND HORIZONTAL MODELS Cooling Heating EWT WPD GPM EWT(ºF) GPM EAT TC SC THR EAT HC H Absrp. (ºF) (PSI) KW KW (db/wb) (MBH) (MBH) (MBH) (db) (MBH) (MBH) 75/62 7.1 5.1 0.51 8.8 60 7.2 0.59 5.2 1.0 0.8 80/67 7.7 5.0 0.53 9.5 1.0 70 7.2 0.63 5.0 85/72 8.3 4.9 0.55 10.2 80 7.1 0.67 4.8 50 50 75/62 7.3 5.2 0.46 8.9 60 7.5 0.60 5.4 1.5 2.0 80/67 8.1 5.2 0.48 9.7 1.5 70 7.4 0.64 5.2 85/72 8.8 5.1 0.50 10.5 80 7.3 0.68 5.0 75/62 6.9 5
ページ5に含まれる内容の要旨
359583-YTG-B-0208 TABLE 3: RP 009 @ 300 CFM NOMINAL AIRFLOW VERTICAL AND HORIZONTAL MODELS Cooling Heating EWT WPD GPM EWT(ºF) GPM EAT TC SC THR EAT HC H Absrp. (ºF) (PSI) KW KW (db/wb) (MBH) (MBH) (MBH) (db) (MBH) (MBH) 75/62 9.1 7.0 0.55 11.0 60 8.2 0.62 6.0 1.35 1.4 80/6
ページ6に含まれる内容の要旨
359583-YTG-B-0208 TABLE 4: RP 012 @400 CFM NOMINAL AIRFLOW VERTICAL AND HORIZONTAL MODELS Cooling Heating EWT WPD GPM EWT(ºF) GPM EAT TC SC THR EAT HC H Absrp. (ºF) (PSI) KW KW (db/wb) (MBH) (MBH) (MBH) (db) (MBH) (MBH) 75/62 13.2 10.0 0.80 15.9 60 11.7 0.87 8.7 1.8 2.1 80/67 14.4 9.9 0.83 17.2 1.8 70 11.6 0.93 8.4 85/72 15.4 9.6 0.89 18.4 80 11.4 0.98 8.1 50 50 75/62 13.4 10.1 0.76 15.9 60 12.4 0.90 9.4 3.0 5.3 80/67 14.7 10.0 0.78 17.3 3.0 70 12.3 0.96 9.0 85/72 16.0 9.8 0.80 18.7 80 12.1 1
ページ7に含まれる内容の要旨
359583-YTG-B-0208 TABLE 5: RP 018 @ 600 CFM NOMINAL AIRFLOW VERTICAL AND HORIZONTAL MODELS Cooling Heating EWT WPD GPM EWT(ºF) GPM EAT TC SC THR EAT HC H Absrp. (ºF) (PSI) KW KW (db/wb) (MBH) (MBH) (MBH) (db) (MBH) (MBH) 75/62 18.4 14.6 1.01 21.9 60 16.2 1.13 12.4 2.75 2.3
ページ8に含まれる内容の要旨
359583-YTG-B-0208 TABLE 6: RP 0024 @ 800 CFM NOMINAL AIRFLOW VERTICAL AND HORIZONTAL MODELS Cooling Heating EWT WPD GPM EWT(ºF) GPM EAT TC SC THR EAT HC KW H Absrp. (ºF) (PSI) KW (db/wb) (MBH) (MBH) (MBH) (db) (MBH) (MBH) 75/62 25.5 19.9 1.25 29.8 60 21.0 1.43 16.1 3.5 3.3 80/67 28.3 19.8 1.26 32.6 3.5 70 20.7 1.53 15.5 85/72 30.9 19.5 1.27 35.2 80 20.5 1.62 14.9 50 50 75/62 26.1 20.2 1.15 30.0 60 21.8 1.46 16.9 6.0 8.0 80/67 29.0 20.1 1.17 33.0 6.0 70 21.5 1.56 16.2 85/72 31.8 19.9 1.19 35.9
ページ9に含まれる内容の要旨
359583-YTG-B-0208 TABLE 7: RP 030 @ 1000 CFM NOMINAL AIRFLOW VERTICAL AND HORIZONTAL MODELS Cooling Heating EWT WPD GPM EWT(ºF) GPM EAT TC SC THR EAT HC H Absrp. (ºF) (PSI) KW KW (db/wb) (MBH) (MBH) (MBH) (db) (MBH) (MBH) 75/62 32.8 25.0 1.71 38.6 60 27.0 1.91 20.5 4.5 3.6
ページ10に含まれる内容の要旨
359583-YTG-B-0208 TABLE 8: RP 036 @ 1200 CFM NOMINAL AIRFLOW VERTICAL AND HORIZONTAL MODELS Cooling Heating EWT WPD EWT GPM GPM EAT TC SC THR EAT HC H Absrp. (ºF) (PSI) (ºF) KW KW (db/wb) (MBH) (MBH) (MBH) (db) (MBH) (MBH) 75/62 38.8 29.9 1.78 44.8 60 31.4 2.20 23.9 5.5 2.9 80/67 42.9 29.7 1.85 49.1 5.5 70 31.0 2.35 23.0 85/72 47.1 29.4 1.91 53.6 80 30.7 2.49 22.2 50 50 75/62 39.2 30.1 1.65 44.8 60 32.8 2.24 25.2 9.0 7.0 80/67 43.9 30.1 1.68 49.6 9.0 70 32.3 2.39 24.2 85/72 48.2 29.8 1.76 54.
ページ11に含まれる内容の要旨
359583-YTG-B-0208 TABLE 9: RP 048 @ 1600 CFM NOMINAL AIRFLOW VERTICAL AND HORIZONTAL MODELS Cooling Heating EWT WPD GPM EWT(ºF) GPM EAT TC SC THR EAT HC H Absrp. (ºF) (PSI) KW KW (db/wb) (MBH) (MBH) (MBH) (db) (MBH) (MBH) 75/62 51.2 39.6 2.80 60.7 60 44.3 3.11 33.7 7.5 3.9
ページ12に含まれる内容の要旨
359583-YTG-B-0208 TABLE 10: RP 060 @ 2000 CFM NOMINAL AIRFLOW VERTICAL AND HORIZONTAL MODELS Cooling Heating EWT WPD GPM EWT(ºF) GPM EAT TC SC THR EAT HC H Absrp. (ºF) (PSI) KW KW (db/wb) (MBH) (MBH) (MBH) (db) (MBH) (MBH) 75/62 61.7 48.4 3.82 74.7 60 52.0 3.88 38.7 9.0 3.6 80/67 68.1 48.1 3.91 81.4 9.0 70 51.3 4.13 37.2 85/72 75.0 47.6 4.03 88.7 80 50.8 4.38 35.9 50 50 75/62 63.0 49.0 3.66 75.5 60 56.9 4.05 43.1 15.0 8.8 80/67 69.5 48.6 3.74 82.2 15.0 70 56.1 4.32 41.4 85/72 76.5 48.1 3.85 8
ページ13に含まれる内容の要旨
359583-YTG-B-0208 TABLE 11: BLOWER PERFORMANCE EXTERNAL STATIC PRESSURE (IN W.G.) Unit Speed 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 High ---- 270 235 195 150 - 007 Med - - 260 240 210 175 - - - Low 225 215 200 180 150 ---- High - - 380 360 330 290 240 - - 009 Med 350 340 325 300 27
ページ14に含まれる内容の要旨
359583-YTG-B-0208 SERVICE DOORS 1 - Electrical Box Service Door 2 - Compressor and Condenser Service Door 3 - Blower Service Door RETURN AIR MODEL DIMENSIONS IN INCHES FIGURE 1 - HORIZONTAL DIMENSIONAL DATA 14 Johnson Controls Unitary Products
ページ15に含まれる内容の要旨
359583-YTG-B-0208 SERVICE DOORS 1 - ELECTRICAL BOX SERVICE DOOR 2 - COMPRESSOR AND CONDENSER SERVICE DOOR 3 - BLOWER SERVICE DOOR FIGURE 2 - VERTICAL DIMENSIONAL DATA Johnson Controls Unitary Products 15
ページ16に含まれる内容の要旨
Subject to change without notice. Printed in U.S.A. 359583-YTG-B-0208 Copyright © 2008 by Johnson Controls, Inc. All rights reserved. Supersedes: 359583/036-21486-001-A-1102 Johnson Controls Unitary Products 5005 York Drive Norman, OK 73069