ページ1に含まれる内容の要旨
™
Sun StorEdge
A3500/A3500FC
Hardware Configuration
Guide
Sun Microsystems, Inc.
901 San Antonio Road
Palo Alto, CA 94303-4900 USA
650 960-1300 Fax 650 969-9131
Part No. 805-4981-13
December 1999, Revision A
Send comments about this document to: docfeedback@sun.com
ページ2に含まれる内容の要旨
Copyright 1999 Sun Microsystems, Inc., 901 San Antonio Road • Palo Alto, CA 94303-4900 USA. All rights reserved. This product or document is protected by copyright and distributed under licenses restricting its use, copying, distribution, and decompilation. No part of this product or document may be reproduced in any form by any means without prior written authorization of Sun and its licensors, if any. Third-party software, including font technology, is copyrighted and licensed from Sun supplie
ページ3に含まれる内容の要旨
Contents Preface vii 1. SCSI Host Connections 1-1 1.1 Configuration Guidelines 1-2 1.2 Supported SCSI Host Configurations 1-3 1.2.1 Single Host Connected to One Controller Module 1-3 1.2.2 Two Controller Modules Daisy-Chained to One Host 1-4 1.2.3 Independent Controller Module Connected to Two Hosts 1-5 1.2.4 Multi-Host 1-6 1.3 Ultra 2 Host System Power Connection Requirement 1-7 2. FC-AL Host Connections 2-1 2.1 Configuration Guidelines 2-2 2.2 Supported FC-AL Host Configurations 2-3 2.2.1 Sing
ページ4に含まれる内容の要旨
2.2.5 Single Host Connected to Four Controller Modules in a Loop Using Hubs 2-9 2.2.6 Multi-Host 2-11 2.3 Setting the Loop ID 2-13 3. Sun StorEdge A3500/A3500FC Configurations 3-1 3.1 StorEdge D1000 Disk Array Settings 3-2 3.1.1 1x2 Configuration 3-3 3.1.1.1 Option Switch 3-3 3.1.1.2 Module ID Switch 3-4 3.1.1.3 SCSI Jumper Cables and Terminators 3-4 3.1.2 1x5 Configuration 3-5 3.1.2.1 Option Switch 3-5 3.1.2.2 Module ID Switch 3-6 3.1.2.3 SCSI Jumper Cables and Terminators 3-6 3.1.3 2x7 Configu
ページ5に含まれる内容の要旨
3.4 2x7 Cables and Connections 3-17 3.4.1 SCSI Cable Lengths 3-17 3.4.2 Power Connections 3-19 3.5 3x15 Cables and Connections 3-20 3.5.1 SCSI Cable Lengths 3-20 3.5.2 Connections Between Power Sequencers 3-25 3.5.3 Connections to AC Power Sources 3-25 3.5.4 Power Connections for Expansion Cabinets 3-26 A. Sun StorEdge A3500 and A3500FCSpecifications A-1 A.1 Initial Cold Start Surge Current Specifications A-1 Contents v
ページ6に含まれる内容の要旨
vi Sun StorEdge A3500/A3500FC Hardware Configuration Guide • December 1999
ページ7に含まれる内容の要旨
Preface The Sun StorEdge A3500/A3500FC Hardware Configuration Guide provides configuration instructions for the Sun StorEdge™ A3500/A3500FC systems. These instructions are designed for an experienced system administrator. How This Book Is Organized Chapter 1 describes configurations for one or two small computer system interface (SCSI) StorEdge A3500 controller modules connected to one or more hosts. It also contains information about connecting power to a Sun Ultra™ host system. Chapter 2 descr
ページ8に含まれる内容の要旨
See one or more of the following for this information: ■ Solaris Handbook for Sun Peripherals ■ AnswerBook™ online documentation for the Solaris™ software environment ■ Other software documentation that you received with your system Typographic Conventions TABLE P-1 Typographic Conventions Typeface or Symbol Meaning Examples AaBbCc123 The names of commands, files, Edit your .login file. and directories; on-screen Use ls -a to list all files. computer output. % You have mail. AaBbCc123 What you t
ページ9に含まれる内容の要旨
Related Documentation TABLE P-3 Related Documentation Title Part Number Sun StorEdge A3500/A3500FC Controller Module Guide 805-4980 Sun StorEdge A3500/A3500FC Task Map 805-4982 Sun StorEdge Expansion Cabinet Installation and Service Manual 805-3067 Sun StorEdge RAID Manager Controller Replacement Guide 805-7854 Sun StorEdge A3500FC Controller Upgrade Guide 806-0479 Sun StorEdge RAID Manager 6.22 Release Notes 805-7758 Sun StorEdge RAID Manager 6.22 Installation and Support Guide for Solaris 805-
ページ10に含まれる内容の要旨
Sun Documentation on the Web sm The docs.sun.com web site enables you to access Sun technical documentation on the Web. You can browse thedocs.sun.com archive or search for a specific book title or subject at: http://docs.sun.com Sun Welcomes Your Comments We are interested in improving our documentation and welcome your comments and suggestions. You can email your comments to us at: docfeedback@sun.com Please include the part number of your document in the subject line of your email. x Sun Stor
ページ11に含まれる内容の要旨
CHAPTER 1 SCSI Host Connections This chapter describes configurations for one or two small computer system interface (SCSI) Sun StorEdge A3500 controller modules connected to one or more hosts. It also contains information about connecting power to a Sun Ultra™ host system. The topics covered in this chapter are: ■ Configuration Guidelines—page 1-2 ■ Supported SCSI Host Configurations—page 1-3 ■ Single Host Connected to One Controller Module—page 1-3 ■ Two Controller Modules Daisy-Chained to One
ページ12に含まれる内容の要旨
1.1 Configuration Guidelines Use the following guidelines to install and cable or reconfigure your StorEdge A3500 system. ■ The part number for the 12 meter SCSI host cable is 530-1886-xx. ■ Do not exceed a SCSI bus length of 25 meters (82 feet). ■ Make sure that the last StorEdge A3500 controller module in any daisy chain has a total of two terminators—one in each SCSI OUT port. ■ If you are adding a controller module to an already existing configuration, halt all activity on the SCSI bus befor
ページ13に含まれる内容の要旨
1.2 Supported SCSI Host Configurations The illustrations in this section show the SCSI cable connections for the configurations that are supported by Sun. ■ Single Host Connected to One Controller Module ■ Two Controller Modules Daisy-Chained to One Host ■ Independent Controller Module Connected to Two Hosts ■ Multi-Host 1.2.1 Single Host Connected to One Controller Module FIGURE 1-1 shows one host connected with SCSI cables to one StorEdge A3500 controller module. StorEdge A3500 Controller Modu
ページ14に含まれる内容の要旨
1.2.2 Two Controller Modules Daisy-Chained to One Host FIGURE 1-2 shows two StorEdge A3500 controller modules daisy-chained with SCSI cables to one host. You can daisy-chain controller modules in the same or separate cabinets. Host StorEdge A3500 Controller Modules Differential SCSI terminators SCSI cables FIGURE 1-2 Two Controller Modules Daisy-Chained to One Host Note – The SCSI cables between the two controller modules are crossed to prevent the SCSI IDs for the controllers from conflicting.
ページ15に含まれる内容の要旨
1.2.3 Independent Controller Module Connected to Two Hosts FIGURE 1-3 shows one StorEdge A3500 controller module connected with SCSI cables to two hosts. StorEdge A3500 Controller Module SCSI cables Hosts Differential SCSI terminators FIGURE 1-3 Independent Controller Module Connected to Two Hosts Chapter 1 SCSI Host Connections 1-5
ページ16に含まれる内容の要旨
1.2.4 Multi-Host FIGURE 1-4 shows a two-node multi-host configuration: one StorEdge A3500 controller module connected with SCSI cables to two hosts. StorEdge A3500 Controller Module SCSI cables Hosts Differential SCSI SCSI cables terminators FIGURE 1-4 Two-Node Multi-Host Configuration Note – The configuration shown in FIGURE 1-4 requires cluster software for management. For more information regarding the two-node multi-host configuration, such as instructions for setting host SCSI IDs, refer to
ページ17に含まれる内容の要旨
1.3 Ultra 2 Host System Power Connection Requirement You can connect a controller module to an Ultra 2 host system; however, you must connect the power cord of the Ultra 2 host to one of the AC power sequencers in the expansion cabinet that contains the controller module. Note – The RAID Manager 6.22 software does not support Ultra 2 host systems. You need to order one of the following power cords depending on the type of power sequencer in the expansion cabinet (FIGURE 1-5): ■ Ultra Enterprise™
ページ18に含まれる内容の要旨
Ultra Enterprise 1422 mm/56-inch Connect Ultra 2 expansion cabinet data center power cord here and StorEdge expansion cabinet expansion cabinet power sequencer power sequencer FIGURE 1-5 AC Power Sequencers—Ultra 2 Power Connector To connect the power cord: 1. Gain access to the AC power sequencers. See the documentation that came with the expansion cabinet. 2. Route the power cable from the Ultra 2 host under the expansion cabinet frame on the same side as the power sequencer. 3. Connect the po
ページ19に含まれる内容の要旨
CHAPTER 2 FC-AL Host Connections This chapter describes configurations for one or two Fibre Channel-Arbitrated Loop (FC-AL) Sun StorEdge A3500FC controller modules connected to one or more hosts. The following topics are covered in this chapter: ■ Configuration Guidelines—page 2-2 ■ Supported FC-AL Host Configurations—page 2-3 ■ Single Host Connected to One Controller Module—page 2-4 ■ Independent Controller Module Connected to Two Hosts—page 2-5 ■ Single Host Connected to One Controller Module
ページ20に含まれる内容の要旨
2.1 Configuration Guidelines Use the following guidelines to install and cable or reconfigure your StorEdge A3500FC system. Caution – The onboard SOC+ on the I/O board is not qualified yet to work with the StorEdge A3500FC controller module. Caution – At this time, only single port connection is qualified on the dual-ported host bus adapter card. ■ The part number for the 15 meter FC-AL host cable is 595-3379-xx; the Marketing part number is X978A. ■ Do not exceed a fiber-optic cable length of 5