HEAT CONTROLLER, INC.
Installation, Operation and
Maintenance Manual
HAH13XX-00-1A Series
Electric Heat
Air Handling Units
HEAT CONTROLLER, INC.
1900 Wellworth Ave., Jackson, Michigan 49203 Ph. 517-787-2100 Fax 517-787-9341 www.heatcontroller.com
THE QUALITY LEADER IN CONDITIONING AIR
1 of 6
06/06
ページ2に含まれる内容の要旨
9. Cabinet insulation is rated for R=4.2 (standard). A. Introduction Heat Controller Air Handlers come in a variety of Some jurisdictions require R=6.0 on installations in models and sizes for upflow or horizontal use and non-conditioned space. Add insulation 1” thick to when combined with cooling coils, are ready for air exterior of air handler to comply in these conditioning and heat pump applications. jurisdictions, putting the vapor barrier on the outside. These instruction
ページ3に含まれる内容の要旨
made prior to installing these lines). For left to speed change for heating and cooling airflow right applications. volumes. The pre-selected motor speeds would normally not have to be changed in the field. All 1. Remove and set aside front panels. 2. Remove the coil support bracket (4- HAH models contain a post purge timer (TDR) that screws. delays the blower turning off at the end of the cooling cycle, this improves energy efficiency. 3. Remove horizontal drain pan Terminal numbe
ページ4に含まれる内容の要旨
K. CONDENSATE DRAIN M. CHECK TEST AND START UP TURN OFF POWER AT BREAKER PANEL Electric heaters are high current devices. Verify that all electrical connectors, whether push-on or compression-type are tight. Loose connections will cause the wire and/or terminal to fail. The unit should be tested after the system has been completely installed to determine proper operation. Energize the unit by switching on the line voltage source and the thermostat. The air handler drain pan
ページ5に含まれる内容の要旨
ELECTRIC HEATER KIT SPECIFICATIONS MODEL MINIMUM CIRCUIT MAX. FUSE OR kW@ AMPACITY BREAKER (HACR) USED WITH 240V 208V 240V 208V 240V 208V N/A Without heat 0 0 2.1 1.9 15 15 7800-305B 5.0 3.8 29 25 30 25 HAH1324-00-1A 7800-306B 8.0 6.0 44 39 45 40 7800-308B 10 7.5 55 48 60 50 N/A Without heat 0 0 3.5 3.4 15 15 7800-305B 5.0 3.8 30 27 30 30 7800-306B 8.0 6.0 46 40 50 40 HAH1336-00-1A 7800-308B 10 7.5 56 49 60 50 7800-312B 15 11.3 56/26 49/23 60/30 50/30 N/A Without heat 0 0 4.0 3.9
ページ6に含まれる内容の要旨
24 56 13 GROUND LUG 6 of 6 L L 1 2 CB CB CB CB 1 2 2 1 H S-2 HEAT ST RIP-4 LS-4 H S-2 HEAT STRIP-3 LS-3 HS-1 HEAT ST RIP-2 LS-2 HS-1 HEAT STRIP - 1 LS-1 FR LO FR BLOWER MOTOR HI 208VAC XFMR FR TD R H S-1 HS-2 W2 C RED BLK BLU 5 4 4, 5 KW RESISTIVE HEAT STRIP RED BLU 3 1 LS- 4 HS-1 WHT RED WHT BLU 4, 5 KW RESISTIVE HEAT STRIP 5 4 RED LL LL 12 12 BLU 3 1 LS- 3 CB 1 CB 2 HS-2 RED T T T T 1 2 1 2 5 KW RESISTIVE HEAT STR IP P2 RED 4 RED P3 3 3 4 P3 P2 LS- 2 XFMR 2 6 6 2 P2 P3 P3 P2 H H RED TD R