                        FS-8700-127 Hanning & Kahl HCS-R Manual    Table of Contents      TABLE OF CONTENTS  1. HANNING & KAHL HCS-R DESCRIPTION.................................................................... 3  2. DRIVER SCOPE OF SUPPLY ........................................................................................ 4  2.1. Supplied by FieldServer Technologies for this driver.................................................. 4  3. HARDWARE CONNECTIONS........................................................
                    
                    ページ3に含まれる内容の要旨 
                    
                        FS-8700-127 Hanning & Kahl HCS-R Manual     Page 3 of 17    1.  Hanning & Kahl HCS-R Description   The Hanning & Kahl HCS-R driver allows the transfer of data from devices over RS-232 HCS-R  protocol. Data is read from HCS-R and current data stored in a specified memory area.  The  driver can store the data with its loop data status distinct memory areas depending on wheter  the data is on loop or from loop.  The driver is based on section 10.5 of Hanning & Kahl - part  number 40801121.  The Fie
                    
                    ページ4に含まれる内容の要旨 
                    
                        FS-8700-127 Hanning & Kahl HCS-R Manual     Page 4 of 17    2. Driver Scope of Supply  2.1. Supplied by FieldServer Technologies for this driver  FieldServer Technologies  Description  PART #  FS-8915-10 UTP cable (7 foot) for RS-232 use  FS-8700-127 Driver Manual.  FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA  Web:www.FieldServer.com  Tel: 408 262-2299   Fax: 408-262-2269   Toll_Free: 888-509-1970   email: support@FieldServer.com                                      
                    
                    ページ5に含まれる内容の要旨 
                    
                        FS-8700-127 Hanning & Kahl HCS-R Manual     Page 5 of 17    3. Hardware Connections  The FieldServer is connected to the Hanning & Kahl HCS-R as shown in connection drawing.  Configure the HCS-R according to manufacturer’s instructions    HCS-R (Hanning Communication System) RS-232 FS-8917-02 8917-02 WIRE LIST FUNCTION FROM TO Rx RJ45-01 DB9F-03 GND RJ45-04 DB9F-05 Tx RJ45-08 DB9F-02 RTS DB9F-07 CTS DB9F-08 RJ45 CAT 5 Cable (408)-262-2299 FIELDSERVER HANNING KAHL CONNECTION DIAGRAM BASE NAME:   
                    
                    ページ6に含まれる内容の要旨 
                    
                        FS-8700-127 Hanning & Kahl HCS-R Manual     Page 6 of 17    4. Configuring the FieldServer as a HCS-R Client  For a detailed discussion on FieldServer configuration, please refer to the FieldServer  Configuration Manual.  The information that follows describes how to expand upon the factory  defaults provided in the configuration files included with the FieldServer (See “.csv” sample files  provided with the FieldServer).  This section documents and describes the parameters necessary for configu
                    
                    ページ7に含まれる内容の要旨 
                    
                        FS-8700-127 Hanning & Kahl HCS-R Manual     Page 7 of 17    4.2. Client Side Connection Descriptions  Section Title  Connections  Column Title Function Legal Values  Specify which port the device is  1 Port P1-P8  connected to the FieldServer  HCS-R  Protocol Specify protocol used HCSR  H&K HCS-R  Baud* Specify baud rate 9600 (Vendor limitation)  Parity* Specify parity None (Vendor limitation)  Data_Bits* Specify data bits 8 (Vendor limitation)  Stop_Bits* Specify stop bits 1 (Vendor limitation)
                    
                    ページ8に含まれる内容の要旨 
                    
                        FS-8700-127 Hanning & Kahl HCS-R Manual     Page 8 of 17    4.4. Client Side Map Descriptors  4.4.1. FieldServer Related Map Descriptor Parameters  Column Title Function Legal Values  Up to 32 alphanumeric  Map_Descriptor_Name Name of this Map Descriptor  characters  Name of Data Array where data  One of the Data Array names  Data_Array_Name is to be stored in the  from “Data Array” section above  FieldServer  0 to maximum specified in  Data_Array_Offset Starting location in Data Array  “Data Ar
                    
                    ページ9に含まれる内容の要旨 
                    
                        FS-8700-127 Hanning & Kahl HCS-R Manual     Page 9 of 17    4.5. Map Descriptor Example: Read Data  The CMD_DI Map Descriptor polls HCS-R Node_A (described in Client Side Node Descriptors sections) every 5 seconds.  The other Map Descriptors are used to store the data for various loops. Refer to Appendix A for data storage format.    Map_Descriptors         Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_name Length  Scan_Interval  CMD_DI_HCSR_01, DA_CURRENT, 0, RDBC, Nod
                    
                    ページ10に含まれる内容の要旨 
                    
                        FS-8700-127 Hanning & Kahl HCS-R Manual     Page 10 of 17    4.6. Map Descriptor Example: Read Data and Keep History  This Map Descriptor allows the storage of data history up to HCSR_Data_Stages.  Data will be shifted to next Stage only if the data  is changed. The driver divides the Data Array into sections corresponding to the number of HCSR_Data_Stages. Current data  (stage1) will be stored in the first section and oldest (last stage) data will be stored in the last section in the Data array
                    
                    ページ11に含まれる内容の要旨 
                    
                        FS-8700-127 Hanning & Kahl HCS-R Manual     Page 11 of 17    5. Configuring the FieldServer as a HCS-R Server  For a detailed discussion on FieldServer configuration, please refer to the FieldServer  Configuration Manual. The information that follows describes how to expand upon the factory  defaults provided in the configuration files included with the FieldServer (See “.csv” sample files  provided with the FieldServer).  This section documents and describes the parameters necessary for configu
                    
                    ページ12に含まれる内容の要旨 
                    
                        FS-8700-127 Hanning & Kahl HCS-R Manual     Page 12 of 17      5.2. Server Side Node Descriptors  Section Title  Nodes  Column Title Function Legal Values  Up to 32 alphanumeric  Node_Name Provide name for Node  characters  Station address of physical server  Node_ID 240  Node  HCS-R  Protocol Specify protocol used HCSR  H&K HCS-R  Specifies the time that the  FieldServer will reserve the Server  Server_Hold_Timeout* side connection while waiting for >1.0s, 2.0s  the Client side to update data i
                    
                    ページ13に含まれる内容の要旨 
                    
                        FS-8700-127 Hanning & Kahl HCS-R Manual     Page 13 of 17    5.3. Server Side Map Descriptors  5.3.1. FieldServer Specific Map Descriptor Parameters  Column Title Function Legal Values  Up to 32 alphanumeric  Map_Descriptor_Name Name of this Map Descriptor  characters  Name of Data Array where One of the Data Array names  Data_Array_Name data is to be stored in the from “Data Array” section  FieldServer above  0 to maximum specified in  Data_Array_Offset Starting location in Data Array  “Data Ar
                    
                    ページ14に含まれる内容の要旨 
                    
                        FS-8700-127 Hanning & Kahl HCS-R Manual     Page 14 of 17    5.3.3. Map Descriptor Example. - SMD_HCSR_01 Map Descriptor to Serve HCS-R clients.  //   Server Side Map Descriptors          Map_Descriptors        Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name, Length, Scada_Hold_Timeout  SMD_HCSR_01, DA_HCSR, 0, Server, HCSR_01, 22, 5    One of the Data  The starting location One of the Nodes  Array name  The number of items  of data to serve described in  described i
                    
                    ページ15に含まれる内容の要旨 
                    
                        FS-8700-127 Hanning & Kahl HCS-R Manual      Page 15 of 17    Appendix A. Advanced Topics  Appendix A.1. 1. How Client Stores Data:  The HCS will be polled by an RDBC Map Descriptor and data will be stored in the  DA_Current Data Array in the following fashion if parameter HCSR_Data_Stages >1:  • New data is stored as current data.  nd nd • If data is changed, last current data is moved to 2 Stage, 2 Stage data is moved  rd rd to 3 stage and 3 stage data is lost.  Appendix A.1.1. Data_Type is An
                    
                    ページ16に含まれる内容の要旨 
                    
                        FS-8700-127 Hanning & Kahl HCS-R Manual      Page 16 of 17    The same data will be stored in a Loop based Data Array which will then have the last  known data for each loop    Data Array Offset Description  Current Data   0 - 18 Data bits ( 0 – 1)  19 Receipt ok ( 0 ), Disturbance ( 1 )  20  From Loop ( 0 ), On Loop ( 1 )  nd 2 (Previous) Data   21 – 39 Data bits ( 0 – 1)  40 Receipt ok ( 0 ), Disturbance ( 1 )  41 From Loop ( 0 ), On Loop ( 1 )  rd 3 (Prior to previous) Data   42 – 60 Data bit
                    
                    ページ17に含まれる内容の要旨 
                    
                        FS-8700-127 Hanning & Kahl HCS-R Manual      Page 17 of 17      THIS PAGE INTENTIONALLY LEFT BLANK  FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA  Web:www.FieldServer.com  Tel: 408 262-2299   Fax: 408-262-2269   Toll_Free: 888-509-1970   email: support@FieldServer.com