BLUE FLAME
VENT-FREE PROPANE GAS HEATER
OWNER’S OPERATION AND INSTALLATION MANUAL
®
Models: VP2000BTC and VP2800BTC
20,000 and 30,000 Btu/Hr Thermostatically Controlled Models
WARNING: Improper installation,
WARNING: If the information in this manual is not fol-
adjustment, alteration, service, or
lowed exactly, a fire or explosion may result causing
maintenance can cause injury or
property damage, personal injury, or loss of life.
property damage. Refer to this
— Do not store or use ga
ページ2に含まれる内容の要旨
SECTION PAGE CONTENTS Safety Information ......................................................................... 2 Product Identification .................................................................... 4 Local Codes ................................................................................... 4 Unpacking...................................................................................... 4 Product Features ............................................................................
ページ3に含まれる内容の要旨
SAFETY WARNINGS Continued WARNING ICON G 001 INFORMATION WARNING: Any change to this heater or its controls can be dangerous. Continued 1. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases. 2. Do not place propane supply tank(s) inside any structure. Locate propane supply tank(s) outdoors. 3. If you smell gas • shut off gas supply • do not try to light any appliance • do not touch any electrical switch;
ページ4に含まれる内容の要旨
Ignitor Button Control Knob PRODUCT IDENTIFICATION Grill Guard Glass Panel Front Panel Heater Cabinet Figure 1 - Vent-Free Propane Gas Heater (Model VP2800BTC Shown) Install and use heater with care. Follow all local codes. In the absence of local LOCAL CODES codes, use the latest edition of National Fuel Gas Code ANSI Z223.1, also known as NFPA 54*. *Available from: American National Standards Institute, Inc. 1430 Broadway New York, NY 10018 National Fire Protection Association, Inc. Batteryma
ページ5に含まれる内容の要旨
AIR FOR WARNING WARNING ICON G 001 This heater shall not be installed in a confined space unless COMBUSTION provisions are provided for adequate combustion and ventilation AND air. Read the following instructions to insure proper fresh air for this and other fuel-burning appliances in your home. VENTILATION Today’s homes are built more energy efficient than ever. New materials, increased insulation, and new construction methods help reduce heat loss in homes. Home owners weather strip and caulk
ページ6に含まれる内容の要旨
DETERMINING AIR FLOW FOR HEATER LOCATION AIR FOR Determining if You Have a Confined or Unconfined Space COMBUSTION Use this worksheet to determine if you have a confined or unconfined space. AND Space: Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between the rooms. VENTILATION 1. Determine the volume of the space (length x width x height). Continued Length x Width x Height = ___________________ cu. ft. (volume of spac
ページ7に含まれる内容の要旨
AIR FOR WARNING WARNING ICON G 001 COMBUSTION If the area in which the heater may be operated is smaller than that defined as an unconfined space, provide adequate combus- AND tion and ventilation air by one of the methods described in the National Fuel Gas Code, ANSI Z223.1, 1992, Section 5.3 or appli- VENTILATION cable local codes. Continued VENTILATION AIR Ventilation Air From Inside Building This fresh air would come from an adjoining unconfined space. When ventilating to an adjoining uncon
ページ8に含まれる内容の要旨
Ventilation Air From Outdoors AIR FOR Provide extra fresh air by using ventilation grills or ducts. You must provide two COMBUSTION permanent openings: one within 12" of the ceiling and one within 12" of the floor. Connect these items directly to the outdoors or spaces open to the outdoors. These AND spaces include attics and crawl spaces. Follow the National Fuel Gas Code NFPA 54/ANSI Z223.1, Section 5.3, Air for Combustion and Ventilation for required size VENTILATION of ventilation grills or
ページ9に含まれる内容の要旨
INSTALLING NOTICE A qualified service person must install heater. Follow all local codes. TO WALL CHECK GAS TYPE Use only propane/LP gas. If your gas supply is not propane/LP, do not install heater. Call dealer where you bought heater for proper type heater. INSTALLATION ITEMS Before installing heater, make sure you have the items listed below. • external regulator (supplied by • manual shutoff valve * • sediment trap installer, see page 14) • ground joint union • tee joint • piping (check local
ページ10に含まれる内容の要旨
For convenience and efficiency, install heater INSTALLING TO • where there is easy access for operation, inspection, and service • in coldest part of room WALL An optional fan kit is available from your dealer. See Accessories, page 30. If Continued planning to use fan, locate heater near an electrical outlet. CEILING 36" Minimum 6" Minimum From Sides Of Heater Left Right Side Side 3" Minimum To Top Surface Of Carpeting, Tile Or Other FLOOR Combustible Material Figure 4 - Mounting Clearances As
ページ11に含まれる内容の要旨
INSTALLING HEATER TO WALL INSTALLING TO Mounting Bracket WALL The mounting bracket is located on back panel of heater. It has been taped there for shipping. Remove mounting bracket from back panel. Continued Mounting Bracket Figure 6 - Mounting Bracket Removing Front Panel Of Heater 1. Remove two screws near bottom corners of front panel. 2. Lift straight up on grill guard until it stops. Grill guard will slide up about 1/4". 3. Pull bottom of front panel forward, then down. 4. Remove cardboard
ページ12に含まれる内容の要旨
Marking Screw Locations INSTALLING TO 1. Tape mounting bracket to wall where heater will be located. Make sure mount- ing bracket is level. WALL Continued WARNING WARNING ICON G 001 Maintain minimum clearances shown in Figure 8. If you can, provide greater clearances from floor and joining wall. 2. Mark screw locations on wall (see Figure 8). Note: Only mark last hole on each end of mounting bracket. Insert mounting screws through these holes only. 3. Remove tape and mounting bracket from wall.
ページ13に含まれる内容の要旨
4. For thin walls (1/2" or less), insert red key into wall anchor. Push red key to INSTALLING TO “pop” open anchor wings. IMPORTANT: Do not hammer key! For thick walls (over 1/2" thick) or solid walls, do not pop open wings. WALL Continued Figure 10 - Popping Open Anchor Wings For Thin Walls 5. Place mounting bracket onto wall. Line up last hole on each end of bracket with wall anchors. 6. Insert mounting screws through bracket and into wall anchors. 7. Tighten screws until mounting bracket is f
ページ14に含まれる内容の要旨
CONNECTING NOTICE A qualified service person must connect heater to gas supply. TO GAS Follow all local codes. SUPPLY CAUTION WARNING ICON G 001 Never connect heater directly to the propane supply. This heater requires an external regulator (not supplied). Install the external regulator between the heater and propane supply. The installer must supply an external regulator. The external regulator will reduce incoming gas pressure. You must reduce incoming gas pressure to between 11 and 14 inches
ページ15に含まれる内容の要旨
IMPORTANT: Hold the pressure regulator with wrench when connecting it to gas CONNECTING piping and/or fittings. Note: Burner bracket TO GAS not shown for clarity Pressure SUPPLY Regulator Continued 3/8" NPT Pipe Nipple Heater Ground Joint Cabinet Union Tee Joint Manual Test Reducer Shutoff Bushing to Gauge Valve * 1/8" NPT Connection * Typical Inlet 1/8" NPT Pipe From Plug Tap External Regulator (11" W.C. to 14" W.C. Tee Joint Pressure) Sediment Pipe Trap 3" Minimum Nipple Cap Figure 14 - Gas C
ページ16に含まれる内容の要旨
3. Pressurize supply piping system by either using compressed air or CHECKING opening propane supply tank valve. 4. Check all joints of gas supply piping system. Apply mixture of liquid soap and GAS water to gas joints. Bubbles forming show a leak. CONNECTIONS 5. Correct all leaks at once. Continued Test Pressures Equal To or Less Than 1/2 PSIG 1. Close manual shutoff valve (see Figure 15). 2. Pressurize supply piping system by either using compressed air or opening propane supply tank valve. 3.
ページ17に含まれる内容の要旨
OFF HI OPERATING FOR YOUR SAFETY READ BEFORE LIGHTING HEATER WARNING WARNING ICON G 001 If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life. A. This appliance has a pilot which must be lighted by hand. When lighting the pilot, follow these instructions exactly. B. BEFORE LIGHTING smell all around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle
ページ18に含まれる内容の要旨
4. Wait five (5) minutes to clear out any gas. Then smell for gas, including OPERATING near the floor. If you smell gas, STOP! Follow “B” in the safety information HEATER at the top of page 17. If you don’t smell gas, go to the next step. Continued 5. Turn control knob counterclockwise to the PILOT position. Press C-clockwise in control knob for five (5) seconds (see Figure 17). Note: You may be running this heater for the first time after hooking up to gas supply. If so, the control knob may n
ページ19に含まれる内容の要旨
OPERATING TO TURN OFF GAS TO APPLIANCE HEATER Shutting Off Heater 1. Turn control knob clockwise to the OFF position. Continued Clockwise 2. Turn off all electric power to the appliance if service is to be performed. Shutting Off Burner Only (pilot stays lit) 1. Turn control knob clockwise to the PILOT position. Clockwise THERMOSTAT CONTROL OPERATION The thermostatic control used on these models differs from standard thermo- stats. Standard thermostats simply turn on and off the burner. The th
ページ20に含まれる内容の要旨
Check pilot flame pattern and burner flame pattern often. INSPECTING PILOT FLAME PATTERN BURNER Figure 19 shows a correct pilot flame pattern. Figure 20 shows an incorrect pilot flame pattern. The incorrect pilot flame is not touching the thermocouple. This will cause the thermocouple to cool. When the thermocouple cools, the heater will shut down. Pilot Burner Thermocouple Figure 19 - Correct Pilot Flame Pattern Thermocouple Pilot Burner Figure 20 - Incorrect Pilot Flame Pattern If pilot flame