ページ1に含まれる内容の要旨
LOW BATT
AC LOSS
AC ON
IPGSM-4GC Commercial Fire Communicator
RADIO TROUBLE
IPGSM-4GC
IPGSM-4GC
Commercial Fire Communicator
Commercial Fire Communicator
up Guide
IIn ns stta alllla attiio on n a an nd d S Se ettup Guide
800-12458 7/12 Rev. C
ページ2に含まれる内容の要旨
Contents General Information ..................................................................................................................... 1 Package Contents ..................................................................................................................... 1 Compatible Fire Panels.............................................................................................................. 1 Operation ...............................................................
ページ3に含まれる内容の要旨
IPGSM-4GC Commercial Fire Communicator – Installation and Setup Guide General Information The IPGSM-4GC Commercial Fire Communicator (henceforth referred to as IPGSM-4GC) includes everything you need to upgrade a commercial fire system that previously reported by POTS to a system that uses the Internet as its primary reporting path, and uses a GSM cellular reporting path as a backup. In addition, the communicator’s power module (PowerBoost1) monitors and reports AC power loss, and low ba
ページ4に含まれる内容の要旨
IPGSM-4GC Commercial Fire Communicator – Installation and Setup Guide STEP 1 – Setup the Customer Account The communicator requires a subscriber account (customer account) to be setup with AlarmNet Direct. This is accomplished by registering the communicator with AlarmNet. Registering, enables the fire panel to send reports. To setup the customer account you will need to contact the central monitoring station to get account information, and have access to the AlarmNet Direct website. T
ページ5に含まれる内容の要旨
IPGSM-4GC Commercial Fire Communicator – Installation and Setup Guide 3. Temporarily wire the battery's negative [–] terminal to TB1–4 on the communicator, then wire the battery's plus [+] terminal to TB1–2 on the communicator. Wait about one minute for the communicator to initialize. 4. Position the assembly near a suitable mounting position and observe the RSSI display. 5. Look for a mounting position that yields at least 3 bars lit solid. For optimal performance 4 or 5 bars are bet
ページ6に含まれる内容の要旨
IPGSM-4GC Commercial Fire Communicator – Installation and Setup Guide 11. Verify the PowerBoost1 DIP switches are configured as shown below. PowerBoost1 ON 15 2 3 4 ON (Switch handle = white) 15 2 3 4 12. Ensure the following: LED Display board is fully seated. All wiring terminals and connectors are tight. All wiring has been completed and secured with cable ties. 13. Install the battery (not supplied). Apply power to the 1451-UL9 Wired Transformer, and attach the battery
ページ7に含まれる内容の要旨
Data Out IPGSM-4GC Commercial Fire Communicator – Installation and Setup Guide ANTENNA 1451-UL9 WIRED WIRES MUST BE TRANSFORMER RUN IN CONDUIT TO 24 HR NUT, BLU FACILITY POWER WASHER BLU 120VAC, 60Hz, 850mA 18 VAC GND 72 VA POST ANTENNA MOUNTING TO Cabinet Ground Post GND ADAPTER BLU TO PowerBoost1 BLU DO NOT REMOVE these knockouts. CABINET DOOR ON 15 2 3 4 RED GREEN Dialer Capture Module BATTERY TO Facility Ground TB 1 1 2 FUSE 3 4 PN: 100-02415 5 6 + 7 8 9 10 11 CONDUIT BATTERY 7AH (n
ページ8に含まれる内容の要旨
IPGSM-4GC Commercial Fire Communicator – Installation and Setup Guide Wiring the 659EN Line Fault Monitor (Required for ULC) The IPGSM-4GC is compatible with Fire Panels when the model 659EN Line Fault Monitor, (also known as the HFS- 659EN), is installed. Note, the wire colors may vary. 1. Refer to the installation guide for the 659EN. 2. Mount the 659EN on the lower left side of the IPGSM-4GC cabinet. 3. DO NOT cut the 659EN’s BLACK Output Relay Jumper or the BLUE Voltage Trip Threshol
ページ9に含まれる内容の要旨
IPGSM-4GC Commercial Fire Communicator – Installation and Setup Guide STEP 5 – Program the Communicator You must use the 7720P Programming tool to program the IPGSM-4GC. When using the 7720P Programming tool, the values given below are for most installations. Press the [#] key to accept the displayed default value (xxx) or enter the new value and press the [#] key for the next prompt. Use the [Space] key to scroll through a list of options. 1. (no display) Connect the 7720P. (Y
ページ10に含まれる内容の要旨
IPGSM-4GC Commercial Fire Communicator – Installation and Setup Guide To exit the programming mode, press [N] in response to the "Review?" prompt. Then press [Y] to the "Exit Prog Mode?" prompt. Upon exiting, the root file is updated to log the changes made. A message is displayed telling the user that this step is being executed. When complete, the message "DONE" is displayed to indicate the file was successfully uploaded. Note: If critical configuration changes were made, such as th
ページ11に含まれる内容の要旨
IPGSM-4GC Commercial Fire Communicator – Installation and Setup Guide Dialer Capture Module Information LED Indicator STATUS RED – Steady ON Messages exist in buffer. RED – Flashing No messages to be sent. Waiting for messages. GREEN – Steady ON Normal Indication. GREEN – Blinks every 2 sec. PowerBoost1 communication problem. GREEN – Blinks twice every sec. Connection with the Communicator is lost. GREEN – Blinks 10 times every sec. PowerBoost1 and Communicator connections are lost.
ページ12に含まれる内容の要旨
IPGSM-4GC Commercial Fire Communicator – Installation and Setup Guide PowerBoost1 Information LED Indicator STATUS AC (green) AC power available. ACTIVE (green) Cyclical flashing – normal communications. Repetition of 3 flashes – loss of communications. LOW BATT (yellow) Missing or low battery. TROUBLE (yellow) One or more trouble conditions exist, such as; overload, output supervision, ground fault, or charger failure. Notes: If AC power is lost and the battery voltage fa
ページ13に含まれる内容の要旨
IPGSM-4GC Commercial Fire Communicator – Installation and Setup Guide Communicator Information ON – NOT registered with AlarmNet. Cellular Status LED GRN OFF – Registered with AlarmNet. Voice Session – FAST BLINK – Download session with Compass Short blink every second in progress. Data Session – SLOW BLINK – In unison with yellow LED, 7720P Short blink every 2 seconds registration in progress. Programmer Port Connected to Cell network –
ページ14に含まれる内容の要旨
IPGSM-4GC Commercial Fire Communicator – Installation and Setup Guide RF Specifications Frequency Bands 2G GSM/GPRS/EDGE Quad Band, 850/900/1800/1900 MHz 3G/4G UMTS/HSPA+ Band V, Band II Output Power 2G GPRS +33dBm, GMSK modulation EDGE +27dBm, 8-PSK modulation 3G UMTS +24dBm, QPSK modulation WCDMA +24dBm, QPSK modulation 4G HSPA+ +24dBm, 64 QAM modulation WCDMA +24dBm, 64 QAM modulation Central Station Messages Alarm Condition Alarm Code Restore Code Power On / Reset E339
ページ15に含まれる内容の要旨
IPGSM-4GC Commercial Fire Communicator – Installation and Setup Guide IPGSM-4GC Trouble Detection Information Telco 1 is used for the Fire Panel to output contact ID messages to the IPGSM-4GC, and Telco 2 is used by the IPGSM- 4GC to report faults to the Fire Panel. If Telco 1 is not operational, the Fire Panel will use Telco 2 to report events if there are no faults in the Communicator. Fault Condition Indication to Fire Panel PowerBoost1 fault Telco 2 is cut. Communicator fault
ページ16に含まれる内容の要旨
IPGSM-4GC Commercial Fire Communicator – Installation and Setup Guide NOTES – 14 –
ページ17に含まれる内容の要旨
IPGSM-4GC Commercial Fire Communicator – Installation and Setup Guide NOTES – 15 –
ページ18に含まれる内容の要旨
IPGSM-4GC Commercial Fire Communicator – Installation and Setup Guide NOTES – 16 –
ページ19に含まれる内容の要旨
IPGSM-4GC Commercial Fire Communicator – Installation and Setup Guide NOTES – 17 –
ページ20に含まれる内容の要旨
IPGSM-4GC Commercial Fire Communicator – Installation and Setup Guide NOTES – 18 –