DIRECT-VENT GAS FIREPLACE
OWNER’S OPERATION AND INSTALLATION MANUAL
(Peninsula
Shown)
EVDDVF36PN (PENINSULA) AND EVDDVF36STN (SEE THRU)
NATURAL GAS - ELECTRONIC IGNITION
SAVE THIS BOOK
WARNING: If the information in these instruc-
This book is valuable. In addition to instructing
tions is not followed exactly, a fire or explosion
you on how to install and maintain your appli-
may result causing property damage, personal
ance, it also contains information that will
injury, or loss of life.
enab
ページ2に含まれる内容の要旨
® DIRECT-VENT GAS FIREPLACE EVDDVF36PN and EVDDVF36STN Alternate GLOSSARY OF Left Side TOP VIEW BACK VIEW Bottom Gas Surround Supply Inlets (Left Side) TERMS Back of Surround Chase - A box-like enclosure to protect 5 23 /8 3 39 /4 3 (60cm) 34 /4 (Front) venting from the elements when the venting (101cm) ø1.5 ø1.5 (88cm) 15 11 /16 (4cm) (4cm) 3 (Back) 26 /8 5 22 /8 run is on the outside of a structure. (30cm) (67cm) (57cm) Mastic - A pliable sealant for use around (Right Side) Right Side 1 1 10 /
ページ3に含まれる内容の要旨
OWNER’S MANUAL This appliance, when installed, must be elec- In selecting a location, the following pre- INTRODUCTION trically grounded in accordance with local cautions must be observed: codes, or in the absence of local codes, with the Model EVDDVF36PN series is a three-sided 1. A projection may be ideal for a new ad- National Electrical Code, ANS/NFPA 70 or direct-vent gas fireplace with a sealed com- dition on an existing finished wall. See the Canadian Electrical Code, CSA C22.1. bustion ch
ページ4に含まれる内容の要旨
® DIRECT-VENT GAS FIREPLACE EVDDVF36PN and EVDDVF36STN MANTEL CLEARANCES PRE-INSTALLATION CAUTION: Do not block re- Woodwork, such as wood trims, mantels, PREPARATION quired air spaces with insula- and other combustible materials projecting tion or any other material. Do not 1 no more than 1 /2 inches (3.8cm) shall not CLEARANCES obstruct the effective opening of be placed within 7 inches (17.8cm) from the the appliance with any type of Minimum clearances to combustibles are: opening of the uni
ページ5に含まれる内容の要旨
1 40 /2" (1029mm) 1 40 /2" (1029mm) 1 43 /4" (1098mm) OWNER’S MANUAL PRE-INSTALLATION GENERAL VENTING These models are approved for use with PREPARATION 5 1" (25mm) Simpson Dura-Vent 6 /8" direct-vent pipe Continued Dia. Hole components and terminations as well as both flex and rigid Vanguard vent components. Your fireplace is approved to be vented either through the side wall, or vertically using the 3" following guidelines: (76mm) 2" (51mm) Dia. Hole • Only use Vanguard or Simpson Dura- Vent G
ページ6に含まれる内容の要旨
V G G V A E D V B L ® DIRECT-VENT GAS FIREPLACE EVDDVF36PN and EVDDVF36STN GENERAL VENTING Continued N N H C I B Fixed V V Fixed Closed Openable Closed Openable B F V J G V X B B M A V K X TERMINATION CAP G GAS METER RESTRICTED AREA V X AIR SUPPLY INLET (TERMINATION PROHIBITED) A = clearance above grade, veranda, porch, deck, or balcony I = clearance to service regulator vent outlet [*72 inches (1829mm) [*12 inches (305mm) minimum] minimum] B = clearance to window or door that may be opened J =
ページ7に含まれる内容の要旨
OWNER’S MANUAL • Installation of any component part not You may use one or two 90° elbows in this VENTING manufactured or approved by DESA vent configuration. See Vertical Termination INSTALLATION International Configurations on pages 13 and 14. • Installation other than as instructed by Note: You may use two 45° elbows in place WARNING: Read all instruc- these instructions of a 90° elbow. You must follow rise to run tions completely and thoroughly ratios when using 45° elbows. before attemptin
ページ8に含まれる内容の要旨
® DIRECT-VENT GAS FIREPLACE EVDDVF36PN and EVDDVF36STN VENTING INSTALLATION Continued 12" Minimum INSTALLATION FOR HORIZONTAL TERMINATION 1. Determine the route your horizontal 90° venting will take. Note: The location of the horizontal vent termination on 1' Minimum the exterior wall must meet all local and national building codes and must not be easily blocked or obstructed. Snorkel WARNING: Do not recess vent terminal into a wall or siding. 45° Snorkel terminations are available for terminat
ページ9に含まれる内容の要旨
OWNER’S MANUAL 4. Apply a bead of non-hardening mastic 6. Carefully move the fireplace with vent VENTING around the outside edge of the vent cap. assembly attached toward the wall and INSTALLATION Position the vent cap in the center of insert the vent pipe into the horizontal 1 the 7 /2" or 10" hole on the exterior termination. The pipe overlap should be Continued 1 wall with the arrow on the vent cap a minimum of 1 /4". Apply silicone to 3. Attach vent pipe assembly to the fire- pointing up. In
ページ10に含まれる内容の要旨
UP UP ® DIRECT-VENT GAS FIREPLACE EVDDVF36PN and EVDDVF36STN VENTING INSTALLATION Continued Horizontal Venting Vertical (V) Horizontal (H) Horizontal Termination 45° Starter Configurations 49.5" min. 15" max. Elbow (45° elbow, 1' vertical pipe, 90° elbow) Required Figures 21 through 23 show different con- figurations for venting with horizontal ter- 61.5" min. 34" max. mination. Each figure includes a chart with 73.5" min. 58" max. vertical minimum/maximum and horizon- 85.5" min. 10' max. Note:
ページ11に含まれる内容の要旨
OWNER’S MANUAL VENTING INSTALLATION Continued Venting with Two 90° Elbows Vertical (V) Horizontal (H ) + 1 Horizontal (H ) 2 5' min. 4' max. 6' min. 8' max. 7' min. 10' max. 8' min. 15' max. 45° Starter Elbow 20' max. 20' max. Required Figure 23 - Horizontal Termination Configuration for Rigid Venting Using Two 90° Elbows with Termination at 90° with Fireplace Continued 106573 11
ページ12に含まれる内容の要旨
® DIRECT-VENT GAS FIREPLACE EVDDVF36PN and EVDDVF36STN 4. Connect a section of pipe and extend Flat Ceiling Installation VENTING up through the hole. 1. Cut a 10" square hole in the ceiling us- INSTALLATION Note: If an offset is needed to avoid ing the locating hole as a center point. Continued obstructions, you must support the vent The opening should be framed to pipe every 3 feet. Use wall straps for 10"x10" (254mm x 254mm) inside di- INSTALLATION FOR this purpose (see Figure 24). Whenever me
ページ13に含まれる内容の要旨
OWNER’S MANUAL Vertical Termination Configurations VENTING Figures 28 through 31 show four different configurations for vertical termination. All INSTALLATION connections must be sealed with high temperature silicone sealant as specified in the second Continued warning statement on page 7. 3. Lower the support box through the hole Venting with Two 90° Elbows in the roof until the bottom of the box extends at least 2" below the ceiling Vertical (V) Horizontal (H ) + 1 (see Figure 26). Align
ページ14に含まれる内容の要旨
® DIRECT-VENT GAS FIREPLACE EVDDVF36PN and EVDDVF36STN VENTING INSTALLATION Continued 45° Starter Elbow Required 45° Starter Elbow Required RVF Kit Shown Vertical Venting V = 40' max. Figure 31 - Vertical Rigid Venting Configuration With No Horizontal Run Venting with Two 90° Elbows Vertical (V ) Horizontal (H) 1 5' min. 6' max. 6' min. 12' max. 7' min. 18' max. 8' min. 20' max. Note: Vertical (V ) + 1 Vertical (V ) = 20' max. 2 Figure 30 - Vertical Rigid Venting Configuration Using Two 90° Elbo
ページ15に含まれる内容の要旨
OWNER’S MANUAL Vanguard Rigid Venting (Cont.) Vanguard Flexible Venting VENTING Number Description Number Description INSTALLATION *SVK Snorkel Rigid Vent Kit FGFVK Flex Ground Floor Vent Kit Continued Includes: 7" x 30° Elbow, 7" x 4' Includes: Flex Adapter, 7" x 4' Galvanized Pipe, 7" x 90° El- Flexible Pipe, 4" x 4' Flexible HIGH ALTITUDE bow, 7" Adjustable Galvanized Pipe, Wall Thimble, Horizontal INSTALLATION Pipe (7-12"), Wall Thimble, 36" Termination, (4) Spacer Springs, Snorkel Terminati
ページ16に含まれる内容の要旨
® DIRECT-VENT GAS FIREPLACE EVDDVF36PN and EVDDVF36STN INSTALLATION Peninsula or See-Thru For Optional INSTALLING OPTIONAL Fireplace Fan Kit Installed WALL MOUNT SWITCH Flue Exit GWMS2 From Blower NOTICE: The GWMS2 includes Inside Assembly 25' of wire for installation. Your Wall fireplace includes 15' of wire for Blower accessory installation. Choose the Assembly length that best fits your needs when installing this accessory. Figure 34 - Connecting Blower Accessory The installation of a wall sw
ページ17に含まれる内容の要旨
OWNER’S MANUAL Battery Cover Route a 1/2” NPT black iron gas line to- INSTALLATION wards the appliance coming in from the left. Continued 12 Volt Battery It is recommended to route the pipe between the stand of the firebox and the surround of OPTIONAL REMOTE the fireplace (see Figure 40). CONTROL INSTALLATION IMPORTANT: The appliance and its indi- (Model WRC) vidual shutoff valve must be disconnected Note: If using optional wireless hand-held from the gas supply piping system during remote contr
ページ18に含まれる内容の要旨
® DIRECT-VENT GAS FIREPLACE EVDDVF36PN and EVDDVF36STN 8. Place logs “A” as shown in Figure 45, INSTALLING LOG SET INSTALLATION page 19. Continued Before proceeding, make sure the gas con- 9. Place logs “B” as shown in Figure 46, trol valve is in the “OFF” position. Logs page 19. Lift the end of log “A” that will have been packaged separately to prevent WARNING: All gas piping be propped up and place log “B” under damage to glass or refractory. and connections must be tested it. At the same tim
ページ19に含まれる内容の要旨
OWNER’S MANUAL INSTALLATION Left Continued D C 0.75 WARNING: Improper installa- tion, adjustment, alteration, ser- E vice, or maintenance can cause injury or property damage. Refer 0.34 to this manual. For assistance or C D additional information, consult a Figure 49 - Burner and Electrode (Top qualified installer, service Right View) agency, or gas supplier. Figure 47 - Installing Twigs “C, D, E ” (Top View) B C BURNER FLAME D A DECORATIVE FACING ADJUSTMENT Any noncombustible material may be u
ページ20に含まれる内容の要旨
® DIRECT-VENT GAS FIREPLACE EVDDVF36PN and EVDDVF36STN BURNER FLAME OPERATING CAUTION: If the glass breaks, be cautious of fragments on the ADJUSTMENT GUIDELINES AND floor. Keep children away from Continued MAINTENANCE the area. Do not operate the unit. BURNER REMOVAL Use proper safety gloves to re- INSTRUCTIONS move the broken glass door. Dis- When lit for the first time, the appliance may card safely. A glass door kit can CAUTION: Before proceed- emit a slight odor for about 16 - 24 hours. T