DS9400 Series
Release Notes for Firmware V2.07
EN Fire Alarm Control Panel
ページ2に含まれる内容の要旨
DS9400 Series | Release Notes for Firmware V2.07 | Trademarks Upgrade Information Trademarks If this firmware is installed in a control panel that has been running version 1.x Gentex™ is a trademark of Gentex Corporation, Fire software, it is necessary to erase the old Protection Group programming in the control panel and re- CleanMe® is a registered trademark of GE select the control panel type when the Interlogix control panel is first powered up. Be careful to select “1-DS94
ページ3に含まれる内容の要旨
DS9400 Series | Release Notes for Firmware V2.07 | 5.0 DS9400 Series Version 2.03A October, 2002 . • Wheelock Sync Protocol. This feature no When communicating to the control panel longer requires the Detection Systems using RPS, the control panel will report D411/D412 in order to produce Temporal Code v2.03 software installed even when the 3. upgrade v2.03A has been installed. • Auto Silence Operation. The auto-silence operation is now correctly processed on a 6.0 Fixed Items in
ページ4に含まれる内容の要旨
DS9400 Series | Release Notes for Firmware V2.07 | 7.0 Fixed Items Since Firmware Version 1.08 • DS9431 Accidental Removal (DS9400M Boards shipped before August 31, 1999 only): On control panels running firmware must be modified according to Technical version 2.02 or earlier, if the wires on the Service Note (P/N: 42363) to ensure that keypad option bus are momentarily shorted for the battery test runs properly. Affected less than a second, the DS9431 Multiplex boards carry a lot
ページ5に含まれる内容の要旨
DS9400 Series | Release Notes for Firmware V2.07 | 7.0 Fixed Items Since Firmware Version 1.08 . • Manual Battery/NAC Test during AC Fail: • Programming Access: Firmware version 2.02 Manually initiating a battery test (Test Menu, corrects a configuration problem found in Option 4) when AC has failed will now correctly control panels with prior firmware that display the current battery voltage. However, if improperly allows programming access to all a user at the control panel requests a ma
ページ6に含まれる内容の要旨
DS9400 Series | Release Notes for Firmware V2.07 | 8.0 New Features since Firmware Version 1.X • User ID Report for Drill and Walk Test: As 8.0 New Features since shown in Appendix C of the DS9400M Firmware Version 1.X Reference Guide (P/N: 31499) or the DS9400i Reference Guide (P/N: 43707), the control panel • Supports the DS9431 Multiplex Expansion does not report the ID of the person starting a Module to add addressable points (247 fire drill or walk test to the central station. a
ページ7に含まれる内容の要旨
DS9400 Series | Release Notes for Firmware V2.07 | 9.0 Known Issues with Firmware Version 2.07 . • Temporarily swap lines 1 and 2 on the control panel and see if the problem indication moves to the control panel’s other phone line channel, in which case the phone line is causing the problem rather than the line monitor. 5. Confirm that the fault message is “phone fault” and not “Comm fault”. • “Comm fault” is often caused by failing to program a phone number or account number for pho
ページ8に含まれる内容の要旨
Bosch Security Systems 130 Perinton Parkway Fairport, NY 14450-9199 Customer Service: (800) 289-0096 Technical Support: (888) 886-6189 © 2006 Bosch Security Systems 36925V