ページ1に含まれる内容の要旨 
                    
                         
   Operating & Service Instructions 
-for- 
  HP7 Microprocessor Controller 
Includes Connection of External Controllers  
      
Dealer & Service Version 
   Not for Distribution to Owners 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
th
2737 24 Street North 
St. Petersburg, FL 33713 
800-786-7751 
www.aquacal.com                                                                                                                                                                                         
                    
                    ページ2に含まれる内容の要旨 
                    
                              Revised 10/14/03    TABLE of CONTENTS      GENERAL DESCRIPTION of HP7 CONTROLLER.................................................4  HP7 CONTROLLER SPECIFICATIONS....................................................................4  Inputs: ........................................................................................................................................................4  Outputs:...........................................................................................
                    
                    ページ3に含まれる内容の要旨 
                    
                        2. Time Delay [dEL] : ......................................................................................................................12  3. Configuring for External Controllers [JAO] or [FS2]: ................................................................12  4. Water Sensor calibration [tSC]… ................................................................................................13  5. Defrost Sensor Calibration [dSC]… ............................................................
                    
                    ページ4に含まれる内容の要旨 
                    
                                        GENERAL DESCRIPTION of HP7 CONTROLLER    The HP7 is a powerful microprocessor control designed for use in swimming pool & spa heat  pumps. The control features 3-digit temperature and set point display, with programming changes  easily performed via simple 3-button (key) operation.     The HP7 offers precise water temperature control, accurate defrost management, anti short-cycle  protection,  circulator pump management, compressor contactor control, refrigerant circuit  pressure
                    
                    ページ5に含まれる内容の要旨 
                    
                         Control Features:   ♦ Compressor Operation  ♦ Refrigerant Circuit Hi & Low-Pressure Lock Out   ♦ Water Pump Option (Call Flex)   ♦ Precise Evaporator Temperature Control (Defrost Management)   ♦ Anti Short Cycle Timer (4-Minute Restart Delay)              ♦ Precise Water Temperature Control  ♦ Corrosion Protection (Conformal Coating)         CONTROL PANEL LAYOUT                       (Appearance will vary between model lines)        1) DOWN ARROW – Reduces temperature setting. Turn heater off. 
                    
                    ページ6に含まれる内容の要旨 
                    
                        CONTROL PANEL SYMBOLS   UNIT is HEATING      WATER TEMPERATURE SET POINT      ACTUAL WATER TEMPERATURE    POOL SELECTION    SPA SELECTION   6                                                                                                                                                                                                                                                                                                                                                                       
                    
                    ページ7に含まれる内容の要旨 
                    
                         SEQUENCE of OPERATION      HP-7 (6200P) Sequence of Operation LINK to  Codes START PUMP OFF OPERATIONAL CODES POWER ON ______________________ ______________________ Other Possible Displays "FS"...Defrost  Mode Normal Operation in Colder Weather "FLO" Displayed FAILURE CODES ______________________ CSE- Control System Error SET POINT BELOW 60ºF PUMP ON dPC-Defrost Sensor Shorted ______________________ POWER ON dPO- Defrost Sensor Open Heater is "OFF" Other Possible Displays ______________________
                    
                    ページ8に含まれる内容の要旨 
                    
                        START UP & SETTING OPERATING CONTROLS  LEVEL-1 (Owner) ACCESS        NOTE:   Covered within this section are features and settings typically accessed first by  the installer, and then remaining accessible by the end user (owner).  These  features reside at the Level-1 access point within the microprocessor.  (Please  see page-11  for information concerning Level-2, service-related access.)           1. Applying Power to The Controller:     A. When power is first applied, the control performs a l
                    
                    ページ9に含まれる内容の要旨 
                    
                          5. Changing The Pool Temperature Set Point:    A. Using the Pool / Spa key, select the POOL temperature set point. The pool set point  indicator light will confirm your selection by lighting.     B. The pool temperature set point range is adjustable from 60 °F. to 95 ° F (104 °F in latest  models). using the Up ⇑ or Down ⇓ arrow keys. The desired temperature can be selected  by briefly depressing the arrow keys, or by holding them down to scroll the temperature  up or down.     6. Changing The
                    
                    ページ10に含まれる内容の要旨 
                    
                        5) With  [ELC] displayed, use the Up or Down arrow keys to select a lock code  number. The factory set lock code is “17”.  Not depressing any buttons for 15- seconds will allow the control to save the selection and return to the normal  operating mode. Pressing the Pool / Spa key will also save the selection and step to  the next menu parameter [CFO] (Call Flex Options);    6) Once the ULC option has been enabled, depressing any key will display [000]  (prompting the entry of the correct lock co
                    
                    ページ11に含まれる内容の要旨 
                    
                            10. Fan Speed Control… This option is not applicable to any current models. If option present,   factory default setting of “80” MUST  remain.  Controllers Version .06 or newer will not  contain a FAN option.      LEVEL-1 DISPLAY CODES    Menu Codes        Description       Function     [FLO] No water flow Displayed Code Message:  Appears whenever the circulating  detected  pump is off, or when the heater is not receiving correct  water flow.  [OFF] System is off  Displayed Code Message: App
                    
                    ページ12に含まれる内容の要旨 
                    
                        WARNING !!!!  Dealer &  Service Center Use Only  SERVICE & SET UP FEATURES  LEVEL-2 ACCESS   (Includes Configuration for External Controllers)    1. Entering Service Menu:    A. To enter the service menu level, depress and hold both the Up ⇑ and Down ⇓ arrow keys  simultaneously until the code message [CF1]  (Celsius Fahrenheit Selection) is  displayed.  (NOTE: If [000] displays, User Lock Code is enabled, and the ULC pass  code must be entered before proceeding.  See section: “User Lock Code Op
                    
                    ページ13に含まれる内容の要旨 
                    
                        WARNING !!!!  Dealer &  Service Center Use Only  3.2:  Configuring for External Controllers not Equipped with an “OFF” Position            Switch, and All Double-Function Air Switch Controllers.     (Also see Appendix Item “B”)    3.3 Remote Flow Switch / Automatic Thermostat Switching [FS2]:  (Also see Appendix Item “C”)      A. Follow the steps 1a. through 1d. above to enter the service menu. Once [dEL] is  displayed, press the Pool / Spa key twice to display [FS2].    B. With the [FS2] (Remot
                    
                    ページ14に含まれる内容の要旨 
                    
                        WARNING !!!!  Dealer &  Service Center Use Only  B. Remove the unit front panel to gain access to the defrost sensor . The defrost sensor  will  be found strapped to the suction line in combination with the TXV sensing bulb, or, in  some models, the defrost sensor will be connected to the suction line independent of the  TXV bulb;    C. Carefully remove the insulation from around the sensor area;     D. Using a highly-accurate, surface-mount thermometer, attach the thermometer probe to  the suct
                    
                    ページ15に含まれる内容の要旨 
                    
                        WARNING !!!!  Dealer &  Service Center Use Only    7. Changing Service Lock Code & “Backdoor” Entry…    A. Changing the Code…    The factory default Service Lock Code is “50”.  Service personnel are strongly advised  to retain the factory default setting. However, should  unauthorized access to the Level-2  (Service) menu be suspected, it may be useful to select a code other than “50”.  To  change the Service Lock Code:    1) Enter the service menu level by depressing and holding both the Up ⇑ a
                    
                    ページ16に含まれる内容の要旨 
                    
                        WARNING !!!!  Dealer &  Service Center Use Only  8) [DEL] will display (At this point you have entered the service menu, and service- level programming will be possible.);  9) Push Pool/Spa pad until [LOC] appears on readout for the second time;  10) Push the up arrow,…The current, correct lock code will display.  Using the up or  down arrow, the code can now be changed back to back to the factory default:  “50”, or the code may be set to any number ranging [000] to [999].  Unless  attempting to
                    
                    ページ17に含まれる内容の要旨 
                    
                        WARNING !!!!  Dealer &  Service Center Use Only    LEVEL-2 FAULT CODES        Message     Error Description                    Possible Cause  [dPO] Defrost Sensor Open Cut or loose sensor wiring   Water Temperature Cut or loose sensor wiring   [PO]  Sensor Open  [dPC] Defrost sensor Short circuit in defrost sensor wiring or defective sensor.  shorted  [PC]  Water temperature Short circuit in water sensor wiring or defective sensor.  sensor shorted  [LP] Refrigerant system System refrigerant cha
                    
                    ページ18に含まれる内容の要旨 
                    
                        WARNING !!!!  Dealer &  Service Center Use Only  APPENDIX    Connecting to, and Configuring Microprocessor for, External Control:    • A:  Jandy and Pentair/Compool Brand External Controllers Equipped with an       “OFF” Position    • B:  External Controllers NOT Equipped with OFF Setting    • C:  Remote Flow Switch Connection    • D:  Call/Flex Option                             18                                                                                                                   
                    
                    ページ19に含まれる内容の要旨 
                    
                        WARNING !!!!  Dealer &  Service Center Use Only  Connecting  Specific Jandy Or Pentair/Compool Controllers (See application table within)  Appendix- A    Instructions For Connecting Specific Jandy Or Pentair/Compool  Controllers To AquaCal’s HP7 Microprocessor    The microprocessor terminal block, labeled X,Y,Z, is located on the low-voltage portion of the  MICROPROCESSOR POWER BOARD.  (See figure 1, below.)        Figure-1    Controllers Suitable for this Application:    Jandy and Compool contr
                    
                    ページ20に含まれる内容の要旨 
                    
                        WARNING !!!!  Dealer &  Service Center Use Only  Warning !      MAKE CERTAIN POWER SUPPLY TO HEATPUMP and CONTROLLER IS DISCONNECTED  PRIOR TO CONTINIUING.  FAILURE TO DISCONNECT ELECTRICAL POWER MAY  RESULT IN SERIOUS INJURY OR DEATH.      1. String 18/2 cable from the controller to the heat pump.  2. Locate the MICROPROCESSOR POWER BOARD inside the heat pumps electric box. (See figure 1)  3. Connect the 18/2 cable from the controllers low voltage heater terminals to the MICROPROCESSOR  POWER B