INSTALLATION 10-175UL
Power Supply
®
10-175UL
Access Control Power Supply/Charger
Installation and Specifications Manual
ページ2に含まれる内容の要旨
Overview The 10-175UL is a power limited power supply/charger that will convert 115VAC / 60Hz input, into two individually PTC protected 12VDC or 24VDC output, (see specifications). They are intended for use in applications requiring UL Listing for Access Control (UL294) and applications requiring an interface with Fire Alarm Control Panels. It must be installed in accordance with National and Local Electrical Codes and Regulations. Specifications • UL listed Access Control (UL294) • CSFM approv
ページ3に含まれる内容の要旨
Installation Instructions The 10-175UL should be installed in accordance with article 760 of The National Electrical Code or NFPA 72 as well as all applicable Local Codes. See Terminal Identification Chart on page 4 for a description of each terminal function. 1. Mount the 10-175UL in desired location. 2. Connect AC power (115VAC 60Hz) to the black and white flying leads of the trans- former. Secure green wire lead to earth ground. Use 18 AWG or larger for all power connections (Battery, DC outp
ページ4に含まれる内容の要旨
Terminal / Switch Identifcation: Terminal Legend Function/Description TRGI & TRG2 These input terminals are designed to connect to the normally closed outputs of an access control or fire alarm relay. These terminals control [LOCK+], and [STRIKE+], as well as 10-175UL output relay contacts [N.C., N.O., C] LOCK+ This terminal provides DC output voltage when [TRG1] and [TRG2] are shorted together and are typically used to power Mag Locks. STRIKE+ This terminal provides DC output voltage when [TRG1
ページ5に含まれる内容の要旨
AC FAIL NC NO C 115VAC input 60 Hz, .6 amps Reset AC Power Switch LED Green Black White Lead Lead Lead (ground) XFMR JUMPER NC NO C TRG1 TRG2 SW1 CLOSED -24V OPEN - 12V DC SW1 VR1 Molex AC Connector AC 10-175UL LOCK + STRIKE + COM - AUX + FACP AUX - + BAT -- AC AC Stand-by Battery (optional) Constant output (not affected by trigger) Switched DC output (trigger control) 5
ページ6に含まれる内容の要旨
Enclosure Dimensions 1.50" 4.50" 4.50" [38.1mm] [114.3mm] [114.3mm] 1.25" [31.8mm] 4.50" [114.3mm] 12.00" [304.8mm] 0.88" 9.88" 4.50" 0.94" [22.2mm] [250.8mm] 1.25" [114.3mm] [23.8mm] [31.8mm] 2.13" [54.0mm] 15.50" 3.38" [393.7mm] [85.7mm] 3.38" [85.7mm] 2.25" [57.2mm] 0.88" 4.50" 1.25" [22.2mm] [114.3mm] [31.8mm] 4.50" [114.3mm] 1.25" [31.8mm] 1.50" 4.50" 4.50" [38.1mm] [114.3mm] [114.3mm] FIG 1. Typical mag lock with fire alarm tie- FIG 2. Multiple 10-175 power supply in using aux
ページ7に含まれる内容の要旨
FIG 3. Typical Single Mag lock or door strike installation with fire alarm tie-in using trigger controlled output. FIG 4. Typical dual mag lock installation with fire alarm tie- in using trigger controlled outputs. 7
ページ8に含まれる内容の要旨
FIG 5. Latching fire alarm tie-in ith manaul reset. Troubleshooting Guide Problem Solution - Check AC and DC LED’s on power No DC output from terminals. supply board. Both should be on for proper operation AC ON –GREEN, Trouble: Normal – AMBER, DC ON - RED. - If LED’s are not on, check AC power. - Disconnect AC power, battery(s) and all connected equipment IMMEDIATELY. Output voltage is not correct for the con- - Change voltage selection switch to nected equipment. desired voltage. - Recon