ページ1に含まれる内容の要旨
STEAM
DISTRIBUTORS
ASD / BSD / CSD
Steam Distribution
Installation Manual
IMPORTANT: Read and save this guide for future
reference. This guide to be left with equipment owner.
1506117-B
ページ2に含まれる内容の要旨
Table Of Contents INSTALLATION .....................................1 RECEIVING & UNPACKING EQUIPMENT .....................1 PRE-INSTALLATION.................................1 STEAM LINE INSTALLATION............................1 GUIDELINES...................................1 CONDENSATE RETURN GUIDELINES FOR MAIN STEAM LINES..........2 DISTRIBUTOR MOUNTING...............................3 VERTICAL AIRFLOW..................................4 HORIZONTAL AIRFLOW ................................5 VERTI
ページ3に含まれる内容の要旨
Chart #1 INSTALLATION Steam Line Material RECEIVING & UNPACKING EQUIPMENT Steam Copper Tube Stainless Hose Steel Tube 1. Check packing slip to ensure ALL material has been delivered. Short run < 10 feet (3 m) 2. All material shortages are to be reported to Walter Meier (NORTEC) within 48 hours from receipt of goods. Walter Meier Long run > 10 feet (NORTEC) assumes no responsibility for (3m) any material shortages beyond this period. DI/RO 3. Inspect shipping boxes for damage and water
ページ4に含まれる内容の要旨
Chart #3 6. Vertical drop of the drip station should be Recommended Condensate line at distributor(s) 1.5 times the diameter of the steam main but no less then 12”. Dispersion Condensate StainlessSteel Coppertube Method Hose tube 7. At the bottom of this drip station is where the “p-trap” is installed. It is to be 2” larger 1/4"MED-L 1 x Steam 3/8"Nortec 3/8”tube then the duct static duct pressure. Tubing distributor 1328840 0.049”thick. (3/8"O.D.) 8. All distributors must be individually trappe
ページ5に含まれる内容の要旨
Figure #2 Distributor Mounting A HORIZONTAL FLOW VERTICAL FLOW min. 2º min. 10º min. 2º min. 10º min. 10º min. 10º Use vertical Use vertical condensate leg condensate leg only. only. Nortec Nortec To be 2” (50mm) longer Humidifier Humidifier then duct static pressure or minimum. NHB, NHP, NHMC, NHB, NHP, NHMC, RESDELUX ONLY RESDELUX ONLY GO TO GO TO C1 B min. 2º min. 10º min. 2º min. 10º min. 10º min. 10º Nortec Nortec Humidifiers Use vertical Humidifiers Use vertical condensate leg condensate l
ページ6に含まれる内容の要旨
Figure #3 Vertical Airflow B Always align distributor holes so that steam is discharged upwards to ensure condensate will remain in the distributor. 1 1x 2 +45º -45º 3 GO TO C2 -4-
ページ7に含まれる内容の要旨
81-... 61-... / 41-... 81-... 61-... / 41-... 61 mm Figure #4 Horizontal Airflow C1 Always align distributor holes so that steam is discharged upwards to ensure condensate will remain in the distributor. Template provided 81-... by Nortec in box. 41-... 61-... XMin. HMin. ASD 3” (76mm) 8” (203mm) BSD 4” (102mm) 10” (254 mm) CSD 5” (127mm) 14” (356mm) ASD ø 1.7" (43 mm) BSD ø 1.7" (43 mm) CSD ø 2.4" (61 mm) H X 2/3H H 1/3H 2/5H H 2/5H 1/5H 5”min. A AB ASD: 5” 3” A BSD: 6” 4” CSD:9” 5” B GO TO D -
ページ8に含まれる内容の要旨
Figure #5 Vertical Airflow C2 Always align distributor holes so that steam is discharged upwards to ensure condensate will remain in the distributor. W 1/3W 2/3W 1/ 1/3W 3W 1/3W 1/3W Min. W = 8” (203 mm) GO TO D WARNING: These installation guidelines apply for duct velocities under 2000 ft/min (610 m/min), please consult factory for higher velocities. Please make sure no obstacles (elbow, filter, or diffuser) are located after the distributor in the direction of the airflow closer than the a
ページ9に含まれる内容の要旨
Figure #6 Distributor Mounting - Horizontal & Vertical Flow D #10 Screw Use selftapping screws. GO TO E Figure #7 Distributor Mounting E 5/16” unc Mount Level 5/16” Mandatory for Distributors longer than 36” (915mm). Support Bracket by Others -7-
ページ10に含まれる内容の要旨
-8- ASD & BSD 1506162- Distributor End Cap Assembly CSD 1506164 - Distributor End Cap Assembly Distributor Core ASD & BSD 1506161- Distributor Inlet Assembly CSD 1506163 - Distributor Inlet Assembly Exploded Views December 18, 2002
ページ11に含まれる内容の要旨
LIMITED WARRANTY Walter Meier Inc. and/or Walter Meier Ltd. (hereinafter collectively referred to as THE COMPANY), warrant for a period of one year from date of shipment, that THE COMPANY’s manufactured and assembled products, not otherwise expressly warranted, are free from defects in material and workmanship. No warranty is made against corrosion, deterioration, or suitability of substituted materials used as a result of compliance with government regulations. THE COMPANY’s obligations and lia
ページ12に含まれる内容の要旨
Walter Meier (Climate USA) Inc. 826 Proctor Avenue, Ogdensburg, New York 13669 Walter Meier (Climate Canada) Ltd. 2740 Fenton Road, Ottawa, Ontario K1T3T7 Tel: 866 NORTEC 1 Fax: 613 822 7964 nortec@humidity.com www.humidity.com PRINTED IN CANADA