GENERAC GUARDIAN SERIES
STANDBY GENERATORS
60 kW
Liquid-Cooled Engine Generator Sets
Includes: Standby Power Rating
Model QT060 (Steel - Bisque) - 60 kW 60Hz
• Generac Turbocharged/Aftercooled
Model QT060 (Aluminum - Gray) - 60 kW 60Hz
Gaseous Fueled 2.4L Engine
• Two Line LCD Tri-lingual
Digital Nexus™ Controller
• Isochronous Electronic Governor
• Sound Attenuated Enclosure
• Closed Coolant Recovery System
• Smart Battery Charger
• UV/Ozone Resistant Hoses
• ±1% Voltage Regulation
•
ページ2に含まれる内容の要旨
Application & Engineering Data QT060 GENERATOR SPECIFICATIONS ENGINE SPECIFICATIONS TYPE Synchronous MAKE Generac ROTOR INSULATION Class H MODEL In line STATOR INSULATION Class H CYLINDERS 4 3 TELEPHONE INTERFERENCE FACTOR (TIF) <50 DISPLACEMENT 2.4 Liter, 146 in. ALTERNATOR OUTPUT LEADS 3 PHASE 4 wire BORE 3.41 BEARINGS Sealed Ball STROKE 3.94 COUPLING Flexible Disc COMPRESSION RATIO 8.5:1 LOAD CAPACITY (STANDBY RATING) 60 kW INTAKE AIR SYSTEM Turbocharged/Aftercooled EXCITATION SYSTEM Direct L
ページ3に含まれる内容の要旨
® ® ® Generac Guardian Series Standby Generator - 60 kW OPERATING DATA KW RATING (LP/NG) 60/60 ENGINE SIZE 2.4 Liter 4 cyl. inline GENERATOR OUTPUT VOLTAGE/KW - 60Hz KW AMP CB Size 120/240V, 1-phase, 1.0 pf 60 250 300 120/208V, 3-phase, 0.8 pf 60 208 250 120/240V, 3-phase, 0.8 pf 60 180 200 277/480V, 3-phase, 0.8 pf 60 90 100 ENGINE FUEL CONSUMPTION (Natural Gas) (Propane) Natural Gas Propane 3 (ft /hr.) (gal/hr.) cu ft/hr Exercise cycle 123 1.34 49.3 25% of rated load 267 2.7 101 50% of rated l
ページ4に含まれる内容の要旨
48850-T CUSTOMER CONNECTIONS INTERCONNECTIONS QT060 UTILITY SUPPLY FROM RTS TRANSFER SWITCH SERVICE DISCONNECT QT SERIES ENGINE GENERATOR CONNECTION PANEL 0 GROUND 15B +12V 23 TRANSFER T1 NEUTRAL AIR 1 CONTACTOR 1 CUSTOMER SUPPLIED N1 N2 AIR 2 CONTACTOR NEUTRAL WIRE 2 PRIORITY 1 CONTACTOR 3 PRIORITY 2 UTILITY PRIORITY 3 CONTACTOR LOAD SHED 4 (C1 & VR1) PRIORITY 4 ON NOTE: N1 N2 MODULE MATCH WIRE NUMBERS TO TERMINAL NUMBERS 0 E1 E2 0 DC COMMON E1 E2 NEUTRAL BLOCK STANDBY 194 194 +12VDC (C2 & VR2
ページ5に含まれる内容の要旨
INSTALLATION LAYOUT QT060
ページ6に含まれる内容の要旨
AVAILABLE ACCESSORIES QT060 Model # Product Description If the temperature regularly falls below 32° F, install a cold weather kit to maintain 5630 Cold Weather Kit optimal battery temperature. Kit consists of battery warmer with thermostat built into the wrap. Recommended where the temperature regularly falls below 32° F for extended periods 5616 Extreme Cold Weather Kit of time. For liquid cooled units only. 5651 Base Plug Kit Add base plugs to the base of the generator to keep out debris.