SAFETY SETUP OPERATION MAINTENANCE Table of Contents Safety ......................................................... 2 Maintenance .............................................. 14 Setup .......................................................... 6 Parts List and Diagram .............................. 19 Specifications ............................................. 6 Warranty .................................................... 23 Operation .................................................... 8 W
ページ3に含まれる内容の要旨
Set up Precautions (cont.) 9. Improper connections to a building electrical 10. Do not operate the Generator before grounding. system can allow electrical current from the The Generator must be earth-grounded generator to backfeed into the utility lines. in accordance with all relevant electrical Such backfeed may electrocute utility company codes and standards before operation. workers or others who contact the lines during a power outage, and the generator may explode, burn, or cause fire
ページ4に含まれる内容の要旨
SAFETY SETUP OPERATION MAINTENANCE Operating Precautions (cont.) 16. Connect the Generator only to a load or 29. Stay alert, watch what you are doing and electrical system (120 volt or 240 volt) that is use common sense when operating this compatible with the electrical characteristics piece of equipment. Do not use this piece of and rated capacities of the Generator. equipment while tired or under the influence of drugs, alcohol or medication. 17. Insulate all connections and disconnected
ページ5に含まれる内容の要旨
Service Precautions 1. Before service, maintenance, or cleaning: 8. Have the equipment serviced by a qualified repair person using only identical replacement parts. a. Unplug all devices from the generator. This will ensure that the safety of the equipment b. Turn the engine switch to its “OFF” position. is maintained. Do not attempt any service or maintenance procedures not explained in this c. Allow the engine to completely cool. manual or any procedures that you are uncertain d. Then,
ページ6に含まれる内容の要旨
SAFETY SETUP OPERATION MAINTENANCE Functional Description Specifications 120/240V~, 60Hz Rated Output 5,500 Watts (6,500 max) Generator Two 3-Prong, duplex NEMA #5-20 120V Electrical Receptacle One 4-Prong, NEMA #L14-30 twistlock 120V/240V One DC Outlet 12VDC Displacement 420cc Horizontal Single Cylinder 4 stroke OHV Engine Type EPA phase III compliant Cooling System Forced air cooled Type 87+ octane unleaded gasoline Fuel Engine Capacity 6.1 Gallons (23L) 10W-30 above 32° F Type SAE 5W-30 a
ページ7に含まれる内容の要旨
Components and Controls (cont.) ON The following are descriptions of the controls OFF on the power panel. Your generator has sockets to power your products with circuit 3. Circuit Breakers: The circuit breaker protects the breakers to protect the voltage flow. Generator from overloading. The rating of the breaker and the load it protects are marked near the breaker. Should any of the Circuit Breakers trip, the Generator I will stop the electricity output. If this happens, unplug all l
ページ8に含まれる内容の要旨
SAFETY SETUP OPERATION MAINTENANCE Initial Tool Set Up/Assembly CAUTION: This generator is not intended to power Read the ENTIRE IMPORTANT sensitive electronic equipment without the addition of an SAFETY INFORMATION section at the appropriate line conditioner and surge protector (both not beginning of this manual including included). Sensitive electronic equipment includes, all text under subheadings therein but is not limited to, audio/video equipment, some before set up or use of th
ページ9に含まれる内容の要旨
Checking and Filling Fuel WARNING! TO PREVENT SERIOUS INJURY FROM FIRE: Full level Fill the fuel tank in a well-ventilated area Full level away from ignition sources. If the engine is hot from use, shut the engine off and wait for it to cool before adding fuel. Do not smoke. 4. Reinsert the Dipstick without threading it in and remove it to check the oil level. The oil level 1. Clean the Fuel Cap and the area around it. should be up to the full level as shown above. 2. Unscrew and remo
ページ10に含まれる内容の要旨
SAFETY SETUP OPERATION MAINTENANCE Starting the Engine 1. To start a cold engine, move the Choke to the CHOKE position. To restart a warm engine, leave the Choke in the RUN position. 2. Open the Fuel Valve. 3. Turn the Engine Switch to ON. I ON O 4. Grip the Starter Handle of the Engine loosely and pull it slowly several times to allow the gasoline to flow into the Engine’s carburetor. Then pull the Starter Handle gently until resistance is felt. A
ページ11に含まれる内容の要旨
Connecting Electrical Loads Familiarize yourself with the engine controls, power panel and how to start the engine before using the generator. Calculate the wattage of the products you will use with the generator and verify that the generator can handle the total load. WARNING! Connect only properly wired plugs to the generator. A plug that is spliced onto a different cord may be hazardous. Only a qualified electrician should wire a plug onto a cord. CAUTION Never exceed the rated capa
ページ12に含まれる内容の要旨
SAFETY SETUP OPERATION MAINTENANCE Calculating Total Wattage of Devices Used with the Generator Before using the Generator, check that the products Wattage Estimate Charts you want to plug into the unit are below the rated and Note: Wattages listed below are estimates for that maximum wattage ratings of the Generator. Use the type of equipment only. Check nameplate wattages Wattage Calculation Table below, and the watts listed on all loads before connecting to Generator. on your products,
ページ13に含まれる内容の要旨
Stopping the Engine in an Emergency 1. To stop the engine in an emergency, turn the Engine Switch off. I NOTICE: Generator shut-off under load may damage O OFF the generator and attached equipment. Stopping the Engine Under Normal Conditions 1. Before turning off the Engine, turn off all electrical loads, then unplug them. 2. Turn the Engine Switch off. I O OFF 3. Close the Fuel Valve. For Generator technical questions, please call 1-800-444-33
ページ14に含まれる内容の要旨
SAFETY SETUP OPERATION MAINTENANCE User-Maintenance Instructions TO PREVENT SERIOUS INJURY FROM ACCIDENTAL OPERATION: Turn the Power Switch of the generator to its “OFF” position, wait for the engine to cool, and disconnect the spark plug cap before performing any inspection, maintenance, or cleaning procedures. TO PREVENT SERIOUS INJURY FROM EQUIPMENT FAILURE: Do not use damaged equipment. If abnormal noise, vibration, or excess smoking occurs, have the problem corrected before further u
ページ15に含まれる内容の要旨
Checking and Filling Fuel Note: Do not use gasoline containing more than WARNING! TO PREVENT SERIOUS 10% ethanol (E10). Do not use E85 ethanol. INJURY FROM FIRE: Fill the fuel tank in a well-ventilated area Note: Do not use gasoline that has been stored in a away from ignition sources. If the engine is metal fuel container or a dirty fuel container. It can hot from use, shut the engine off and wait cause particles to enter the carburetor, effecting for it to cool before adding fuel.
ページ16に含まれる内容の要旨
SAFETY SETUP OPERATION MAINTENANCE Spark Plug Maintenance 1. Disconnect spark plug cap from end of plug. 4. When installing a new spark plug, adjust Clean out debris from around spark plug. the plug’s gap to the specification on the Specifications chart. Do not pry against the 2. Using a spark plug electrode, the spark plug can be damaged. Spark Plug wrench, remove the spark plug. 5. Install the new spark plug or the cleaned spark plug into the engine. Gasket-style: Finger-tighten unt
ページ17に含まれる内容の要旨
Troubleshooting Problem Possible Causes Probable Solutions Engine will not start FUEL RELATED: FUEL RELATED: 1. No fuel in tank or fuel valve closed. 1. Fill fuel tank and open fuel valve. 2. Choke not in CHOKE position, cold engine. 2. Move Choke to CHOKE position. 3. Gasoline with more than 10% ethanol used. 3. Clean out ethanol rich gasoline from fuel (E15, E20, E85, etc.) system. Replace components damaged by ethanol. Use fresh 87+ octane unleaded gasoline only. Do not use gasolin
ページ18に含まれる内容の要旨
SAFETY SETUP OPERATION MAINTENANCE Troubleshooting (cont.) Problem Possible Causes Probable Solutions Engine misfires 1. Spark plug cap loose. 1. Check wire connections. 2. Incorrect spark plug gap or 2. Re-gap or replace spark plug. damaged spark plug. 3. Defective spark plug cap. 3. Replace spark plug cap. 4. Old or low quality gasoline. 4. Use only fresh 87+ octane unleaded gasoline. Do not use gasoline with more than 10% ethanol (E15, E20, E85, etc.). 5. Diagnose and repair compression.
ページ19に含まれる内容の要旨
Parts List and Diagram PLEASE READ THE FOLLOWING CAREFULLY THE MANUFACTURER AND/OR DISTRIBUTOR HAS PROVIDED THE PARTS LIST AND ASSEMBLY DIAGRAM IN THIS MANUAL AS A REFERENCE TOOL ONLY. NEITHER THE MANUFACTURER OR DISTRIBUTOR MAKES ANY REPRESENTATION OR WARRANTY OF ANY KIND TO THE BUYER THAT HE OR SHE IS QUALIFIED TO MAKE ANY REPAIRS TO THE PRODUCT, OR THAT HE OR SHE IS QUALIFIED TO REPLACE ANY PARTS OF THE PRODUCT. IN FACT, THE MANUFACTURER AND/OR DISTRIBUTOR EXPRESSLY STATES THAT ALL REP
ページ20に含まれる内容の要旨
SAFETY SETUP OPERATION MAINTENANCE Parts List (cont.) Part Description Qty Part Description Qty 87 Grommet, Crankcase 1 125 Bolt, Flange 7 88 Bolt, Flange 4 126 Avr 1 89 Stay Comp., Muffler 1 127 Bolt, Flange, 3 90 Seal, Protector Muffler 1 128 Cover, Generator End 1 91 Protector Comp., Muffler Inner 1 129 Bolt, Hex. 1 92 Muffler Assy. 1 130 Frame Comp., Side 1 93 Protector, Muffler Side 1 131 Bolt, Flange 2 94 Bolt, Flange, 6×14 7 132 Stay, Air Cleaner 1 95 Protector Comp., Muffler Outer 1 133