ページ1に含まれる内容の要旨
® ®
GENERAC GUARDIAN SERIES
STANDBY GENERATORS
30 kW
Liquid-Cooled Engine Generator Sets
Includes: Standby Power Rating
Model QT030 (Bisque) - 30 kW 60Hz
• Generac Naturally Aspirated
Gaseous Fueled 1.5L Engine
• Two Line LCD Tri-lingual
Digital Nexus™ Controller
• Isochronous Electronic Governor
• Sound Attenuated Enclosure
• Closed Coolant Recovery System
• Smart Battery Charger
• UV/Ozone Resistant Hoses
• ±1% Voltage Regulation
• Natural Gas or LP Operation
• 2 Year Limited Warranty
•
ページ2に含まれる内容の要旨
Application & Engineering Data QT030 GENERATOR SPECIFICATIONS ENGINE SPECIFICATIONS TYPE Synchronous MAKE Generac ROTOR INSULATION Class H MODEL In line STATOR INSULATION Class H CYLINDERS 4 TELEPHONE INTERFERENCE FACTOR (TIF) <50 DISPLACEMENT 1.5 Liter ALTERNATOR OUTPUT LEADS 1-PHASE 4 wire BORE (mm) 77.4 ALTERNATOR OUTPUT LEADS 3-PHASE 6 wire STROKE (mm) 79.52 BEARINGS Sealed Ball COMPRESSION RATIO 11:1 COUPLING Flexible Disc INTAKE AIR SYSTEM Naturally Aspirated LOAD CAPACITY (STANDBY RATING)
ページ3に含まれる内容の要旨
® ® ® Generac Guardian Series Standby Generator - 30 kW OPERATING DATA KW RATING (LP/NG) 30/30 ENGINE SIZE 1.5 Liter 4 cyl. inline GENERATOR OUTPUT VOLTAGE/KW - 60Hz kW AMP CB Size 120/240V, 1-phase, 1.0 pf 30 125 150 120/208V, 3-phase, 0.8 pf 30 104 125 120/240V, 3-phase, 0.8 pf 30 90 100 Natural Gas Propane ENGINE FUEL CONSUMPTION (Natural Gas) (Propane) 3 3 (ft /hr.) (gal/hr.) ft /hr 60 0.7 24 Exercise cycle 240 2.6 96 25% of rated load 320 3.5 128 50% of rated load 400 4.4 160 75% of rated l
ページ4に含まれる内容の要旨
48850-T CUSTOMER CONNECTIONS INTERCONNECTIONS QT030 UTILITY SUPPLY FROM SERVICE DISCONNECT RTS TRANSFER SWITCH QT SERIES ENGINE GENERATOR CONNECTION PANEL 0 GROUND 15B +12V 23 TRANSFER T1 NEUTRAL AIR 1 CONTACTOR 1 N1 N2 CUSTOMER SUPPLIED AIR 2 CONTACTOR NEUTRAL WIRE 2 PRIORITY 1 CONTACTOR 3 PRIORITY 2 UTILITY PRIORITY 3 CONTACTOR LOAD SHED (C1 & VR1) PRIORITY 4 4 ON NOTE: N1 N2 MODULE MATCH WIRE NUMBERS TO TERMINAL NUMBERS 0 E1 E2 0 DC COMMON E1 E2 NEUTRAL BLOCK STANDBY 194 194 +12VDC (C2 & VR2
ページ5に含まれる内容の要旨
INSTALLATION LAYOUT QT030
ページ6に含まれる内容の要旨
AVAILABLE ACCESSORIES QT030 Model # Product Description If the temperature regularly falls below 32° F, install a cold weather kit to maintain 6175 Cold Weather Kit optimal battery temperature. Kit consists of battery warmer with thermostat built into the wrap. Recommended where the temperature regularly falls below 32° F for extended periods 6174 Extreme Cold Weather Kit of time. For liquid cooled units only. 5651 Base Plug Kit Add base plugs to the base of the generator to keep out debris.