ページ1に含まれる内容の要旨
North America’s Best
INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS
QUADRA-FIRE 3100 SERIES
CONGRATULATIONS—You are now the proud owner of one of the finest stoves in the world for your home —the
QUADRA-FIRE. Now, before installing your stove and building your first fire—record the serial number on the
warranty card. Serial number is located on the safety label on the rear of the stove.
PLEASE READ ALL OF THE OWNERS MANUAL AND SAFETY NOTES
IMPORTANT SAFETY NOTES:
1. When installing your
ページ2に含まれる内容の要旨
TABLE OF CONTENTS Safety label ......................................................................................................................................... 3 Dimensions ......................................................................................................................................... 4 Clearances to combustibles ................................................................................................................ 6 Safety listing ..................
ページ3に含まれる内容の要旨
3100 SAFETY LABEL (found on back of stove) Serial No. Model: Quadra-Fire 3100 Manufactaured by: Page 3
ページ4に含まれる内容の要旨
DIMENSIONS PEDESTAL MODEL 23" (584m m ) 24 1/2" (622m m) 2 1/4" (57m m ) 9" (229mm) 20 1/2" (521m m) 26 3/8" (670m m) FIGURE 1a LEG MODEL 23" (584mm) 24 1/2" (622m m ) 2 1/4" (57m m ) 9" (229mm) 21 1/2" (546m m ) FIGURE 1b Page 4
ページ5に含まれる内容の要旨
DIMENSIONS STEP TOP PEDESTAL MODEL 26 5/8" (676m m) 23 7/8" (606m m) 24 5/8" (626m m) 13 11/16" (348m m ) 2 13/16" (72m m ) 9" (229m m ) 4 5/16" (110m m ) FIGURE 2a 20 1/2" (521m m) 21" (533m m ) STEP TOP LEG MODEL 26 5/8" (676m m ) 23 7/8" (606m m ) 24 5/8" (626m m ) 13 11/16" (348m m ) 2 13/16" (72m m ) 9" (229m m ) 4 5/16" (110m m ) 25" (635m m ) 21 1/2 (546m m ) FIGURE 2b Page 5
ページ6に含まれる内容の要旨
CLEARANCES TO COMBUSTIBLES (UL AND ULC) FLOOR PROTECTION: Floor protector must be noncombustible material or equivalent, extending beneath heater and to the front/ sides/rear as indicated. NOTE: A 3/8” (10mm) minimum thickness tile or equivalent is recommended, but not required. Minimum clearances to Combustible Materials (in inches and millimeters) for Quadra-Fire 3100 Standard Stove Chimney & Installation Clearance Connector A B C D E F Residential Standard Note 1 14”(356) 26”(661) 18”(457)
ページ7に含まれる内容の要旨
SAFETY LISTING The Quadra-Fire 3100 is listed by OMNI-Test Laboratories, Inc. , Beaverton, Oregon, to UL 1482-83, (UM)84 HUD and ULC S627. It is also approved for mobile home installations with outside combustion air in the U.S. (see pages 15 and 16 for further details). For residential installations in Canada without an outside combustion air kit, a source of fresh air into the room must be provided. INSTALLATION MATERIALS NEEDED FOR YOUR SAFETY CHIMNEY CONNECTOR (also known as flue pipe or s
ページ8に含まれる内容の要旨
CHIMNEY CONNECTOR The chimney connector must be 6” (152mm) diameter with a minimum thickness of 24 gauge. Do not use aluminum or galvanized steel. They cannot properly withstand the extreme temperatures of a wood fire. Do not use chimney connector pipe as a chimney. You must connect your stove to a chimney comparable to those illustrated in this manual. Chimney connector sections must be attached to the stove and to each other with the crimped end toward the stove (Figure 3). This allows cre
ページ9に含まれる内容の要旨
The chimney must have a fire clay flue liner (or equivalent) with a minimum thickness of 5/8” (16mm) and must be installed with refractory mortar. There must be at least ½” (13mm) air space between the flue liner and the chimney wall (Figure 4). An equivalent liner must be a listed chimney liner system or other approved material. FIGURE 4 A chimney inside the house must have at least 2” (50mm) of clearance to the combustible structure. A chimney outside the house must have at least 1” (25mm)
ページ10に含まれる内容の要旨
Remember that insulation must not contact the chimney. There must be air space around the chimney. Insulation must be 2” (50mm) or more from the chimney (Figure 6). FIGURE 6 A chimney must be the required height above the roof or other obstruction for safety and proper draft operation. The chimney must be a minimum of 3’ (914mm) higher than the highest point where it passes through the roof, and at least 2’ (610mm) higher than the highest part of the roof or structure that is within 10’ (3048mm
ページ11に含まれる内容の要旨
2. THIMBLE: An approved thimble must be used when the connection from the stove is made through a combustible wall to a masonry chimney. There are several methods you can use for connection through a combustible wall, two of which are illustrated in this manual. For additional methods, consult local building authorities or use the standards set forth in NFPA 211. Also, listed prefabricated metal thimbles are available for use with wood stoves. The manufacturer’s installation for the thimbles
ページ12に含まれる内容の要旨
FIGURE 9 Minimum 3 ½” (89mm) [4” (102mm) nominal] thick solid bricks are to be used. The fire clay liner (ASTM C35 or equivalent), 5/8” (16mm) wall thickness, must not penetrate into the chimney beyond the inner surface of the chimney flue liner and must be firmly cemented in place. If it is necessary to cut a hole in the chimney liner, use extreme care to keep it from shattering. Refractory mortar must be used at the junction with the chimney liner. After the assembly is complete, insert th
ページ13に含まれる内容の要旨
First, build the frame for the thimble, making sure that it is no smaller than 14½” (368mm) diameter, which will maintain a 2” (50mm) air space around the chimney section. Attach the wall spacer to the chimney side of the frame. Then insert the frame into the opening, toe-nailing it to the wall studs. Install the wall band in the framing to secure the chimney section in place. Insert a single section of chimney connector into the chimney through the wall band, being sure it does not protrude
ページ14に含まれる内容の要旨
CONNECTION TO A METAL PREFABRICATED CHIMNEY When a metal prefabricated chimney is used, the manufacturer’s installation instructions must be followed precisely. You must also purchase (from the same manufacturer) and install the ceiling support package or wall pass-through and “T” section package, firestops (where needed), insulation shield, roof flashing, chimney cap, etc. Maintain the proper clearance to the structure as recommended by the manufacturer. This clearance is usually a minimum o
ページ15に含まれる内容の要旨
FIGURE 13 EXTERIOR CHIMNEY RUNNING UP THE OUTSIDE OF THE RESIDENCE *Note: Unit has not been tested with a horizontal connector. Refer to local building codes. MOBILE HOME INSTALLATION You must use a Quadra-Fire 3100 outside air kit (see page 16 for part numbers) for installation in a mobile home. Use of alternative material will void warranty. 1. An outside air inlet must be provided for combustion and be unrestricted while unit is in use. 2. Unit must be secured to the mobile home structure
ページ16に含まれる内容の要旨
OUTSIDE AIR KIT INSTALLATION 3100 LEG MODELS Part #831-1740 1. Front cover plate attaches to firebox bottom below ash lip with two ¼”-20 mounting screws. 2. Mount rear air intake cover plate with two mounting screws. 3. Install each side cover with two 8-32 screws. 4. Floor installation: Cut a 3” (76mm) minimum hole in the floor to accommodate outside air piping. Use 3” (76mm) metal flex or rigid piping to directly connect outside air to the unit or into vented crawl space. 4” (102mm) pipe is
ページ17に含まれる内容の要旨
PEDESTAL/LEG KIT INSTALLATION WARNING: DO NOT OPERATE YOUR QUADRA-FIRE STOVE BEFORE FULLY ASSEMBLING ALL COMPONENTS. BURNING YOUR STOVE WITHOUT A PEDESTAL OR LEG KIT ATTACHED WILL VOID YOUR WARRANTY, AND COULD PRESENT A SAFETY HAZARD. PEDESTAL MODEL 1. Place protective pad or stove pallet on floor. 2. Lay body of stove on its back on protective pad or pallet. FOR INSTALLATION OF 3. Slide pedestal over adapter on bottom of stove ASH REMOVAL 4. Line up holes in sides of pedestal with holes i
ページ18に含まれる内容の要旨
ASH REMOVAL SYSTEM INSTALLATION 1. Remove ash removal system top and bottom cover plates by loosening nuts under stove. 2. Discard both plates. 3. Insert ash removal system grate into opening in firebox floor. 4. Continue with proper installation according to model you have purchased: pedestal or leg. PEDESTAL MODEL 1. Place protective pad or stove pallet on floor. 2. Lay body of stove on its back on protective pad or pallet. 3. Line up holes in ash removal system with holes in adapter o
ページ19に含まれる内容の要旨
ASH REMOVAL SYSTEM OPERATING AND CLEANING CAUTION: Do not operate stove with ash removal system door open. Store ash in metal container until hot embers have cooled completely. 1. When stove is cool, open front door and brush most of the ash into the center of the firebox. Remember to leave ¼” to ½” (6-13mm) of ash on the firebox floor to act as a natural grate, allowing air to flow freely underneath wood. 2. Clean ash down through the ash removal system grate into the drawer below. If there
ページ20に含まれる内容の要旨
OPERATING INSTRUCTIONS IMPORTANT - PLEASE READ BEFORE USING STOVE BURNING PROCESS In recent years there has been an increasing concern about air quality. Much of the blame for poor air quality has been placed on the burning of wood for home heating. In order to improve the situation, we at Quadra-Fire have developed cleaner-burning wood stoves that surpass the requirements for emissions established by our governing agencies. These wood stoves, like any other appliances, must be properly operat