ULTRA FLAME
DIRECT VENT GAS STOVE
INSTRUCTIONS MANUAL
WHAT TO DO IF YOU SMELL GAS:
WARNING: If the information in these
instructions is not followed exactly, a fire or
explosion may result causing property • Do not try to light any appliance.
damage, personal injury or loss of life.
• Do not touch any electric switch; do not
use any phone in your building.
FOR YOUR SAFETY: Do not store or use
gasoline or other flammable vapours and
• Immediately call your gas supplier f
ページ2に含まれる内容の要旨
ULTRA FLAME DIRECT VENT GAS STOVE 1 TABLE OF CONTENTS GENERAL INFORMATION.................................................................................................................................................... 2 WARNING.............................................................................................................................................................................. 2 TECHNICAL SPÉCIFICATIONS................................................................
ページ3に含まれる内容の要旨
ULTRA FLAME DIRECT VENT GAS STOVE 2 GENERAL INFORMATION The ULTRA FLAME DIRECT VENT GAS STOVE is a high-efficiency gas appliance with a maximum input rating of 30 000 Btu/h (8,8 kW) with natural gas or 26,000 Btu/h (7,6 kW) with propane. It features an adjustable millivolt valve and a constant pilot independent of any electrical source. Your appliance will therefore continue to heat your house in the event of a power failure. You can set the height of the flame to your liking by turning th
ページ4に含まれる内容の要旨
ULTRA FLAME DIRECT VENT GAS STOVE 3 TECHNICAL SPÉCIFICATIONS Dimensions Dimensions Height : 29 in 735 mm Width : 26 in 920 mm Depth : 23 in 585 mm Ceramic Glass Front : 18 3/16 in x 15 15/16 in 462 mm x 405 mm Sides : 5 1/16 in x 15 15/16 in 129 mm x 405 mm Weight : 140 lbs 64 kg Color : Metallic Black Clearances to Combustibles • Back : 1 po 25 mm • Side : 14 po 355 mm • Corner : 4 po 100 mm • Top : 36 po 915 mm Note 1 • Floor :combustible TOP VIEW Note 1
ページ5に含まれる内容の要旨
ULTRA FLAME DIRECT VENT GAS STOVE 4 Burner Natural Gas Propane LP Maximum Input, BTU/h (kW) minimum : 20 000 (5,9) 20 000 (5,9) maximum : 30 000 (8,8) 26 000 (7,6) Inlet Pressure INWC (kPa) minimum : 5,0 (1,3) 11,0 (2,8) maximum : 7,0 (1,8) 14,0 (3,5) Manifold Pressure INWC (kPa) minimum : 1,8 (0,5) 7,0 (1,8) maximum : 3,5 (0,9) 10,0 (2,5) 36 52 Burner orifice, ∅ : Injecteur du pilot. ∅ : 51 30 Gas Valve SIT 820 Nova mV Natural Gas Propane LP Gas Valve : Model SIT
ページ6に含まれる内容の要旨
ULTRA FLAME DIRECT VENT GAS STOVE 5 Available Wall Venting Kits Venting Kit for Direct Installation AC05506 Venting Kit for Corner Installation AC05507 DESCRIPTION DESCRIPTION • Outer pipe (∅ 8 in.) for admission of fuel-air in carbon • Outer pipe (∅ 8 in.) for admission of fuel-air in carbon steel, black 24GA ; steel, black 24GA ; • Inner flexible pipe (∅ 5 in.) in aluminum allowing the • Inner flexible pipe (∅ 5 in.) in aluminum allowing the exhaust of the flue ; exhaust of the
ページ7に含まれる内容の要旨
ULTRA FLAME DIRECT VENT GAS STOVE 6 SELECTING TYPICAL INSTALLATION Safety Notice • Improper installation may result in a house fire. Follow installation directions. Installation must be done in accordance with local building codes or, in the absence of local codes, with current CAN/CGA B 149 installation codes for gas appliances (Canada) and current National Fuel Gas Code ANSI Z223.1 (USA). • A qualified installer must do installation. • This gas stove must be vented outside. • This gas
ページ8に含まれる内容の要旨
ULTRA FLAME DIRECT VENT GAS STOVE 7 Critical Length of Venting Pipes The following table shows maximum length to be respected while installing your appliance: In conclusion: • If you have no rise (Vertical run= 0 ft) : The maximum horizontal run is 5 ft ; • If you have a known horizontal run : Minimum vertical run = Horizontal run – 5 ft ; • If you have a vertical run shorter than 5 ft : Maximum horizontal run = Vertical run + 5 ft. • If you have a vertical run longer than 5 ft :
ページ9に含まれる内容の要旨
ULTRA FLAME DIRECT VENT GAS STOVE 8 K. 72" Clearance to a mechanical air supply inlet L. 84" Clearance above paved sidewalk or a paved driveway located on public property. A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwelling M. 36" Clearance under veranda, porch, deck, or balcony. Only permitted if veranda, porch, deck, or balcony is fully open on a minimum of 2 sides beneath the floor. Local
ページ10に含まれる内容の要旨
ULTRA FLAME DIRECT VENT GAS STOVE 9 Installation of Wall Venting Kits Direct Vent Kit VENT TERMINAL RADIATION SHIELD -min 1" -max 60" Direct Vent Direct Vent Details 1. Move the stove to its position; 2. Install temporary a 8 in. section (4) to visualize where the opening to be done thru the wall. Center of the opening should be at about 23 ½ “above the base of the stove; Note: Horizontal run should have a slope of ¼ in per foot. 3. Make a 10-1/2" x 10-1/2" opening in the wall, 23
ページ11に含まれる内容の要旨
ULTRA FLAME DIRECT VENT GAS STOVE 10 13. Seal around the 8 in. pipe to prevent cold air to get into 5" LOCKING BAND the house. 14. Seal around the cover slots to avoid water infiltration SCREWS into the vent terminal; 15. Insert spring spacers into the 5 in. flexible pipe; 8"RIGID A 16. Put some high temp silicone on the stove’s 5 in. flange. Insert one locking band on the 5 in. pipe and insert it on the stove flange. Make sure seal is perfect. Tight the locking band 17. Fix the 8 i
ページ12に含まれる内容の要旨
ULTRA FLAME DIRECT VENT GAS STOVE 11 8. Secure the 8 in. pipe to vent terminal wall plate with the metal screw; 9. Fix finally the vent terminal wall plate with six 2 ½ in screws (12). 10. Insert the 5 in. flexible pipe (3) into the 8 in. pipe and fix it to the vent terminal casing. Use high temperature silicone and one locking band to secure it in pace; NOTE: All joints must be sealed with RTV silicone, 315°C. (600°F) temperature resistance. 11. Install the vent casing and the
ページ13に含まれる内容の要旨
ULTRA FLAME DIRECT VENT GAS STOVE 12 Direct Vent Kit for Basement Installation 1. Move the stove to its position; 2. Install temporary an 8 in. section (4) to visualize where the opening to be done thru the wall. Center of the opening should be at about 23 ½ “above the base of the stove; Note: Horizontal run should have a slope of ¼ in per foot. 3. Make a 10-1/2" x 10-1/2" opening in the wall, 23-1/2" inches in order to introduce the radiation shield thru the wall; 4. Cut the radi
ページ14に含まれる内容の要旨
ULTRA FLAME DIRECT VENT GAS STOVE 13 11. Install the vent casing and the cover in place 12. Seal around the terminal to prevent water leakage into the house 13. Seal around the 8 in. pipe to prevent cold air to get into the house. 14. Seal around the cover slots to avoid water infiltration into the vent terminal; 15. Insert spring spacers into the 5 in. flexible pipe; 16. Use all necessary rigid sections to meet your specific needs. Fix 8 in. pipes together with metal screws
ページ15に含まれる内容の要旨
ULTRA FLAME DIRECT VENT GAS STOVE 14 Direct Vent Kit for Floor Installation 1. Move the stove to its position; 2. Install temporarily an 8 in. section (4) to visualize where the opening is to be done thru the wall. Center of the opening should be at about 23 ½‘’ above the base of the stove; Note: Horizontal run should have a slope of ¼ in per foot. 3. Make a 10-1/2" x 10-1/2" opening in the wall, 23-1/2" inches in order to introduce the radiation shield thru the wall; 4. Cut the ra
ページ16に含まれる内容の要旨
ULTRA FLAME DIRECT VENT GAS STOVE 15 11. Install the vent casing and the cover in place 12. Seal around the terminal to prevent water leakage into the house 13. Seal around the 8 in. pipe to prevent cold air to get into the house. 14. Seal around the cover slots to avoid water infiltration into the vent terminal; 15. Insert spring spacers onto the 4 in. flexible pipe; Use all necessary rigid sections to meet your specific needs. Fix 8 in. pipes together with metal screws; 16. Put som
ページ17に含まれる内容の要旨
ULTRA FLAME DIRECT VENT GAS STOVE 16 Gas Piping • Move the ULTRA FLAME to the desired position. • Mark the location for the gas inlet pipe and the location where the vent pipes will go through the wall. Remove the appliance. • Route a 3/8" minimum NPT iron pipe gas line to the desired location. • Install a shutoff valve to the gas line. Tighten securely using a pipe joint compound. • Check the gas line piping for leaks. Use a soap and water solution. CAUTION: Do not use open flame to
ページ18に含まれる内容の要旨
ULTRA FLAME DIRECT VENT GAS STOVE 17 Logs Installation 1. Remove the front glass. 4. Place logs 2 and 3 against the stops in the middle 2. Locate the log grate in the retainers in the right of the grate. Again see that grooves in the bottom and left rear corners. of the logs line up with the grate. 3. Place the rear log (1) against the rear log stop. 5. Place log 4 into the grooves of logs 1 and 2. Make sure grooves under the log line up with the 6. Log 5 sits over log 1 and 3. grate. 7.
ページ19に含まれる内容の要旨
ULTRA FLAME DIRECT VENT GAS STOVE 18 OPERATION OF YOUR STOVE For your safety CAUTION: • A qualified installer must perform installation of the appliance, venting, piping and adjustments. • During operation, this stove is hot. Do not touch. Keep children, clothing and flammable materials away • Hot when in operation. Keep children, furniture, clothing and flammable material away from the appliance. • Make sure your stove is in good condition. Verify that the bay window close perfectly, a
ページ20に含まれる内容の要旨
ULTRA FLAME DIRECT VENT GAS STOVE 19 Shut down Instructions To turn the burner OFF • Push in and rotate the gas control knob clockwise to "PILOT" position. Do not force. To turn the pilot OFF • Push in and rotate the gas control knob clockwise to "OFF" position. Do not force. Optional Blower The blower control contains a variable speed switch and a thermal switch. When the stove is operating, the thermal switch will turn on at 120° F, allowing the blower to operate. When the stove co