ページ1に含まれる内容の要旨
Gas Fireplaces
Gas Fireplaces
P36 - P36D Gas Fireplace
P36 - P36D Zero Clearance Direct Vent Gas Fireplace
Model P36-NG4 P36-LP4 P36D-NG1 P36D-LP1
Fuel Type Natural Gas Propane Natural Gas Propane
Minimum Supply 5” W.C. 12” W.C. 5” W.C. 12” W.C.
Pressure (1.25 kPa) (3.00 kPa) (1.25 kPa) (3.00 kPa)
Manifold 3.8” W.C. 11” W.C. 3.8” W.C. 11” W.C.
Pressure - High (0.95 kPa) (2.74 kPa) (0.95 kPa) (2.74 kPa)
Manifold 1.1” W.C. 2.9” W.C. 1.1” W.C. 2.9” W.C.
Pressure - Low (0.27 kPa) (0.72 kPa) (0.2
ページ2に含まれる内容の要旨
Gas Fireplaces P36 - P36D Gas Fireplace Framing and Finishing Vent Clearances Clearance Dimension 1) Determine the total thickness of facing material (e.g. drywall plus Horizontal - Top 2” (51mm) ceramic tiles) to allow the fi nished surface to be fl ush with the front Horizontal - Side 1-1/2” (38mm) of the unit. Total facing thickness can vary from 1/2” (13mm) to 1-1/4” (32mm) thick. Horizontal - Bottom 1-1/2” (38mm) 2) Frame in the enclosure for the unit with framing material. Vertical (Fle
ページ3に含まれる内容の要旨
Gas Fireplaces Gas Fireplaces P36 - P36D Gas Fireplace FPI Direct Vent System (Flex) Snorkel Terminations Horizontal Terminations Only Snorkel Terminations: These venting systems, in combination with the P36 / P36D Direct Vent For installations requiring a vertical rise on the exterior of the building, Gas Fireplace, have been tested and listed as a direct vent heater system 14-inch and 36-inch tall Snorkel Terminations and the Riser Vent are by Warnock Hersey. The location of the terminati
ページ4に含まれる内容の要旨
Gas Fireplaces P36 - P36D Gas Fireplace Rigid Pipe Venting Horizontal or Vertical Terminations Vertical 2 4 6 8 10 12 12 14 16 18 20 22 24 26 28 30 Terminal Storm Collar Part # 953 Vinyl Siding 40 Standoff (Optional) Part #950 Flashing 943 or 943S 38 Ceiling Firestop Horizontal (Part # 963) Termination Cap (Part #946-523/P) 36 Wall Thimble Part # 942 2 4 6 8 10 12 34 Pipe Length Adj.Pipe Length 11" - 14-5/8" o 90 Elbow 40 32 Alternate Horizontal Termination Caps 38 Pipe 30 Length 2 4 8 36 6 10
ページ5に含まれる内容の要旨
Gas Fireplaces Gas Fireplaces P36 - P36D Gas Fireplace Vertical Venting with Two (2) 90° Elbows Two 45° elbows = One 90° elbow Option V H V+ V1 Maximum total pipe: length, of all sections, must not exceed A) 0’ Min. 2’ Max. 1’ Min. 30 feet. Total horizontal sections must B) 1’ Min. 4’ Max. 3’ Min. not exceed 8 feet. C) 2’ Min. 5’ Max. 4’ Min. Minimum of 1 foot between 90° elbows is required. D) 3’ Min. 6’ Max. 5’ Min. E) 4’ Min. 7’ Max. 6’ Min. F) 5’ Min. 8’ Max. 7’ Min. Vertical Venting w
ページ6に含まれる内容の要旨
2 4 6 8 10 12 40 38 2 4 8 36 6 10 12 34 40 32 38 30 36 28 34 Gas Fireplaces 26 32 P36 - P36D Gas Fireplace Note: Must use optional fl ue adapter (Part # 510-994) when using 24 Venting Arrangements - Horizontal 30 Rigid Pipe. Terminations 22 • Maintain clearances to combustibles. 28 This diagram shows all allowable combinations of vertical runs with • Horizontal vent must be supported every 3 feet. • Firestops are required at each fl oor level and whenever passing horizontal terminations, u
ページ7に含まれる内容の要旨
Gas Fireplaces Gas Fireplaces P36 - P36D Gas Fireplace Horizontal Venting with Two (2) 90° Elbows Two 45° elbows = One 90° elbow Option V H+ H1 Maximum total pipe: length, of all sections, must not exceed A) 0’ Min. 2’ Max. 30 feet. Total horizontal sections must B) 1’ Min. 3’ Max. not exceed 8 feet. C) 2’ Min. 4’ Max. Minimum of 1 foot between 90° elbows is required. D) 3’ Min. 5’ Max. E) 4’ Min. 6’ Max. F) 5’ Min. 7’ Max. F) 6’ Min. 8’ Max. Horizontal Venting with Three (3) 90° Elbow
ページ8に含まれる内容の要旨
Gas Fireplaces P36 - P36D Gas Fireplace Vertical termination with co-linear Required Parts: fl ex system Part # Description 946-529 Co-linear DV Vertical Termination Cap The appliance must not be connected to a chimney fl ue 948-305 3” Flex - 35 ft. serving a separate solid fuel burning appliance. 946-563 Coaxial to Co-linear Adapter Kit which contains the following: Co-linear Flex Adapter Outer Pipe Inner Pipe Adapter Masonry chimneys may take various contours which the fl exible liner will