ページ1に含まれる内容の要旨
www.hampton-fi re.com
Owners &
H25 Direct Vent Gas Fireplace
Installation Manual
MODELS: H25-NG1 Natural Gas H25-LP1 Propane
WARNING: FOR YOUR SAFETY This appliance may only be
If the information in these instructions are not installed in an aftermarket
followed exactly, a fi re or explosion may result What to do if you smell gas: permanently located, manu-
causing property damage, personal injury or loss Do not try to light any appliance factured (USA only) or mobile
of life.
ページ2に含まれる内容の要旨
® HAMPTON Direct Vent Freestanding Gas Stove To the New Owner: Congratulations! ® You are the owner of a state-of-the-art Hampton Gas Stove by FPI FIREPLACE PRODUCTS INTERNATIONAL LTD. The H25 is a hand crafted appliance and has been designed to provide you with all the warmth and charm of a wood fi replace at the fl ick of a switch. The model H25 has been approved by Warnock Hersey for both safety and effi ciency. As it also bears our own mark, it promises to provide you with economy, comf
ページ3に含まれる内容の要旨
TABLE OF CONTENTS Log Set Installation ......................................................32 SAFETY LABEL Decorative Door Grill Installation .................................34 Wall Thermostat .........................................................34 Safety Label ..................................................................4 Remote Control ..........................................................34 Final Check .................................................................35 REQUI
ページ4に含まれる内容の要旨
SAFETY LABEL ® This is a copy of the label that accompanies NOTE: Hampton units are constantly being each Direct Vent Freestanding Gas Stove. improved. Check the label on the unit and if We have printed a copy of the contents here there is a difference, the label on the unit is for your review. the correct one. COPY OF SAFETY LABEL FOR H25-NG1 & H25-LP1 For the State of Massachusetts, installation and repair must be done by a plumber or gasfi tter licensed in the Commonwealth of Massachu
ページ5に含まれる内容の要旨
REQUIREMENTS MA Code - CO Detector (for the State of Massachusetts only) 5.08: Modifications to NFPA-54, Chapter 10 (2) Revise 10.8.3 by adding the following additional requirements: (a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished gr
ページ6に含まれる内容の要旨
INSTALLATION This appliance installation must comply with the IMPORTANT MESSAGE DUE TO HIGH TEMPERATURES, manufacturer's installation instructions and local THE APPLIANCE SHOULD BE codes, if any. In the absence of local codes fol- SAVE THESE low the current National Fuel Gas Code, ANSI LOCATED OUT OF TRAFFIC AND INSTRUCTIONS Z223.1 and the current National Electrical Code AWAY FROM FURNITURE AND ANSI/NFPA 70 in the U.S.A., and the current DRAPERIES. The Direct Vent Freestanding Gas St
ページ7に含まれる内容の要旨
INSTALLATION Thermostat. Some areas may have further 2) If required, adjusting the primary air to ensure Emissions from burning wood or gas could requirements, check local codes before that the fl ame does not carbon. First allow contain chemicals known to the State of Cali- installation. the unit to burn for 15-20 min. to stabilize. fornia to cause cancer, birth defects or other reproductive harm. 5) This appliance is Listed for Alcove installa- CAUTION: Any alteration to the product tha
ページ8に含まれる内容の要旨
INSTALLATION 4) Remove the nylon hole plug from the control OPTIONAL FAN LOCATING YOUR panel. GAS STOVE INSTALLATION 5) Install the fan speed controller onto the control panel and secure with nut and Fan Kit Contains: When selecting a location for your stove, ensure washer. Connect the red and black wires that the clearances listed above are met as well from the wire harness to speed controller. as ensuring that there is adequate accessibility Qty. Description NOTE: Speed control wire
ページ9に含まれる内容の要旨
INSTALLATION 9) Place the blower close to the base of the unit and feed the long red 12) Before re-attaching the rear access panel, the valve wires and the fan wires need to be connected. and black wires through the opening of the base of the unit and connect them to the thermodisc. Re-connect the red and grey valve wires. Connect the fan wires. 10) Feed the short red and black wires through the small hole at the base of the unit. 13) Slide the Rear Access Panel back into position and secur
ページ10に含まれる内容の要旨
INSTALLATION VENTING INSTALLATION SAFETY PRECAUTIONS INTRODUCTION PRECAUTIONS FOR THE INSTALLER The Horizontal Termination Kit and the Simpson These venting systems are engineered products 1) Wear gloves and safety glasses for protec- Dura-Vent Direct Vent System Model DV-GS that have been designed and tested for use tion. venting systems, in combination with the Direct with the H25-NG1, and H25-LP1. The warranty Vent Freestanding Gas Stoves, H25-NG1, and will be voided and serious fi re, he
ページ11に含まれる内容の要旨
A= Clearance above grade, veranda, porch, deck, or balcony *(min. 12"/30cm) B= Clearance to window or door that may be opened *(12"/30cm) C= Clearance to permanently closed window *(min. 12"/30cm) D= Vertical clearance to ventilated soffi t located above the terminal within a horizontal distance of (24"/60cm) from the centerline of the terminal (min. 22"/55cm) check with local code. E= Clearance to unventilated soffi t (min. 12"/30cm) F= Clearance to outside corner: with AstroCap Termination Ca
ページ12に含まれる内容の要旨
INSTALLATION 4” X 6-5/8” RIGID PIPE CROSS REFERENCE CHART Components from different Manufacturers may not be mixed. Not All Rigid Pipe components are available directly from FPI. Simpson American Metal ® Simpson Metal-Fab Security ® Selkirk ® Direct Vent GS Description Products ® ® Direct Vent Pro Sure Seal Secure Vent Direct-Temp™ Amerivent Direct Discontinued 6” Pipe Length, Galvanized 46DVA-06 908 4DT-6 N/A 4D6 SV4L6 6” Pipe Length, Black 46DVA-06B 908B 4DT-6B N/A 4D6B SV4LB6 7” Pipe Leng
ページ13に含まれる内容の要旨
INSTALLATION 4” x 6-5/8” Rigid Pipe Cross Reference Chart (Cont.) Components from different Manufacturers may not be mixed. Not All Rigid Pipe components are available directly from FPI. Simpson American Metal ® Simpson Metal-Fab Security ® Selkirk ® Direct Vent GS Description Products ® ® Direct Vent Pro Sure Seal Secure Vent Direct-Temp™ Amerivent Direct Discontinued 46DVA-IS - N/A from FPI N/A N/A 4DAIS12 N/A SV4RSA Attic Insulation Shield 12” Attic Insulation Shield - Cold Climates 36” N/
ページ14に含まれる内容の要旨
INSTALLATION RIGID PIPE VENTING SYSTEMS Horizontal or Vertical Terminations Vertical Alternate Termination Horizontal Cap Termination Caps Storm Collar Vinyl Siding Standoff (Optional) Flashing Horizontal Termination Ceiling Firestop Cap Wall Thimble Pipe Length Adj.Pipe Length 11" - 14-5/8" o 90 Elbow WARNING: Do not combine venting components from 24" Pipe different venting systems. Length TM However use of the the AstroCap and FPI Riser is acceptable with all systems. This product has be
ページ15に含まれる内容の要旨
INSTALLATION VENTING ARRANGEMENTS Horizontal Terminations for Vertical Terminations Systems for All Venting Systems Residential Manufactured and Mobile Homes The shaded areas in the diagram below show all The shaded area in the diagram below shows all allowable combinations of straight o vertical and offset to vertical runs with vertical terminations. Maximum two 45 allowable combinations of vertical runs with hori- O zontal terminations. Maximum one 90 elbow (two elbows. o o 45 elbows equa
ページ16に含まれる内容の要旨
INSTALLATION o Horizontal Venting with Two (2) 90 Elbows o o One 90 elbow = Two 45 elbows. With these options, maxi- Option V H + H1 mum total pipe length is 30 A) 2' Min. 4' Max. feet with minimum of 6 feet B) 3' Min. 5' Max. total vertical and maximum C) 4' Min. 6' Max. 8 feet total horizontal. Please note minimum 1 D) 5' Min. 7' Max. o foot between 90 elbows E) 6' Min. 8' Max. is required. H1 Lengths do not include elb
ページ17に含まれる内容の要旨
INSTALLATION o Vertical Venting with Two (2) 90 Elbows o o One 90 elbow = Two 45 elbows. Option V H V + V1 With these options, max. total pipe length is 30 feet with min. A) 1' Min. 4' Max. 2' Min. of 6 feet total vertical and max. B) 2' Min. 5' Max. 3' Min. 8 feet total horizontal. C) 3' Min. 6' Max. 4' Min. Please note min. 1 foot o D) 4' Min. 7' Max. 5' Min. between 90 elbows is re- quired. E) 5' Min. 8' Max. 6' Min. V1 Lengths do not include elbow i
ページ18に含まれる内容の要旨
INSTALLATION VERTICAL TERMINATION WITH CO-LINEAR FLEX SYSTEM Masonry chimneys may take various contours which the fl exible liner will accommodate. However, THE APPLIANCE MUST NOT BE CONNECTED TO A CHIMNEY FLUE keep the fl exible liner as straight as possible, avoid unnecessary bending. SERVING A SEPARATE SOLID FUEL BURNING APPLIANCE. The Air Intake pipe must be attached to the inlet air collar of the termination cap. This appliance is designed to be attached to Alternate Approved Caps Require
ページ19に含まれる内容の要旨
INSTALLATION DV STOVE HORIZONTAL VENT KIT DV 2 ft. Stove Vent Kit (Part # 946-116) and DV 4 ft. Stove Vent Kit (946-216) includes all the parts needed to install the H25 Direct Vent unit with minimum horizontal and vertical vent dimensions. For installations that require longer vertical and/or horizontal vents use the Dura-Vent system as shown in the "Dura-Vent Termination Kit" and "Dura-Vent Venting Components" sections. Qty. Description 1) 1 Rigid Pipe Section (Kit # 946-116: 2 ft. (
ページ20に含まれる内容の要旨
INSTALLATION 9) Secure the 4" dia. fl ex liner to the 4" adapter with Mill-Pac and 3 of the #8 x 1/2" screws (stainless steel). 10) Slide the decorative Thimble Cover over the pipe sections and secure with 4 screws (#8 x 1-1/2" drill point, black) to the wall. o o 11) Slide the 90 elbow (crimp end up), the 45 elbow and the 4 ft. pipe section (crimp end up) over the 4" dia. fl ex liner. 12) Install the spring spacers onto the pipe sec- tions. 13) Secure the 4" dia. fl ex liner with adapter o