Setup Manual
®
BACnet Protocol Gateway for TempTrac and
XR10CX Water Heater Control
When a BAS interface with Temptrac or the XR10CX requires a protocol other than the standard
Modbus RTU for Temptrac and XR10CX, PVI Industries offers a premapped gateway from FieldServer
Technologies. The ProtoCessor ProtoNode RER currently supports BACnet IP or MSTP. Consult factory
for other protocols.
This manual is meant to be a general overview of the application of this gateway, for additional
ページ2に含まれる内容の要旨
SYSTEM OVERVIEW TEMPTRAC & XR10CX BACnet IP/MSTP BUILDING AUTOMATION SYSTEM BACnet GATEWAY Modbus RTU XR10CX OPERATING CONTROL TEMPTRAC OPERATING CONTROL Protonode + ‐ GND R C GND OPTIONAL FIELD INSTALLED Power 5Vdc, 9‐30 TERMINATION RESISTOR Vac or Vdc COMMON/SHIELD RS‐485 +/‐ LT PREINSTALLED TERMINATION TempTrac ‐ + ‐ + XJ485 SERIAL INTERFACE XR10CX Optional serial cable must be order
ページ3に含まれる内容の要旨
CONFIGURATION SETTINGS TEMPTRAC & XR10CX Dip switches A0 to A7 configure the serial address. The table below lists the settings up to 10. The full 257 address settings can be found in the ProtoCessor Getting Started (T17007) manual at www.protocessor.com A7 A6 A5 A4 A3 A2 A1 A0 Address Off Off Off Off Off Off Off Off 0 Off Off Off Off Off Off Off On 1 Off Off Off Off Off Off On Off 2 Off Off Off Off Off Off On
ページ4に含まれる内容の要旨
POWERING UP THE PROTOCESSOR/PROTONODE Power LED comes on and remains solid LA starts flashing about once per second. This tells us that PIC (Peripheral Interface Controller) number 1 in the ProtoCessor has powered up successfully. LB starts flashing about once per second. This tells us that PIC number 2 in the ProtoCessor has powered up successfully. GP105 will go on solid within 45 – 60 seconds after power up, signifying normal operation. ProtoCessor will be able to co
ページ5に含まれる内容の要旨
CONNECTION TO PROTOCESSOR USING UTILITIES Make sure that the FST Utilities is downloaded on the computer. (http://fieldserver.com/techsupport/utility/utility.php) Connect an Ethernet cross‐over cable between the PC and ProtoCessor or connect the ProtoCessor and the PC to the Hub/switch using a straight cat5 cable. The Default IP Address of the ProtoCessor is 192.168.1.24, Subnet Mask is 255.255.255.0. If the PC and the ProtoCessor are on different IP Networks, assign a Static
ページ6に含まれる内容の要旨
Double click on the debugging utility, “RUINET4” (Remote User Interface). The following screen will appear: See the “ProtoCessor Mapping” document to ensure that the device is set up correctly with respect to Baud rate, Node Address, and Points which are configured in the device. Select “O” for Connect Overview to see the number of messages on each protocol. If the ProtoCessor is communicating correctly with the device then the display will show Tx and Rx messages without an
ページ7に含まれる内容の要旨
TROUBLESHOOTING TIPS If PWR LED does not come on and LA and LB don’t flash, call or email ProtoCessor support support@ProtoCessor.com. If PWR LED does not come on but the LA and LB flash, then the PWR LED is broken. If LA and LB don’t start to flash there could be a problem with the ProtoCessor and you need to contact support@ProtoCessor.com. If GP105 never comes on then you need to contact ProtoCessor support. If TX and or RX don’t flash, it may represent a problem wi