ページ1に含まれる内容の要旨
®
American Metal Ware Hot Water Boiler
Installation, Operation & Service Manual
For
Models 815, 830, 850
Gas
TABLE OF CONTENTS
X
Electric Steam
General Description.................................1
Installation...............................................1
Thermostat..............................................4
Adjustment..................................4
Service Instructions.................................5
Dual Level Control...................................6
Special F
ページ2に含まれる内容の要旨
Electric Models 815, 830, 850 Equipped with Option 46 Automatic Refill Option 39 Low Water Cut-Off System General Description This unit is a high temperature hot water boiler. It consists of a non-pressure, vented water compartment into which is installed an electric immersion heater thermostatically controlled through a contactor relay, to keep the water always at the desired brewing temperature. Automatic refill maintains water level in water compartment. All control system components are encl
ページ3に含まれる内容の要旨
Installation (cont.) 5) TO CHECK REFILL RATE, allow water to fill to stop/full level automatically; then turn off master switch. Draw off 1 gallon of water from faucet. Turn master switch back on and time how long it takes for the water level to come up to stop/full mark again. Compare time with chart provided and adjust accordingly. TIME TO REFILL 1 GALLON HEATER SIZE COLD WATER* HOT WATER (OR EQUIV. STEAM USE) CONNECTION CONNECTION 5.5KW/208 Volt or 3min. 30sec. 1min. 25sec. 7KW/240 Volt 1min.
ページ4に含まれる内容の要旨
Page 3 American Metal Ware Hot Water Boiler
ページ5に含まれる内容の要旨
Thermostat Factory set so that knob on BREW setting holds unit at brewing temperature toward HIGH end of brew zone on thermometer dial. Then, if turned back to HOLD position, thermostat should cycle on and off and hold at LOW 'end of BREW zone on thermometer. Thermostat Adjustment 1. If water temperature is below HIGH end of BREW zone on thermometer dial with knob on BREW setting, remove knob by pulling straight outward. Using a small screwdriver, insert in hole in center of shaft, turn slotte
ページ6に含まれる内容の要旨
Service Instructions PROBLEM: THERMOSTAT DIAL TURNED TO BREW AND WATER IN COMPARTMENT REMAINS COLD POSSIBLE CAUSE 1. No power at urn. Check main switch, Check main fuses. (3 on 3 phase power, 2 on single phase power). Check that Pilot Light by On-Off switch is ON. Power at urn, but no power Check control circuit fuse. Check that pilot light over thermostat 2. at heater terminals. dial is lighted with dial set to BREW. Check that water level is at FULL mark on water gauge glass. NOTE: If urn i
ページ7に含まれる内容の要旨
Dual Level Control Auto Refill And Low Water Cutoff System I) Dual Level Control: What it does: A. AUTO REFILL of the water compartment to keep the tank filled with water. When water is used, the fill valve opens automatically to let in more. The fill valve closes when the water level reaches full. B. LOW WATER CUTOFF to prevent burn out of the electric immersion heater when there is not enough water to cover it. When low water occurs, the heat automatically switches off. The heat stays off
ページ8に含まれる内容の要旨
II) Description and Operation of Dual Level Control System (continued) B. Operation Water Level Action 1) Below both electrodes 1) Both “HI” and “XL” electrode circuits open. Dual Level Control turns power on to fill valve and keeps power off to thermostat. Fill Solenoid Thermostat Valve O OFF ON “XL” electrode circuit closes. Power to 2) Rises to low electrode 2) above heater coils thermostat turned on. Power to fill valve remains on. Fill Solenoid Thermostat Valve O ON ON 3) Rises to high el
ページ9に含まれる内容の要旨
American Metal Ware Hot Water Boiler Page 8 IV) Trouble Shooting Auto Refill, Low Water Cutoff, and Dual Level Control System PROBLEM POSSIBLE CAUSE SERVICE CHECK REMEDY A) Overfilling of water 1) Fill solenoid valve leaking Visual. Water entering Disassemble and clean out. May tank when power is due to dirt or scale holding tank continuously, and require new plunger assembly. Caution off. valve open, or worn usually slowly. is advised to avoid damage to valve. plunger seat. See valve instru
ページ10に含まれる内容の要旨
Page 9 American Metal Ware Hot Water Boiler IV) Trouble Shooting Auto Refill, Low Water Cutoff, and Dual Level Control System (continued) PROBLEM POSSIBLE CAUSE SERVICE CHECK REMEDY C) Auto refill fails to 3) Water strainer clogged. Water pressure before Remove and clean micromesh screen fill water tank strainer and not after. filter located in water strainer. (continued). 4) No power on Dual Check for 120V AC across If voltage missing or incorrect, Level Control. “H” and “N” terminals. check
ページ11に含まれる内容の要旨
American Metal Ware Hot Water Boiler Page 10 IV) Trouble Shooting Auto Refill, Low Water Cutoff, and Dual Level Control System (continued) PROBLEM POSSIBLE CAUSE SERVICE CHECK REMEDY 1) Thermostat off. Visual. Make sure knob is turned fully clockwise. E) Tank fills with water, but heat does not come 2) Thermostat inoperative Jumper across thermostat Recalibrate thermostat. If no remedy, or ther- on. or out of calibration. terminals causes heat to mostat does not cycle, replace. come on. 3) Pow
ページ12に含まれる内容の要旨
INSTALLATION AND SERVICE 53.20.10 INSTRUCTIONS FOR 202CB and 204CD Series May 1983 General Purpose Solenoid Valve Supd’s 3-80 Safety Instructions ATTENTION: Read carefully before attempting to install, operate or service your Alco solenoid valve. Retain for future reference. 1. Read installation instructions- thoroughly. Failure to comply can 6. CAUTION: Always disconnect power source and depressurize result in valve failure or system damage or personal injury. the system before working on sol
ページ13に含まれる内容の要旨
Diassembly Cleaning Disassemble in the same general order as indicated in exploded-view As with all valves, it may become necessary to clean them illustrations except as noted in the following steps: periodically to keep them in peak operating condition. Any cleaning 1. De-pressurize valve and disconnect electrical power source. methods or fluids used should be compatible with valve materials. 2. To remove solenoid coil: Insert small screwdriver into gap in voltage nameplate. Slide screwdriver t
ページ14に含まれる内容の要旨
Parts List 815, 830, 850 - Electric, Gas or Steam Heat AMW Part # Description 522004 Aluminum Gauge Shield Only for 815 - 5/8” x 13” 522006 Aluminum Gauge Shield Only for 830 - 5/8” x 16” 522010 Aluminum Gauge Shield Only for 850 - 5/8” x 20” 522034 Gauge Glass Only for 815 - 5/8” x 13” 522036 Gauge Glass Only for 830 - 5/8” x 16” 522129 Gauge Glass Only for 850 - 5/8” x 20” 522030 Aluminum Bracket for Gauge Shield 522026 Upper Gauge Glass Washer 522027 Lower Gauge Glass Washer A-682 Gauge Shiel
ページ15に含まれる内容の要旨
RED GREEN HEAT FILL H H American Metal Ware Hot Water Boiler Page 14 XL HI C
ページ16に含まれる内容の要旨
Grindmaster® Coffee Grinders and Brewers • Espressimo® Espresso Machines • Crathco® Hot Beverage Dispensers Crathco® Cold and Frozen Beverage Dispensers • American Metal Ware® Coffee and Tea Systems Tel (502) 425-4776 • Fax (502) 425-4664 • 1-800-695-4500 P.O. Box 35020 • Louisville, KY 40232 • USA www.grindmaster.com • email: info@grindmaster.com