ページ16に含まれる内容の要旨
condensate drain combustible material storage The water heaters covered in this manual are condensing appliances and require a building drain to be located in close proximity to allow the condensate to drain safely. Fire or Explosion Hazard Condensate drains from the water heater at the exhaust elbow located at the bottom. The field installed condensate drain line Do not store or use gasoline or other flammable vapors and must not be elevated above the condensate drain connection liquids in
ページ17に含まれる内容の要旨
unusually tight construction air reQuirements In unconfined spaces in buildings, infiltration may be adequate to provide air for combustion, ventilation and dilution of flue gases. However, in buildings of unusually tight construction (for example, weather stripping, heavily insulated, caulked, vapor barrier, etc.) additional air must be provided using the methods Breathing Hazard - Carbon Monoxide Gas described in the Confined Space section that follows. Install water heater in accordance
ページ1に含まれる内容の要旨
instruction manual
commercial gas water heaters
models (a)hcg3 130t 300/400
series 100 & 101
installation - operation - ser Vice
- maintenance - limited warranty
PO Box 1597, 500 Princeton Road
Johnson City, TN 37605
ASME CRN
ANSI/NSF-5 OPTIONAL
Low Lead Content
WARNING: If the information in these
instructions is not followed exactly, a fire
or explosion may result causing property
damage, personal injury or death.
Do not store or use gasoline or other
flammable vapors and li
ページ18に含まれる内容の要旨
Alternatively a single permanent opening, commencing within 12 fresh air openings for confined spaces inches (300 mm) of the top of the enclosure, shall be provided. The following instructions shall be used to calculate the size, See Figure 11. The water heater shall have clearances of at number and placement of openings providing fresh air for least 1 inch (25 mm) from the sides and back and 6 inches (l50 combustion, ventilation and dilution in confined spaces. The mm) from the front of
ページ19に含まれる内容の要旨
outdoor air through two Vertical ducts air from other indoor spaces The illustrations shown in this section of the manual are a reference for the openings that provide fresh air into confined spaces only. do not refer to these illustrations for the purpose of vent installation. See Venting Installation on page 21 for complete venting installation instructions. figure 14 The confined space shall be provided with two permanent openings, one commencing within 12 inches (300 mm) of the top and
ページ20に含まれる内容の要旨
installation reQuirements - commonwealth of massachusetts commonwealth of massachusetts inspection The state or local gas inspector of the side wall horizontally For all side wall terminated, horizontally vented power vent, direct vented gas fueled equipment shall not approve the installation vent, and power direct vent gas fueled water heaters installed in unless, upon inspection, the inspector observes carbon every dwelling, building or structure used in whole or in part for monoxide det
ページ2に含まれる内容の要旨
t able of contents SAFE INSTALLATION, uSE AND SERvICE .......................................... 3 Supply Gas Regulator Installation ................................................... 38 GENERAL SAFETy INFORmATION ...................................................... 4 Electrical Wiring ............................................................................... 39 Precautions ........................................................................................ 4 Power Supply Connections
ページ3に含まれる内容の要旨
safe installation, use and ser Vice The proper installation, use and servicing of this water heater is extremely important to your safety and the safety of others. Many safety-related messages and instructions have been provided in this manual and on your own water heater to warn you and others of a potential injury hazard. Read and obey all safety messages and instructions throughout this manual. It is very important that the meaning of each safety message is understood by you and others wh
ページ4に含まれる内容の要旨
general safety information precautions hydrogen gas flammable DO NOT uSE THIS APPLIANCE IF ANy PART HAS bEEN UNDER WATER. Immediately call a qualified service agency to inspect the appliance and to make a determination on what steps should be taken next. Explosion Hazard If the unit is exposed to the following, do not operate heater until all corrective steps have been made by a qualified Flammable hydrogen gases service agency. may be present. 1. External fire. Keep all ignition sources aw
ページ5に含まれる内容の要旨
general safety information Fire or Explosion Hazard Fire Hazard Do not store or use gasoline or other flammable vapors and For continued protection against liquids in the vicinity of this or any other appliance. risk of fire: Avoid all ignition sources if you smell gas. Do not install water heater on Do not expose water heater controls to excessive gas carpeted floor. pressure. Do not operate water heater if Use only the gas shown on the water heater rating label. flood damaged. Maintain require
ページ6に含まれる内容の要旨
introduction Thank You for purchasing this water heater. Properly installed diagrams as these are necessary for checking the operation and maintained, it should give you years of trouble free service. of the water heater. The principal components of the water heater are identified abbreViations used in Features And Components on page 7 in this manual. Abbreviations found in this Instruction Manual include : Use this reference to locate and identify various components on the water heater. • A
ページ7に含まれる内容の要旨
features and components blower/burner assembly detail basic operation The water heaters covered in this manual have a helical coil INTAKE AIR COMBUSTION shaped heat exchanger that is submerged in the storage tank. (combustion air) BLOWER The water heater’s Main Burner is a radial design burner, it CONNECTION is mounted on the top and fires downward through the heat 4 INCH PVC exchanger. This is a forced draft burner; hot burning gases are forced through the heat exchanger under pressure and
ページ8に含まれる内容の要旨
t op View 7 8 9 10 6 11 12 5 13 4 2 3 14 2 15 FRONT 16 1 17 18 figure 3 t op View components Blower is operating properly. The control system monitors this switch and will disable heating operation if its contacts 1. Water Heater’s 120 VAC on/off switch. are closed before the Combustion Blower is energized or 2. Powered anode rods. The water heater’s covered in this open any time during a heating cycle. See Sequence Of manual are equipped with two powered (non sacrificial) Operation on pag
ページ9に含まれる内容の要旨
6 5 11 12 17 15 14 18 13 side Views 1. Cleanout access panel, covers water heater cleanout operational buttons. Used to adjust various user settings and opening. view operational information. See Control System Operation on page 42. 2. CCB enclosure - see Figure 3 on page 8 for description. 11. Temperature-Pressure Relief Valve. See Temperature- 3. 120 VAC junction box. Incoming power supply and ground Pressure Relief Valve on page 15. connections are made here - see requirements for Powe
ページ10に含まれる内容の要旨
T & P VALVE INTAKE AIR 4 INCH PVC installation considerations rough in dimensions 4” PVC 35° 1 1/4” SUPPLY GAS INTAKE AIR CONNECTION CONNECTION 20° 70° 69” BACK FRONT (175.3 cm) T & P WATER OUTLET 69” HEIGHT 33.12” (84.1 cm) (175.3 cm) 63 INCHES OUTSIDE (160 cm) 75.50” DIAMETER (191.8 cm) TOP *1 1/2” NPT 50.77” WATER CLEANOUT (129 cm) OUTLET 3/4” NPT 4” PVC DRAIN VENT CONNECTION (exhaust elbow) 1 1/2” NPT FRONT WATER INLET CONDENSATE 4.86” DRAIN CONNECTION (12.34 cm) 1/2 INCH PVC 12” 18° 45° (30
ページ11に含まれる内容の要旨
locating the w ater heater Carefully choose a location for the new water heater. The placement is a very important consideration for the safety of the Fire or Explosion Hazard occupants in the building and for the most economical use of the appliance. Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance. CAUTION Avoid all ignition sources if you smell gas. Do not expose water heater controls to excessive gas Property Damage Hazard
ページ12に含まれる内容の要旨
Electrical Code, CSA C22.1. extended Vent terminations All-bronze circulators are recommended for used with commercial The water heaters covered by this manual can be installed using water heaters. 4 inch pipe for the intake air and/or vent piping up to a maximum of 70 equivalent feet (21.3 m). The intake air and/or vent piping Some circulating pumps are manufactured with sealed bearings and do not require further lubrication. Some circulating pumps can be extended up to 120 equivalent fee
ページ13に含まれる内容の要旨
installation reQuirements gas pressure reQuirements t able 4 *mANIFOLD PRESSuRE †mINImum SuPPL y PRESSuRE ‡mAxImum SuPPL y PRESSuRE mODEL NATuRAL GAS PROPANE GAS NATuRAL GAS PROPANE GAS NATuRAL GAS PROPANE GAS (A)HCG3 130T 300 4” W. C. (1.0 kPa) 10” W. C. (2.49 kPa) 5.2” W. C. (1.29 kPa) 11” W. C. (2.74 kPa) 10” W. C. (2.49 kPa) 12” W. C. (2.99 kPa) 4” W. C. (1.0 kPa) 10” W. C. (2.49 kPa) 5.2” W. C. (1.29 kPa) 11” W. C. (2.74 kPa) 10” W. C. (2.49 kPa) 12” W. C. (2.99 kPa) (A)HCG3 130T 400 * Mani
ページ14に含まれる内容の要旨
mixing Val Ves HOT WATER OUTLET Water temperature over 125°F (52°C) can cause severe burns instantly 12” TO 15” resulting in severe injury or death. (30-38 cm) Children, the elderly and the TEMPERED WATER physically or mentally disabled are at OUTLET highest risk for scald injury. Feel water before bathing or CHECK COLD showering. VALVE WATER Temperature limiting devices such as INLET MIXING mixing valves must be installed CHECK VALVE when required by codes and to VALVE ensure safe temperatures
ページ15に含まれる内容の要旨
water in adequate quantities should circumstances demand. If temperature-pressure relief Val Ve the discharge pipe is not connected to a drain or other suitable means, the water flow may cause property damage. Explosion Hazard CAUTION Water Damage Hazard Temperature-Pressure Relief Valve must comply with ANSI Z21.22- CSA 4.4 and ASME code. Temperature-Pressure Relief Valve discharge • pipe must terminate at adequate drain. Properly sized temperature- pressure relief valve must be installed in