GPH 13 H SERIES HORIZONTAL
Package Heat Pump Units
with R-410A
• Refer to Service Manual RS6300011 (Horizontal)
for installation, operation, and troubleshooting information.
• All safety information must be followed as provided in the Service Manual.
• Refer to the appropriate Parts Catalog for part number information.
• Models listed on page 3
This manual is to be used by qualified, professionally trained HV
ページ2に含まれる内容の要旨
PRODUCT IDENTIFICATION The model and manufacturing number are used for positive identification of component parts used in manufacturing. Please use these numbers when requesting service or parts information. GP H 13 24 H 41 A A VOLTAGE: BRAND: 1: 208-230v MINOR REVISION: ® 1ph/60Hz G: Goodman A: Initial Release PRODUCT Brand FAMILY: H: Heat Pump REFRIGERANT: 4: R-410A PRODUCT PRODUCT TYPE: MAJOR REVISION: SERIES: Package Unit A: Initial Release CONFIGURATION: SEER Rating H: Hori
ページ3に含まれる内容の要旨
PRODUCT IDENTIFICATION The model and manufacturing number are used for positive identification of component parts used in manufacturing. Please use these numbers when requesting service or parts information. GPH1324H41AB GPH1330H41AB GPH1336H41AC GPH1342H41AB GPH1348H41BB GPH1360H41BB The United States Environmental Protection Agency (“EPA”) has issued various regulations re- WA WARNI RNING NG garding the introduction and disposal of refrigerants introduced into this unit. Failure to follow th
ページ4に含まれる内容の要旨
PRODUCT DESIGN GPH Package Units are designed for outdoor installations Conditioned air is drawn through the filter(s), field installed, across the coil and back into the conditioned space by the only in either residential or light commercial applications. indoor blower. The connecting ductwork (Supply and Return) can only be connected for horizontal airflow. Package Heat Pump indoor sections are designed to accept optional components such as auxiliary electric heaters and A return air filter mu
ページ5に含まれる内容の要旨
UNIT PLENUM PLATFORM PRODUCT DESIGN 36" WARNING TO PREVENT POSSIBLE PROPERTY DAMAGE, THE UNIT SHOULD REMAIN IN AN UPRIGHT POSITION DURING ALL RIGGING AND MOVING OPERATIONS. TO FACILITATE LIFTING AND MOVING IF A CRANE IS USED, PLACE THE UNIT IN AN ADEQUATE CABLE 24" SLING. Refer to Roof curb Installation Instructions for proper curb installation. Curbing must be installed in compliance with the 36" National Roofing Contractors Association Manual. Rooftop Installation - Horizontal (H) NOTE: To ens
ページ6に含まれる内容の要旨
PRODUCT DESIGN GPH1324-1360H41** ELECTRICAL DATA (*Blower Only, Heat Mode) Circuit #1 Circuit #2 Maximum Maximum Actual Minimum Circuit Minimum Circuit Model and Heat Kit Usage kW & BTU Overcurrent Overcurrent Ampacity Ampacity Protection (amps) Protection (amps) at 240V at 208 / 240V at 208 / 240V at 208 / 240V at 208 / 240V GPH1324H41** HKR05*,C* 24 / 27 30 / 30 ---- ---- 4.75 / 16,200 HKR08*,C* 33 / 28 40 / 40 ---- ---- 7.00 / 23,800 HKR10*,C* 45 / 51 60 / 60 ---- ---- 9.50 / 32,400 GPH1330H4
ページ7に含まれる内容の要旨
PRODUCT DIMENSIONS GPH13[24-60]H41** A 14.000 4.512 4.500 14.000 6.500 14.000 SUPPLY RETURN BACK VIEW (DUCT OPENINGS) 66.542 B 34.075 Chassis Model A B GPH1324H41** 22.000 29.932 Small GPH1330H41** 22.000 29.932 GPH1336H41** 24.000 34.932 Medium GPH1342H41** 24.000 34.932 GPH1348H41** 24.000 38.682 Large GPH1360H41** 24.000 38.682 7
ページ8に含まれる内容の要旨
GPH13[24-36]H41AB PACKAGE HEAT PUMP SPECIFICATIONS GPH1336H41AC GPH1324H41** GPH1330H41** GPH1336H41** COOLING COOLING CAPACITY, BTUH 24,000 28,200 35,000 CAPACITY SEER 13.00 13.00 13.00 47°/43°F HEATING 22,000 27,000 33,600 RATING 35°/33°F 17,600 20,400 27,000 17°/15°F 14,000 15,000 18,000 HSPF 7.7 7.7 7.7 UNIT VOLTAGE (NAMEPLATE) 208/230-60-1 208/230-60-1 208/230-60-1 ELECTRICAL AMPS 15.4 17.06 20.06 SPECIFICATION MIN CIRCUIT AMPACITY 18.6 20.6 24.2 (2) MAX OVERCURRENT PROTECTION 30 30 40 CO
ページ9に含まれる内容の要旨
GPH1342H41AB PACKAGE HEAT PUMP SPECIFICATIONS GPH13[48-60]H41BB GPH1342H41** GPH1348H41** GPH1360H41** COOLING COOLING CAPACITY, BTUH 40,500 46,000 57,500 SEER 13.00 13.00 13.00 CAPACITY 47°/43°F HEATING 38,000 44,500 54,400 RATING 35°/33°F 30,000 33,000 39,000 17°/15°F 21,800 26,000 32,000 HSPF 7.8 7.7 7.7 UNIT VOLTAGE (NAMEPLATE) 208/230-60-1 208/230-60-1 208/230-60-1 ELECTRICAL AMPS 22.2 24.17 33.6 SPECIFICATION MIN CIRCUIT AMPACITY 26.6 29.2 40.2 (2) MAX OVERCURRENT PROTECTION 40 45 60 COM
ページ10に含まれる内容の要旨
ACCESSORIES Part Number Description OT18-60A Outdoor Thermostat Kit w/Lockout Stat OT/EHR18-60 Emergency Heat Relay Kit HKR Electric Heat Kit PCCP101-103 Roof Curb PCP101-103 Downflow Plenum Kit PCP101-103R8 Downflow Plenum Kit w/ R-8 Insulation GPCED101-103 Downflow Economizer for GPC-(H) A/C - To Be Used With PCP101-103 GPHED101-103 Downflow Economizer for GPH-(H) Heat Pump - To Be Used With PCP101-103 GPCEH101-103 Horizontal Economizer for GPC-(H) A/C GPHEH101-103 Horizontal Economizer for G
ページ11に含まれる内容の要旨
GPH13[24-60]H41** BLOWER PERFORMANCE DATA Dry Coil Data E.S.P (In. of H O) 2 Model Speed Volts 0.10.2 0.30.4 0.50.6 0.7 0.8 680 640 590 555 505 440 340 - CFM LOW 230 155 150 145 140 130 120 110 - WATTS 895 855 815 755 700 630 545 390 CFM MED 230 230 220 215 205 195 180 170 145 WATTS 1,185 1,130 1,070 1,010 930 850 760 650 CFM HIGH 230 350 340 325 310 295 280 265 245 WATTS 1,150 1,080 1,025 975 925 845 - - CFM LOW 230 340 330 315 305 295 280 - - WATTS 1,335 1,275 1,205 1,135 1,075 985 910 845 CFM
ページ12に含まれる内容の要旨
BLOWER PERFORMANCE DATA 12 BTU OUTPUT vs TEMPERATURE RISE CHART 100 600 CFM 90 700 80 800 900 1000 70 1100 1200 60 1400 1600 50 1800 2000 2200 40 2400 CFM 30 FORMULAS BTU OUTPUT = CFM x 1.08 x RISE BTU OUTPUT 20 RISE = ÷ CFM 1.08 10 100 30 40 50 60 70 80 90 110 120 130 140 150 OUTPUT BTU/HR x 1000 TEMPERATURE RISE
ページ13に含まれる内容の要旨
COOLING PERFORMANCE DATA GPH1324H41** 13 MODEL: GPH1324H41** COOLING OPERATION EXPANDED PERFORMANCE DATA Design Subcooling, 12±3 °F @ the liquid access fitting connection AHRI 95 test conditions. Design Superheat 8±3 °F @ the compressor suction access fitting connection. Outdoor Ambient Temperature 65 75 85 95 105 115 Entering Indoor Wet Bulb Temperature IDB* Airflow 59 63 677159 6367715963 6771 59 63 67 71 59 63 67 71 59 63 6771 MBh 23.5 24.4 26.7 - 23.0 23.8 26.1 - 22.4 23.2 25.5 - 21.9 22
ページ14に含まれる内容の要旨
COOLING PERFORMANCE DATA GPH1324H41** 14 MODEL: GPH1324H41** COOLING OPERATION EXPANDED PERFORMANCE DATA Design Subcooling, 12±3 °F @ the liquid access fitting connection AHRI 95 test conditions. Design Superheat 8±3 °F @ the compressor suction access fitting connection. Outdoor Ambient Temperature 65 75 85 95 105 115 Entering Indoor Wet Bulb Temperature IDB* Airflow 596367 71 59 63 67 71 59 63 67 7159 63 67 71596367 71596367 71 MBh 24.3 24.9 26.6 28.4 23.8 24.3 26.0 27.7 23.2 23.7 25.3 27.1
ページ15に含まれる内容の要旨
COOLING PERFORMANCE DATA GPH1330H41** 15 MODEL: GPH1330H41** COOLING OPERATION EXPANDED PERFORMANCE DATA Design Subcooling, 12±3 °F @ the liquid access fitting connection AHRI 95 test conditions. Design Superheat 8±3 °F @ the compressor suction access fitting connection. Outdoor Ambient Temperature 65 75 85 95 105 115 Entering Indoor Wet Bulb Temperature IDB* Airflow 5963677159 63 6771 5963 677159 63 67 71596367 71 59636771 MBh 27.6 28.6 31.4 - 27.0 28.0 30.7 - 26.3 27.3 29.9 - 25.7 26.6 29.
ページ16に含まれる内容の要旨
COOLING PERFORMANCE DATA GPH1330H41** 16 MODEL: GPH1330H41** COOLING OPERATION EXPANDED PERFORMANCE DATA Design Subcooling, 12±3 °F @ the liquid access fitting connection AHRI 95 test conditions. Design Superheat 8±3 °F @ the compressor suction access fitting connection. Outdoor Ambient Temperature 65 75 85 95 105 115 Entering Indoor Wet Bulb Temperature IDB* Airflow 5963677159 63 6771 5963 677159 63 67 71596367 71 59636771 MBh 28.629.231.233.4 27.9 28.530.532.6 27.327.9 29.831.826.6 27.2 29
ページ17に含まれる内容の要旨
COOLING PERFORMANCE DATA GPH1336H41** 17 MODEL: GPH1336H41** COOLING OPERATION EXPANDED PERFORMANCE DATA Design Subcooling, 12±3 °F @ the liquid access fitting connection AHRI 95 test conditions. Design Superheat 8±3 °F @ the compressor suction access fitting connection. Outdoor Ambient Temperature 65 75 85 95 105 115 Entering Indoor Wet Bulb Temperature IDB* Airflow 59 636771 59 636771 5963 67 7159 63 67 71 596367 71 596367 71 MBh 34.3 35.5 38.9 - 33.5 34.7 38.0 - 32.7 33.9 37.1 - 31.9 33.1
ページ18に含まれる内容の要旨
COOLING PERFORMANCE DATA GPH1336H41** 18 MODEL: GPH1336H41** COOLING OPERATION EXPANDED PERFORMANCE DATA Design Subcooling, 12±3 °F @ the liquid access fitting connection AHRI 95 test conditions. Design Superheat 8±3 °F @ the compressor suction access fitting connection. Outdoor Ambient Temperature 65 75 85 95 105 115 Entering Indoor Wet Bulb Temperature IDB* Airflow 5963677159 6367715963 677159 63 67 71596367 7159636771 MBh 35.536.338.841.4 34.7 35.437.940.533.834.6 37.039.533.0 33.7 36.1 3
ページ19に含まれる内容の要旨
COOLING PERFORMANCE DATA GPH1342H41** 19 MODEL: GPH1342H41** COOLING OPERATION EXPANDED PERFORMANCE DATA Design Subcooling, 12±3 °F @ the liquid access fitting connection ARI 95 test conditions. Design Superheat 8±3 °F @ the compressor suction access fitting connection. Outdoor Ambient Temperature 65 75 85 95 105 115 Entering Indoor Wet Bulb Temperature IDB* Airflow 59636771 59 6367715963 677159 63 67 7159636771 59 636771 MBh 39.7 41.1 45.1 - 38.8 40.2 44.0 - 37.8 39.2 43.0 - 36.9 38.3 41.9
ページ20に含まれる内容の要旨
COOLING PERFORMANCE DATA GPH1342H41** 20 MODEL: GPH1342H41** COOLING OPERATION EXPANDED PERFORMANCE DATA Design Subcooling, 12±3 °F @ the liquid access fitting connection AHRI 95 test conditions. Design Superheat 8±3 °F @ the compressor suction access fitting connection. Outdoor Ambient Temperature 65 75 85 95 105 115 Entering Indoor Wet Bulb Temperature IDB* Airflow 59 63677159 63 67 715963 6771 59 63 67 7159 63 677159 6367 71 MBh 41.1 42.0 44.8 47.9 40.1 41.0 43.8 46.8 39.2 40.0 42.8 45.7