Installation and Operation Manual
TR5000 Series Transient Voltage Surge Suppressors
Model Types: TR5451 and TR5452
IMPORTANT NOTICE
THE ENTIRE CONTENT OF THIS INSTRUCTION MUST BE READ AND
FULLY UNDERSTOOD BEFORE ATTEMPTING ANY INSTALLATION
OR ENERGIZATION OF THE TVSS.
If the minimum requirements of this manual are not followed, the TVSS could become irreversibly damaged,
and/or the electrical system could be left unprotected. Failure to compl
ページ2に含まれる内容の要旨
PRE-INSTALLATION REQUIREMENTS (CONT.): system. Refer to the “VOLTAGE RATINGS & POWER SOURCE CONFIGURATIONS” chart below. The TVSS model number can be found on the front of the unit. Verify that an NEC (National Electrical Code) compliant X0 bond has been made at the upstream transformer that feeds the electrical supply panel. Per NEC 250.30, this bond must be in place on all grounded electrical systems. The TR5451 or TR5452 model TVSS must be installed on a dedicated branch circui
ページ3に含まれる内容の要旨
INSTALLATION (CONT.): 3. The TVSS can be installed in any orientation, however Optional Alarm Terminal special consideration should be given to allow periodic 903-640-0555 visual inspection of the status indicator lamps. NO COM NC 800-950-2281 LISTED (48E6) UL 1449, 2ND EDITION CONNECTION FOR INDOOR USE ONLY NOTE: If lamp is out, replace unit DUAL PHASE TVSS 1. TR5451 and TR5452 Model TVSS units come equipped 120 VAC 50/60HZ SUPPRESSION VOLTAGES 330 L-N with 10 AWG connection wires
ページ4に含まれる内容の要旨
DIMENSIONS: 5.28 4.63 2.85 2.85 2.29 0.56 903-640-0555 903-640-0555 g 800-950-2281 800-950-2281 LISTED (48E6) LISTED (48E6) ND UL 1449, 2 EDITION ND UL 1449, 2 EDITION FOR INDOOR USE ONLY FOR INDOOR USE ONLY NOTE: If lamp is out, replace unit NOTE: If lamp is out, replace unit 4.54 DUAL PHASE TVSS DUAL PHASE TVSS 120 VAC 50/60HZ 120 VAC 50/60HZ SUPPRESSION VOLTAGES SUPPRESSION VOLTAGES 330 L-N 330 L-N 600 L-L NO COM NC 600 L-L TVSS TVSS PART# ACT452120210N PART# ACT