ページ1に含まれる内容の要旨
Model SMD-202
Smoke Dampers
Steel 3V Blades
Application
UL 555S Leakage Class II
Model SMD-202 is a leakage rated smoke damper with 3V style
blades. The SMD-202 has been qualified to 2,000 fpm (10.2 m/s) and
Model SMD-202 meets the requirements for smoke
4 in. wg (1 kPa) for operational closure in emergency smoke control
dampers established by:
situations. Model SMD-202 may be installed vertically (with blades
National Fire Protection Association
running horizontally) or horizontally and i
ページ2に含まれる内容の要旨
Pressure Drop Data SMD-202 This pressure drop testing was conducted in accordance with AMCA Standard 500-D using the three configurations shown. All 3 3 data has been corrected to represent standard air at a density of .075 lb/ft (1.201 kg/m ). Actual pressure drop found in any HVAC system is a combination of many factors. This pressure drop information along with an analysis of other system influences should be used to estimate actual pressure losses for a damper installed in a given HVAC sy
ページ3に含まれる内容の要旨
5D 6D Figure 5.3 AMCA 5.2 Pressure Drop SMD-202 5D 4 (W) (H) = D 3.14 Figure 5.2 Figure 5. 5 12 in. x 12 in. (305mm x 305mm) 24 in. x 24 in. (610mm x 610mm) 36 in. x 36 in. (914mm x 914mm) 12 in. x 48 in. (305mm x 1219mm) 48 in. x 12 in. (1219mm x 305mm) Pressure Drop Pressure Drop Pressure Drop Pressure Drop Pressure Drop Velocity (fpm) Velocity (fpm) Velocity (fpm) Velocity (fpm) Velocity (fpm) (in. wg) (in. wg) (in. wg) (in. wg) (in. wg) 500 0.04 500 0.02 500 0.01 500 0.01 500 0.0
ページ4に含まれる内容の要旨
AMCA 5.3 Pressure Drop SMD-202 5D 6D Figure 5.3 5D 4 (W) (H) = D 3.14 Figure 5.2 Figure 5. 5 12 in. x 12 in. (305mm x 305mm) 24 in. x 24 in. (610mm x 610mm) 36 in. x 36 in. (914mm x 914mm) 12 in. x 48 in. (305mm x 1219mm) 48 in. x 12 in. (1219mm x 305mm) Pressure Drop Pressure Drop Pressure Drop Pressure Drop Pressure Drop Velocity (fpm) Velocity (fpm) Velocity (fpm) Velocity (fpm) (in. wg) (in. wg) (in. wg) (in. wg) Velocity (fpm) (in. wg) 500 0.02 500 0.01 500 0.01 500 0.01 500 0.
ページ5に含まれる内容の要旨
5D 6D 5D 4 (W) (H) D 3.14 AMCA 5.5 Pressure Drop SMD-202 12 in. x 12 in. (305mm x 305mm) 24 in. x 24 in. (610mm x 610mm) 36 in. x 36 in. (914mm x 914mm) 12 in. x 48 in. (305mm x 1219mm) 48 in. x 12 in. (1219mm x 305mm) Pressure Drop Pressure Drop Pressure Drop Pressure Drop Pressure Drop Velocity (fpm) Velocity (fpm) Velocity (fpm) Velocity (fpm) Velocity (fpm) (in. wg) (in. wg) (in. wg) (in. wg) (in. wg) 500 0.04 500 0.06 500 0.03 500 0.03 500 0.03 1000 0.17 1000 0.22 1000 0.14 10
ページ6に含まれる内容の要旨
Application Data Damper Sleeve Dimensional Data The drawings below and corresponding table show the position of the SMD-202 damper when mounted in a factory sleeve. The standard mounting locations provide enough space for the mounting of actuators, controls and allow space for installa- tion of retaining angles and duct connections. The standard location of a damper mounted in a factory sleeve ("A" dimension) is shown below. The damper can be posi- 1 1 / 2 in. tioned at other locations wit
ページ7に含まれる内容の要旨
Damper Sizing Information Dampers larger than maximum single section size are supplied as a factory assembly of two or more sections of equal size. The following figures show maximum damper section size and assembly configurations for multi-section dampers. Double Section Single Section 50 in. 50 in. (1270mm) (1270mm) 50 in. (1270mm) 96 in. (2435mm) 32 in. (813mm) 32 in. (813mm) 64 in. (1626mm) 32 in. (813mm) When a fire/smoke damper is being used in conjunction with round or oval duc