ページ1に含まれる内容の要旨
PPX:505–6860 RS-485/RF I/O Channel Converter
Installation Instructions
About this Product Related Manuals
These instructions describe the installation of a The following manuals contain information
PPX:505–6860 RS-485/RF I/O Channel related to the installation of the PPX:505–6860
Converter in the SIMATIC 505 programmable converter and cables:
controller system.
• SIMATIC 505 Redundant I/O System
The PPX:505–6860 converter allows the use of Manual (PPX:505–8125–x).
coaxial cables in a 505 syste
ページ2に含まれる内容の要旨
Compatibility Issues Before installing the PPX:505–6860 converter, Compatibility with Power Supplies ensure that your system hardware is The PPX:505–6860 RS-485/RF converter can be compatible with the PPX:505–6860, as defined powered by the following supplies: below: • PPX:505–6660 115/230 VAC Compatibility with Bases • PPX:505–6660A 115/230 VAC The PPX:505–6860 RS-485/RF converter can be (dual media compatible) installed in the following type of bases: • PPX:505–6663 24 VDC • PPX:505–6504 4-slo
ページ3に含まれる内容の要旨
Installation Procedure Installing the PPX:505–6860 4. Connect the RF (coaxial) cable to the PPX:505–6860 port that is labeled: Use the following procedure to install the RF TO I/O BASES. See Figure 1. PPX:505–6860: 1. Remove the power from the base in which you are installing the PPX:505–6860. NOTE: All the remote bases connected to a 2. In the case of a 545/555 installation, install 545/555/575 CPU must have RF RBCs. RS-485 the PPX:505–6860 in the same base as the bases cannot be connected bet
ページ4に含まれる内容の要旨
Upgrading an RF-Based TI560/TI565/TI560T/TI565P to a TI545/TI555/TI575 To upgrade an existing RF-based 560, 560T, 3. Re-number your bases between 1 and 15 so 565, 565P system, replace the existing that no two bases have the same number. programmable controller, including its chassis, Base number 0 is the local base where the its power supply, and all its installed boards CPU resides and may be used for with the 505 base, the 505 power supply, additional 505 modules, if desired. 545/555 CPU, and
ページ5に含まれる内容の要旨
R R C C P/S 560 565 C C 12 3 Upgrade Path 5 0 545 5 Series 505 I/O P/S or – 4, 8, or 16 slots 555 6 Local I/O 8 6 0 Coax Series 500/505 bases with RF RBCs. NOTE: No remote bases can be connected on the RS-485 link between the 545/555 and the PPX:505–6860. Figure 2 Upgrading an RF-Based 560/565/560T/565P System to a 545/555 5 2586546–0009 02/95 Copyright 1995 by Siemens Industrial Automation, Inc. All Rights Reserved — Printed in USA
ページ6に含まれる内容の要旨
R R C C P/S 560 565 C C 12 3 4 Upgrade Path VMEbus 575 P/S 575 VME Base B A Local I/O #8 copper ground strap Bases must be within three feet of each other and connected by a #8 copper 5 5 ground strap. 0 0 5 5 P/S – – 6 6 Series 505 Base 8 8 6 6 0 0 Remote Series 500/505 Bases with RF RBCs NOTE: No remote bases can be connected on the RS-485 link between the 575 and the PPX:505–6860. Figure 3 Upgrading an RF-Based 560/565/560T/565P System to a 575 6