ページ1に含まれる内容の要旨
Rev. 0505
VGM, VGD
Vertical Glass Service Deli, Meat, Fish Case
P/N VGM,VGD-0505
1
INSTALLATION & OPERATION GUIDE
/Chino
Installation
& Operation
VGM, VGD
Manual
Vertical Glass Service Deli, Meat, Fish Case
REV. 0505
ページ2に含まれる内容の要旨
VGM, VGD-0505 General Instructions Contents THIS BOOKLET CONTAINS INFORMATION ON: VGM – Straight Glass Refrigerated Super High General Instructions ................................................. 2 Important Information............................................. 3 Volume Meat or Deli Case Cut & Plan Views....................................................... 3 Installation ................................................................. 4 SHIPPING DAMAGE LOCATION ..........................
ページ3に含まれる内容の要旨
1 29 /4" 1 35 /2" Rev. 0505 Important Information The VGM / VGD service cases are easy to work, attrac- tion solenoid at each case. Do not use EPR valves, liq- tive merchandising display cases capable of maintaining uid line solenoids or electronic control devices of any superb product quality, with the installation of the kind. These controls allow temperature swings proper controlling devices. These should be set according causing product dehydration and excessive to Hussmann’s specifications
ページ4に含まれる内容の要旨
VGM, VGD-0505 Installation LOCATION These steps should release any settled lubricant within The refrigerated merchandisers have been designed for the cylinders, and prevent any stress on the front glass. use only in air conditioned stores where temperature and humidity are maintained at or below 75°F and 55% SETTING AND JOINING relative humidity. DO NOT allow air conditioning, The sectional construction of these models enable them electric fans, ovens, open doors or windows (etc.) to to be joine
ページ5に含まれる内容の要旨
Rev. 0505 6. Slide second case up to first case snugly. Then level second case to the first case so glass front, bumper and top are flush. 7. To compress silicone at joint, use two Jurgenson wood clamps. Make sure case is level from front to back and side to side on inside bulkheads at joint. 8. Attach sections together via a 3 bolts located in the base of the case. Secure the overhead structure by bolting the rear mullions tegether. Do not use bolts to pull cases together! 9. Apply bead of s
ページ6に含まれる内容の要旨
VGM, VGD-0505 Plumbing 1. Never use pipe for condensate drains smaller than It is the contractor's the nominal diameter of the pipe or P-trap supplied responsibility to install with the case. case(s) according to local 2. When connecting condensate drains, the P-trap must construction and health be used as part of the condensate drain to prevent codes. air leakage or insect entrance. Store plumbing system floor drains should be at least 14" off the center of the case to allow use of the P-trap p
ページ7に含まれる内容の要旨
Rev. 0505 Humidification connecting “L”, remove it from the case, and HUMIDIFICATION SYSTEM (WHERE APPLICABLE) flushing with a hose. One contributor to spoilage of fresh meat and deli IMPORTANT INFORMATION products that are displayed in refrigerated service type The VGM / VGD case line is easy to work, and capable of merchandisers is dehydration, which causes the product maintaining superb product quality with the installation to shrink and dry out. The humidification system is of the proper con
ページ8に含まれる内容の要旨
VGM, VGD-0505 Refrigeration THERMOSTATIC EXPANSION VALVE LOCATION REFRIGERANT TYPE This device is located on the same side as the refrigera- The standard refrigerant will be R-22 unless otherwise tion stub. An ALCO expansion valve model is furnished specified on the customer order. Check the serial plate as standard equipment, unless otherwise specified by on the case for information. customer. REFRIGERATION LINES EXPANSION VALVE ADJUSTMENT LIQUID SUCTION There is one (1) valve on the right si
ページ9に含まれる内容の要旨
Rev. 0505 User Information STOCKING Improper temperature and lighting will cause serious 10. Cold coils remove heat and moisture from the case product loss. Discoloration, dehydration and spoilage can and deposit this as frost onto the coil. Thus, a defrost be controlled with proper use of the equipment and is required. Our humidity system induces moisture handling of product. Product temperature should always into the case and helps slow down the dehydration be maintained at a constant and pro
ページ10に含まれる内容の要旨
VGM, VGD-0505 PLEXIGLASS & ACRYLIC CARE hot water. Improper cleaning not only accelerates the cleaning cycle 2. Rinse with hot water, but do not flood. but also degrades the quality of this surface. Normal daily 3. Apply the sanitizing solution according to buffing motions can generated static cling attracting dust Hussmann’s directions. to the surface. Incorrect cleaning agents or cleaning 4. Rinse thoroughly. cloths can cause micro scratching of the surface, causing 5. Dry completely before re
ページ11に含まれる内容の要旨
Rev. 0505 Maintenance ELECTRICAL PRECAUTIONS FOR PROMPT SERVICE BEFORE When Contacting the Factory SERVICING regarding problems, Be sure Always Disconnect Electrical to have the Case MODEL and Power at the Main Disconnect SERIAL NUMBER Handy. when servicing or replacing This Information is on a plate any electrical component. located on the case itself. This includes (but not limited to) Fans, Heaters, Thermostats, and Lights. SHELF GLASS ADJUSTMENT Unload product from shelves. Remove the glass
ページ12に含まれる内容の要旨
VGM, VGD-0505 Maintenance (cont.) 2. Increase the height to 12", and raise and lower the glass 6 more times. 3. Finally, raise the glass to it's full extension. This should release any settled lubricant in the cylinders, and prevent any stress on the front glass. (1)(3) GLASS REPLACEMENT & RIGHT – LEFT ADJUSTMENT 1. Open glass 2. Back out panel. all the set screws Relieve the along the top tension on edge of the glass the hinge. panel (3mm set screw) PVC U-chan
ページ13に含まれる内容の要旨
Rev. 0505 Maintenance cont’d Glass Sweep Installation (WHERE APPLICABLE) BEFORE PARTS LIST • Silicone 1200 (or comparable) SERVICING • Masking tap (not supplied) Always Disconnect Electrical INSTRUCTIONS Power at the Main Disconnect 1. Cut a strip of the glass sweep material to the proper when servicing or replacing length. any electrical component. 2. Open glass wide enough to apply a few small drips of This includes (but not limited to) Fans, #1200 silicone down the edge of one side of the gla
ページ14に含まれる内容の要旨
VGM, VGD-0505 Case Specifications TEMPERATURE DISCHG. TYPE DEFROST 115 V. ELECTRICAL CIRCUITS HUMIDITY MODEL BTU AVG AIR T-STAT/ FAN SIZE FREQ. AIR AIR HUNIDITY LENGTH REQ’D EVAP PROD DISC VELOC CUT IN NUMBER FAN & E E FANS RECEP- SWEEP SWEEP SYSTEM APP. FT. TMP TMP TMP @FPM SETTINGS EVAP. COIL OF MOTORS QTY DURATION (STANDARD) LIGHTS TACLE FANS HEATER FANS VGD Deli (Blower Coil) 1 4' Deli 750 20° 34° 25° 250 26° Forced Evap 4 /2" Axial 3 36 min. 54 1.83 15.0 36 1.04 [.16] 1 Air Air Sweep 4
ページ15に含まれる内容の要旨
Rev. 0505 Electrical Schematics 15 TOP FRONT LIGHTS OPTIONAL LIGHTS CIRCUIT #1 DUPEX (SHELF LIGHT, NOSE LIGHT, LEDGE LIGHT) OUTLET LOADING 115 V W G BK L1 2.5 #.# L2 #.# #.# L3 #.# #.# SINGLE NOTE: CASE MUST OUTLET BE GROUNDED W G BK HUMIDIFIER FANS (2). COMAIR™ 125-01-2011 HUMIDIFIER M M FANS (1). COMAIR™ 125-01-2011 AIR SWEEP M M M FANS (3). COMAIR™ 00001212 LIGHT SWITCH TIPPETTE 125-01-0311 M M M M M M L AXIAL EVAP FANS (6). COMAIR™ L MX2B1-E1 125-01-1023 HARNESS PER BALLA
ページ16に含まれる内容の要旨
VGM, VGD-0505 Electrical Schematics (Continued) 16 TOP FRONT LIGHTS OPTIONAL LIGHTS CIRCUIT #1 DUPEX LOADING OUTLET (SHELF LIGHT, NOSE LIGHT, LEDGE LIGHT) 115 V L1 2.3 #.# W G BK L2 #.# #.# L3 #.# #.# NOTE: CASE MUST SINGLE OUTLET BE GROUNDED W G BK HUMIDIFIER M FANS (1). COMAIR™ 125-01-2011 M M M AIR SWEEP FANS (3). COMAIR™ 00001212 LIGHT SWITCH TIPPETTE 125-01-0311 M M M M L AXIAL EVAP FANS (4). COMAIR™ L MX2B1-E1 125-01-2012 125-01-1023 HARNESS PER BALLAST CIRCUIT #1 125-0
ページ17に含まれる内容の要旨
Rev. 0505 Electrical Schematics (Continued) 17 TOP FRONT LIGHTS OPTIONAL LIGHTS CIRCUIT #1 DUPEX LOADING (SHELF LIGHT, NOSE LIGHT, LEDGE LIGHT) OUTLET 115 V L1 1.7 #.# W G BK L2 #.# #.# L3 #.# #.# NOTE: CASE MUST SINGLE OUTLET BE GROUNDED W G BK M HUMIDIFIER FANS (1). COMAIR™ 125-01-2011 M M AIR SWEEP FANS (2). COMAIR™ 00001212 LIGHT SWITCH TIPPETTE 125-01-0311 M M M M L AXIAL EVAP FANS (4). COMAIR™ L MX2B1-E1 125-01-2012 125-01-1023 HARNESS PER BALLAST CIRCUIT #1 125-01-1024
ページ18に含まれる内容の要旨
VGM, VGD-0505 Electrical Schematics (Continued) 18 TOP FRONT LIGHTS OPTIONAL LIGHTS CIRCUIT #1 (SHELF LIGHT, NOSE LIGHT, LEDGE LIGHT) LOADING DUPEX 115 V OUTLET L1 1.9 #.# L2 #.# #.# W G BK L3 #.# #.# NOTE: CASE MUST BE GROUNDED SINGLE OUTLET W G BK AIR SWEEP FANS (3). COMAIR™ 00001212 M M M LIGHT SWITCH TIPPETTE 125-01-0311 L L CIRCUIT #1 L1 L2 SWITCH 125-01-0311 L3 N G TERMINAL ~115 VAC - 1Ø - 50/60 Hz. BLOCK 125-01-0295 REVISIONS: DRAWN BY: D. QUAN PROJECT TITLE: DWG #: W0
ページ19に含まれる内容の要旨
Rev. 0505 Electrical Schematics (Continued) 19 (SHELF LIGHT, NOSE LIGHT, LEDGE LIGHT) TOP FRONT LIGHTS OPTIONAL LIGHTS CIRCUIT #1 LOADING DUPEX OUTLET 115 V L1 1.9 #.# W G BK L2 #.# #.# L3 #.# #.# NOTE: CASE MUST BE GROUNDED SINGLE OUTLET W G BK AIR SWEEP FANS (3). COMAIR™ 00001212 M M M LIGHT SWITCH TIPPETTE 125-01-0311 L L CIRCUIT #1 L1 SWITCH L2 L3 125-01-0311 N TERMINAL G ~115 VAC - 1Ø - 50/60 Hz. BLOCK 125-01-0295 D. QUAN REVISIONS: DRAWN BY: PROJECT TITLE: DWG #: W02200
ページ20に含まれる内容の要旨
VGM, VGD-0505 20 (SHELF LIGHT, NOSE LIGHT, LEDGE LIGHT) TOP FRONT LIGHTS OPTIONAL LIGHTS CIRCUIT #1 LOADING 115 V L1 1.5 #.# L2 #.# #.# L3 #.# #.# DUPEX OUTLET NOTE: CASE MUST BE GROUNDED W G BK SINGLE OUTLET W G BK AIR SWEEP FANS (3). COMAIR™ 00001212 M M LIGHT SWITCH TIPPETTE 125-01-0311 L L CIRCUIT #1 L1 L2 SWITCH 125-01-0311 L3 N G TERMINAL ~115 VAC - 1Ø - 50/60 Hz. BLOCK 125-01-0295 REVISIONS: DRAWN BY: D. QUAN PROJECT TITLE: DWG #: W0220037 ASCMS-M/F-VGM-6 - MEAT/FISH #