ページ1に含まれる内容の要旨
Tripp Lite
1111 West 35th Street
Chicago, IL 60609 USA
Telephone: +(773) 869 1234
E-mail: saleshelp@tripplite.com
Model Number: SU20KRTHW
SmartOnline 20kVA On-Line Double-Conversion UPS, N+1, 12U Rack/Tower, 200-240V Hardwire output
Highlights
20kVA / 20,000VA / 18,000W on-line double-conversion UPS; 0.9 power factor
200/208/220/230/240V 50/60Hz output; Economy mode option
Hot-swap power and battery modules, N+1 fault tolerance at loads up to 10kVA
USB, RS232 & EPO ports; support for SNMP/WE
ページ2に含まれる内容の要旨
SNMP-enabled UPS, PDU and other networking devices Optional 2POSTRMKITHD supports installation in 2 post 19 inch racks (4 required) Optional 2-9USTAND supports upright tower placement (2 required) Supports Emergency Power Off (EPO) via built-in interface Front panel LEDs and LCD readout with scroll controls LED / LCD display panel rotates for viewing in rackmount or tower configurations External battery packs are field replaceable and hot swappable Frequency conversion mode enables conversion of
ページ3に含まれる内容の要旨
UPS input Hardwire connection type UPS input 3 wire single phase input (L1, L2, G) connection description Recommended 120A @ 200V-240V (L, N, PE), or 125A @ 200V, 208V, or 240V (L1, L2, G) Electrical Service Phase Single-Phase BATTERY Full load runtime 4.3 minutes (18,000 watts) (minutes) Half load runtime 12.5 minutes (9000 watts) (minutes) Expandable battery Runtime is expandable with external battery packs runtime External battery BP240V10RT3U; BP240V557C-1PH; BP240V787C-1PH; BP240V1037C-1PH;
ページ4に含まれる内容の要旨
EMI / RFI AC noise Yes suppression PHYSICAL Included mounting 4 sets of adjustable 4 post rack rails included (one for each included 3U module) accessory description Installation form 2 post rackmount (2POSTRMKITHD); Tower (2-9USTAND) factors supported with optional accessories Optional mounting Qty 4 2POSTRMKITHD required; Qty 2 2-9USTAND required accessory notes Primary form factor Rackmount UPS / Power Module 5.14 x 17.5 x 25.82 dimensions in primary form factor (height x width x depth / inch
ページ5に含まれる内容の要旨
UPS Shipping 91.4 x 102.2 x 129.5 dimensions (height x width x depth / cm) Shipping weight (lbs) 600 Shipping weight (kg) 272.4 Cooling method Fans UPS housing Steel material ENVIRONMENTAL Operating +32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius Temperature Range Storage +5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius Temperature Range Relative Humidity 0 to 95%, non-condensing AC mode BTU / hr. 6830 (full load) AC economy mode 2550 BTU / hr. (full load) AC mode efficiency
ページ6に含まれる内容の要旨
High voltage transfer 300V to battery power (setpoint) SPECIAL FEATURES Cold Start (startup in Cold-start operation supported battery mode during a power failure) Economy mode Optional economy mode enables high efficiency bypass operation with a maximum output voltage variation of operation +/-10%. Double conversion mode is automatically restored as mains voltage varies beyond +/-10% with less than 1 millisecond transfer time between modes High availability UPS Automatic inverter bypass; Manual
ページ7に含まれる内容の要旨
More information, including related products, owner's manuals, and additional technical specifications, can be found online at http://www.tripplite.com/sku/SU20KRTHW. Copyright © 2014 Tripp Lite. All rights reserved. All trademarks are the sole property of their respective owners. Tripp Lite has a policy of continuous improvement. Specifications are subject to change without notice. Photos may differ slightly from final products.