Model #: SU3000RTXLCD3U
SmartOnline 3kVA On-Line Double-Conversion UPS, 3U Rackmount, Interactive LCD display,
100/110/120/127V NEMA outlets
Highlights
3000VA / 3kVA / 2700W on-line double-conversion 3U rackmount UPS
100/110/120/127V 50/60Hz output; High efficiency economy mode option
Interactive LCD with 9 selectable screens of UPS and site power data
Expandable runtime, Hot-sw
ページ2に含まれる内容の要旨
4 post installation hardware included, Optional 2POSTRMKITHD enables 2 post rack installation Single line TEL / Network surge suppression Electronic bypass maintains utility output during a variety of UPS fault conditions Battery independent restart ensures automatic UPS power-up without user interaction after lengthy power outages, even when batteries are expired and require replacement Frequency regulation / conversion mode offers generator-compatible frequency correction or conversion of freq
ページ3に含まれる内容の要旨
Built-in Two switchable four-outlet load banks controllable switched load banks Output AC Pure Sine wave waveform (AC mode) Output AC Pure Sine wave waveform (battery mode) INPUT Rated input 24A current (at maximum load) Nominal Input 100V AC; 110V AC; 115V AC; 120V AC; 127V AC Voltage(s) Supported Nominal input 120V factory default voltage description UPS input L5-30P connection type Input circuit 40A breaker UPS Input cord 10 length (ft.) UPS Input cord 3 length (m) Recommended 30A 120V Electr
ページ4に含まれる内容の要旨
Battery Hot-swappable, user replaceable batteries replacement description VOLTAGE REGULATION Voltage regulation Online, double-conversion power conditioning maintains 2% output voltage regulation during brownouts and description overvoltages Overvoltage Corrects overvoltages to 150V (0-100% load) correction Undervoltage Corrects undervoltages to 100V at full load (90V at 100V nominal) correction Severe Corrects brownouts to 70V (70% load) & 55V (33% load) undervoltage correction LEDS ALARMS & SW
ページ5に含まれる内容の要旨
UPS / Power 13.2 x 44.4 x 66 Module dimensions in primary form factor (height x width x depth / cm) Installed whole 3U system total rack space height (rack spaces) UPS / Power 74 Module weight (lbs) UPS / Power 33.6 Module weight (kg) UPS Shipping 12 x 23 x 33 dimensions (height x width x depth / inches) UPS Shipping 30.5 x 58.4 x 83.8 dimensions (height x width x depth / cm) Shipping weight 120 (lbs) Shipping weight 54.4 (kg) UPS housing Steel material Cooling method Fan ENVIRONMENTAL Operating
ページ6に含まれる内容の要旨
Network Supports detailed monitoring of UPS and site power conditions; DB9 port supports RS232 and contact closure monitoring port communications description PowerAlert Included software Communications USB and DB9 cabling included cable WatchDog Supports Watchdog application, OS and hard-reboot restart options for remote applications compatibility LINE / BATTERY TRANSFER Transfer time Zero (0 milliseconds) in double-conversion mode; 4 milliseconds economy mode Low voltage 55V at 33% load, 70V at
ページ7に含まれる内容の要旨
WEXT5-2200-3000 5-Year Extended Warranty - For Smart Line-Interactive and Online Tower or Rack 1 models, 2200-3000VA or less MODBUSCARD For remote monitoring and control via MODBUS protocol 1 RELAYIOCARD Programmable Relay I/O Card 1 AS400CABLEKIT2 Power Management Tools - UPS Communication Cable Kit for System i / AS400 / 1 iSeries Servers 2POSTRMKITHD Enables 2-Post Rackmount Installation of 3U and Larger UPS, Transformer and Battery 1 Pack Components PDUB30 Single-Phase Hot-Swap PDU, 30A 1