ページ1に含まれる内容の要旨
Owner's Manual
®
SmartPro
1111 W. 35th Street
Datacenter INT
Chicago, IL 60609 USA
Customer Support: (773) 869-1234
www.tripplite.com
Intelligent, Line-Interactive
UPS Systems (230V Output)
Safety: p. 2
Quick Installation: p. 3 - 4
Basic Operation: p. 5 - 7
Storage & Service: p. 8
Specifications: p. 8
®
Copyright ©2000 Tripp Lite. All rights reserved. SmartPro is a registered trademark of Tripp Lite.
1
9905251 230V SmartPro Datacenter OM.p65 1 8/8/00, 2:02 PM
ページ2に含まれる内容の要旨
Safety This manual contains important instructions and warnings that should be followed during the installation, operation and storage of all Tripp Lite UPS Systems. UPS Location Warnings Install your UPS indoors, away from excess moisture or heat, dust or direct sunlight. For best performance, keep the indoor temperature between 0° C and 40° C (between 32° F and 104° F). Leave adequate space around all sides of the UPS for proper ventilation. UPS Connection Warnings If your UPS has a co
ページ3に含まれる内容の要旨
Quick Installation Position your External Battery 1 Pack(s). If positioning multiple Battery Packs, place them side by side or stack them no more than three high. Position your Power Module. 2 The Module may be stacked on top of your Battery Packs or placed beside them. Plug your External Battery Pack 3 into your Power Module's BRANCH CIRCUIT #1 230VAC 10AMPS External Battery Connector on its back panel. 00VA 4500W M 50/60HZ 5000VA 3700W 50HZ 5000VA 3700W CAUTION: DO NOT UNPLUG WHILE OPERATI
ページ4に含まれる内容の要旨
Computer Communications (Optional)* DB9 Port Connection 1 –Optional–* Using the grey or tan Tripp Lite cable CAUTION: DO NOT UNPLUG WHILE OPERATING OR ARCING WILL OCCUR that came with your UPS, connect your 36VDC 175 AMPS MAX primary server’s DB9 port to the single DB9 port labeled “LAN 4.1” or "Smart LAN Primary" (which provides complete intelligent RS-232 communications).** If you have additional 2 computers: IN: 230VAC 50/60HZ 5000VA 4500W OUT-LINE: 230VAC NOM 50/60HZ 5000VA 3700W CA OUT-BAT:
ページ5に含まれる内容の要旨
O Basic Operation Switches System Switch (Middle Back Panel) This switch activates the UPS's battery charger and intelligent microprocessor. ALWAYS leave it in the “ENABLE” (RIGHT) position when your UPS is plugged in. Only set the switch to “DISABLE” (LEFT) to reduce battery drain when you unplug your UPS for storage or shipping. Note: When this switch is on "ENABLE", the “ ” light will flash until you engage the ON/ Standby Switch to turn power ON at the UPS receptacles. ON/Standby Switch (Fro
ページ6に含まれる内容の要旨
Basic Operation (Continued) Indicator Lights Light descriptions apply when the UPS is plugged into a wall outlet and turned ON. This green light will shine constantly to indicate AC power is available at the receptacles. It will flash to indicate AC power is not available. (See “System Enable Switch” and “On/Standby Switch” descriptions above.) This multi-colored light displays 7 separate UPS battery charge conditions. It will turn from red (low) to yellow (medium) to green (full) to show you th
ページ7に含まれる内容の要旨
Other UPS Features AC Receptacles (Rear Panel) These 230V IEC-320 receptacles provide your connected equipment with AC line power during normal operation and battery power during blackouts and brownouts. They also protect your equipment against damaging surges and line noise. You can remotely reboot connected equipment by turning receptacles OFF and ON using Tripp Lite PowerAlert software. Circuit Breakers (Rear Panel) These breakers will trip to prevent damage to your UPS due to overload. Two s
ページ8に含まれる内容の要旨
Storage & Service Storage Turn your UPS OFF: first engage the ON/Standby Switch and release it to place your UPS in the “Standby” mode, then move the System Enable Switch to the “DISABLE” (DOWN) position to prevent battery drain, then disconnect the UPS power cord from the wall outlet. If you plan on storing your UPS for an extended period of time, recharge the UPS batteries once every three months. Follow steps #3 and #4 in the Quick Installation section and allow the UPS to charge until the “