POWER AVAILABILITY
™ ™
GXT2-6000RT230 & GXT2-4500RT230
USER MANUAL
230VAC
ページ2に含まれる内容の要旨
ページ3に含まれる内容の要旨
TABLE OF CONTENTS IMPORTANT SAFETY INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 GLOSSARY OF SYMBOLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 1.0 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 2.0 SYSTEM DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ページ4に含まれる内容の要旨
8.6 Bypass Indicator LED (Amber) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 8.7 UPS ON Indicator LED (Green) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 8.8 Battery Indicator LED (Amber). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 8.9 AC Input Indicator LED (Green). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ページ5に含まれる内容の要旨
IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This Manual Contains Important Safety Instructions. Read all safety and operating instructions before operating the Uninterruptible Power Supply (UPS). Adhere to all warnings on the unit and in this manual. Follow all operating and user instructions. This equipment can be operated by individu- als without previous training. This product is designed for Commercial/Industrial use only. It is not intended for use with life sup- port and other
ページ6に含まれる内容の要旨
GLOSSARY OF SYMBOLS Risk of electrical shock Indicates caution followed by important instructions ! AC input AC output Requests the user to consult the manual i - + Indicates the unit contains a valve-regulated lead acid battery PbH2SO4 R Recycle DC voltage Equipment grounding conductor Bonded to ground AC voltage ON/Alarm Silence/Battery Test OFF/Bypass Indicates the position of a fuse 2
ページ7に含まれる内容の要旨
Introduction 1.0 INTRODUCTION Congratulations on your choice of the Liebert UPStation GXT2-6000RT230 and GXT2-4500RT230 Uninterruptible Power System (UPS). It provides conditioned power to microcomputers and other sensitive electronic equipment. Upon generation, AC power is clean and stable. However, during transmission and distribution it may be subject to voltage sags, spikes, or complete power failure that may interrupt computer opera- tions, cause data loss, or even damage equipment. The
ページ8に含まれる内容の要旨
System Description 2.0 SYSTEM DESCRIPTION Input Output Dynamic Bypass L1 L1 Rectifier TVSS & /PFC Inverter EMI/RFI DC-to-DC Filters Converter N N Battery Battery Charger G G 2.1 Transient Voltage Surge Suppression (TVSS) and EMI/RFI Filters These UPS components provide surge protection and filter both electromagnetic interference (EMI) and radio frequency interference (RFI). They minimize any surges or interference present in the mains line and keep the sensitive equipment protected. 2.2 R
ページ9に含まれる内容の要旨
System Description 2.5 DC-to-DC Converter The DC to DC converter utilizes energy from the battery system and raises the DC voltage to the opti- mum operating voltage for the inverter. This allows the inverter to operate continuously at its opti- mum efficiency and voltage, thus increasing reliability. 2.6 Battery The UPStation GXT2 utilizes valve-regulated, nonspillable, lead acid batteries. To maintain battery design life, operate the UPS in an ambient temperature of 20°C to 25°C (68°F to 77°
ページ10に含まれる内容の要旨
Major Components 3.0 MAJOR COMPONENTS The GXT2 is composed of three major assemblies to provide easier handling, installation, and versa- tility. 3.1 Main Frame and Electronics This 5U cabinet is shipped with internal batteries installed and a basic, hardwire distribution box attached and ready to install. Figure 1 GXT2, front view Top Trim (2 pieces; tower use only) Lower Bezel & Battery Access Door Status Indicators & Controls Upper Bezel 6 ! UPStation GXT
ページ11に含まれる内容の要旨
Major Components Figure 2 GXT2, rear view Battery Disconnect External Battery Fans Connector UPS Output Circuit Breaker DB-9 Communication REPO Connector Port Relay Card Slot Removable Power Distribution Box Serial Card Slot (SNMP, OCWEB, USB) 3.2 Internal Battery Packs The UPS has two internal battery packs behind a battery access door on the front of the unit. Each pack is fitted with a connector to link to the UPS. Figure 3 Internal battery pack with connector 7
ページ12に含まれる内容の要旨
Major Components 3.3 Removable Power Distribution Box The UPS arrives with a basic hardwire power distribution pack installed. This box always contains the UPS input circuit breaker. Optional versions may be available to replace the standard box for custom installations. Figure 4 Power distribution boxes, basic, optional Basic Hardwire Power Distribution Box Optional Hardwire Power Distribution PD-CEHDWR Box with Maintenance Bypass Switch PD-CEHDWRBYP NOTE Hardwire and hardwire/receptacle boxe
ページ13に含まれる内容の要旨
What’s Included 4.0 WHAT’S INCLUDED The GXT2 are shipped with the following items: • GXT2-6000RT230 and GXT2-4500RT230 user manual • Vertical display overlay • Top bezels - 2 • MultiLink software CD • MultiLink serial cable, 10 ft (3m) • Rack mount handles • Support base - 2 • Mounting hardware • Configuration program disk •DB9 port cover Top bezels (tower use) MultiLink software CD MultiLink serial cable 10 ft (3m) Vertical Rack mount display handles www.liebert.com overlay GXT2™ Configurat
ページ14に含まれる内容の要旨
Installation and Configuration 5.0 INSTALLATION AND CONFIGURATION Do NOT attempt to start the UPS, turn on any circuit breaker or energize the input power until instructed to do so in 6.0 - Initial Start-Up and Electrical Checks. Visually inspect the UPS for freight damage. Report any damage to the carrier and your local dealer or Liebert representative. CAUTION ! The UPS is heavy (see 13.0 - Specifications). Take proper precautions when lifting or moving it. Install the GXT2 indoors in a con
ページ15に含まれる内容の要旨
Installation and Configuration 5.1.3 Installing the Adjustable Rack-Mount Kit—Sold Separately This kit contains parts needed to mount several different models of UPS and external battery cabi- nets into EIA310-D standard four-post racks that are 18-32" deep (457-813mm). The weight limit per pair of adjustable rack-mounting brackets is 91 kg (200lbs.). Parts included are: Item Quantity Rear bracket members 2 Front bracket members 2 Inner bracket members 2 M4 x 8mm machine screws 16 M4 locking he
ページ16に含まれる内容の要旨
Installation and Configuration 4. Get eight (8) M4 screws and eight (8) M4 nuts from the M4 nuts M4 screws hardware pack in this kit. Each nut has a locking, nylon insert that begins gripping the screw when it is halfway tight. Make sure to tighten the nut and screw completely to ensure locking action. Fasten the rear member and the front member together using (4) screws and (4) nuts per bracket assembly as shown in at right. For maximum support, insert 457mm fasteners for each bracket a
ページ17に含まれる内容の要旨
Installation and Configuration 5.2 External Battery Cabinet Installation Optional Liebert external battery cabinets may be connected to the UPS to provide additional battery run time. External battery cabinets are designed to be placed on one side of the UPS or stacked beneath the UPS. CAUTION ! The external battery cabinet(s) are heavy (see 13.0 - Specifications). External battery cabinets can be used in rack-mount or tower configuration. Take proper precautions when lifting them. 1. Visua
ページ18に含まれる内容の要旨
Installation and Configuration 5.3 Connect the Internal Batteries Using the External Connector The internal connectors of the internal battery packs will be connected when shipped. However, the internal batteries will be disconnected from the UPS using a rear panel connector. The connector attaches to the UPS in both the open and closed position using two screws. The picture on the left shows the connector in the open position, as shipped. When the UPS is installed, remove the two screws to
ページ19に含まれる内容の要旨
Installation and Configuration Figure 6 Distribution box electrical connections diagram PD-CEHDWR PD-CEHDWRBYP Input Mains Mains Input Byp. Input Input Output 32A Output 32A CB CB External External Inv. 30 30 Branch Branch CB CB UPS UPS Output Output CB CB 30 30 UPS - PFC, Battery, Inverter UPS - PFC, Battery, Inverter PD-CEHDWR and PD-CEHDWRBYP Terminal Block Connections Conduit entry holes are provided on the rear and side of the box. Input and output wiring should not share the same cond
ページ20に含まれる内容の要旨
Initial Start-Up and Electrical Checks 6.0 INITIAL START-UP AND ELECTRICAL CHECKS 1. Verify that the Input Output circuit breakers are off. 2. During initial system checks, disconnect all loads (open load disconnects). 3. Inspect all wiring, cables, and connection. 4. If external battery cabinets are used, verify that the battery interconnect cables are fully inserted in the sockets. 5. If you are using a distribution box that includes a Manual Bypass Switch, place the switch in BYPASS positi