FALCON ELECTRIC, INC.
TM
SUP Series User’s Guide
700-1000VA
SUP700-1C, SUP1.0K-1C
FALCON® ELECTRIC, INC.
5106 Azusa Canyon Road
Irwindale, CA 91706
Tel. 626-962-7770
Fax. 626 962-7720
WWW.FALCONUPS.COM
OM48031-SUP, 01/09/04, Rev A.
800.842.6940
ページ2に含まれる内容の要旨
TABLE OF CONTENTS Important Safety Instructions (READ FIRST) . . 2 Chapter 1. SUP UPS Overview . . . . 3 Chapter 2. Installation . . . . . . 4 Inspecting the Equipment . . . . 4 UPS Setup . . . . . . . 4 Communications Interface . . . . 5 Chapter 3. Controls, Displays & Functions. . . 6 Front Panel Diagram & Description . . . 6 LCD Symbol Descriptions . . . . 6 LCD Metering Display Modes . . . . 9 Rear Panel Diagram & Description . . . 9 Chapter 4. Operation . . . . . . 11 Turning The UPS On an
ページ3に含まれる内容の要旨
IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions which must be followed during the installation, operation and maintenance of this UPS and its batteries. Please read all instructions before operating this equipment and save this manual for future reference. CAUTION All of the models presented herein are designed for installation and use in a controlled environment free of contamination. CAUTION This UPS utilizes voltage that may be hazardous. Do
ページ4に含まれる内容の要旨
CHAPTER 1 CHAPTER 1 ® FALCON SMP Series - Overview ® The FALCON SUP Series UPS has the unique ability to operate from either 120Vac domestic or 230Vac international utility power, while providing 120Vac domestic output power. The SUP does not perform frequency conversion, however it is the ideal solution for the international traveller requring voltage conversion. The Line-interactive or Automatic Voltage Regulator (AVR) feature provides output voltage regulation, while the UPS is operating
ページ5に含まれる内容の要旨
CHAPTER 2 CHAPTER 2 Installation Inspecting the Equipment ® If any FALCON equipment has been damaged during shipment, keep the shipping cartons and packing materials for the carrier and file a claim for shipping damage. If you discover damage after acceptance, file a claim for concealed damage. To file a claim for shipping damage or concealed damage: 1) File with the carrier within 15 days of receipt of the equipment; 2) Send a copy ® of the damage claim within 15 days to the Falcon Service
ページ6に含まれる内容の要旨
Communications Interface The UPS provides both a contact closure and a true RS-232 computer interface. The definition and setup for RS-232 is as follows: Baud Rate : 2400 bps Data Length : 8 bits Stop Bit : 1 bit Parity : None Pin #6: RS-232 data Tx out Pin #7: Common for Pin #6 and Pin #9 Pin #9: RS-232 data Rx In The definition and setup for DB9 (optional) is as follows: Pin #2: AC Power Failure Pin #4: Common GND of Pin #2 & Pin #5 Pin #5: UPS Battery Low Pin #6: Turn off UPS Pin #7: GND fo
ページ7に含まれる内容の要旨
CHAPTER 3 CHAPTER 3 Controls, Displays & Functions FRONT PANEL B C A A. Main Control Button - This button is used to turn the UPS on and off, to perform a UPS self test, or to reset and silence an audible alarm. Refer to page 10 for operation instructions. B. A Liquid Crystal Display (LCD) is provided. Please reference the number designation for the display function and the function descriptions referenced in this manual. Refer to pages 6-8 in this
ページ8に含まれる内容の要旨
LCD SYMBOL DESCRIPTIONS LCD DISPLAY 1. Over Load --The connected load exceeds the UPS output rating. Remove some of the load from the UPS to correct this condition. 2. Load Level --Bar graph indicates the percent of UPS load capacity remaining. 3. UPS is loaded - This symbol is displayed when the UPS output load exceeds 30 watts and disappears when the load is under 25%. 4. Normal Mode - The sinewave symbol will be displayed when the UPS is operating normally from the utility line. Batt
ページ9に含まれる内容の要旨
6 Boost Mode - The AVR is increasing the UPS output voltage due to a low utility voltage condition or "Brown-out". The sinewave symbol is also displayed to indicate that the UPS is operating normally from the utility line. 7. Timer is enabled - This symbol will be displayed during the following conditions: a) The UPS has been programmed to automatically turn on or off using the supplied remote monitoring software. b) The green mode is enabled and the UPS output load is under 25 watts. The UPS
ページ10に含まれる内容の要旨
15. LCD Metering Display - When the UPS is turned on, this portion of the LCD display indicates the AC output voltage initially. Depressing the downward scroll button will indicate the following each time it is depressed: LCD Metering Display Modes (use display scroll buttons to change modes; modes are in descending order) Mode Value Display Description AC Output Voltage AC Output Voltage AC Input Voltage AC Input Voltage AC Output Frequency (Hz) AC Output Frequency Battery Voltage DC Bat
ページ11に含まれる内容の要旨
2. Input Fuse - Always replace with the same fuse type and rating. 3. Inlet - for connection of incoming power cord. 4. UPS output receptacles - The top NEMA type receptacles will be found on all domestic (120V) models. IEC type receptacles will be found on international (230V) models. 5. DB-9 RS-232 computer interface connector. 6. Surge protected, RJ11 type telephone jacks - To provide surge protection for your fax, modem or other telecommunications devices. Connect the incoming telephone
ページ12に含まれる内容の要旨
CHAPTER 4 CHAPTER 4 Operation 1. Turning The UPS On and Off Depending on how the UPS was turned off, it may automatically turn on when the input plug is plugged in. If it does not turn on automatically, depress the control button located on the front panel for four seconds until the UPS turns on. To turn the UPS off press and hold the control button for five seconds or until the UPS turns off. UPS batteries will still continue to recharge after the UPS has turned off. 2. UPS Self Test Depr
ページ13に含まれる内容の要旨
6. Battery Charging This UPS is shipped from the factory with its batteries fully charged. However, some charge may be lost due to the self discharge characteristics of the internal sealed lead-acid battery. Always allow the UPS to recharge for 24 hours prior to use. To recharge, simply connect the UPS line cord to a powered receptacle. The UPS does not have to be turned on for batteries to recharge. During normal use, the UPS will self recharge should the battery be depleted due to a los
ページ14に含まれる内容の要旨
CHAPTER 5 CHAPTER 5 Maintenance & Technical Support 1. Care & Maintenance ® Falcon SUP Series UPSs are designed to be maintenance free. They can be cleaned with a damp cloth or non-abrasive cleanser, providing the UPS is turned off and the input plug is disconnected from the utility source. On a regular basis, check the vents to make sure they are kept free from accumulation of dust, dirt or lint. 2. Battery Replacement Warning Momentarily depressing the UPS control button while the UPS is o
ページ15に含まれる内容の要旨
NECESSARY PRECAUTIONS The following precautions should be observed by a qualified technician when working with batteries: 1. Remove watches, rings, or other metal objects. 2. Use tools with insulated handles. 3. Wear rubber gloves and boots. 4. Do not lay tools or metal parts on top of batteries 4. Storing the UPS and Batteries Should you need to store the UPS for a long period, fully recharge the battery just prior to storage and recharge the battery every 6 months by plugging the UPS into a
ページ16に含まれる内容の要旨
6. Technical Support ® Your FALCON Electric SUP Series UPS is backed by one of the finest customer service teams assembled. Write, call, fax or email should you require technical assistance or service. FALCON ELECTRIC, INC. 5106 Azusa Canyon Road Irwindale, CA. 91706 Voice 626.962.7770 Fax 626.962.7720 Service 800.842.6940 Email: service@falconups.com WWW.FALCONUPS.COM Should service be desired, you must first obtain a Return Material Authorization number (RMA) and return shipping instructions
ページ17に含まれる内容の要旨
WARRANTY WARRANTY 1. TIME AND SCOPE OF WARRANTY: ® 1.1 FALCON hereby warrants parts shipped under this Agreement to be free from defective workmanship for a period of one year following date of shipment. Accidental damage, misuse or normal wear and tear shall not be construed as a defect. 1.2 The date of shipment as used herein will be the date on the Bill of Lading. If no Bill of Lading is issued, the date of shipment shall be shown on seller's shipping document. 1.3 No provision of this
ページ18に含まれる内容の要旨
SUP Series™ UPS 700VA & 1kVA Model Number SUP700-1C SUP1.0K-1C Nominal VA 700 1000 Electrical Input Nominal AC Voltage 120V or 230V 120V or 230V Current-Amps 7 (120V), 3.6 (230V) 10 (120V), 5.2 ( 230V) AC Voltage Window -21% to 25% Frequency 50/60 Hz (Auto – Tracking) Frequency Range 47 – 63Hz UPS is designed for use on 120V domestic or 230V international utility power with neutral, line and ground connections. Electrical Output Watts 490 650 Nominal AC Voltage 120V