Powerware 9170 Rail Kit
9- and 12-Slot Cabinets
Installation Guide
ページ2に含まれる内容の要旨
Powerware is a registered trademark of Eaton Power Quality Corporation. Torx is a registered trademark of Textron, Inc. ECopyright 2002-2006 Eaton Corporation, Raleigh, NC, USA. All rights reserved. No part of this document may be reproduced in any way without the express written approval of Eaton Corporation.
ページ3に含まれる内容の要旨
Rack-Mount Installation To install a 9-or 12-slot uninterruptible power system (UPS) cabinet into a rack, you must order a cabinet specifically designed for rack-mounting. Nine-and 12-slot battery cabinets ASY-0749 and ASY-0750 are also available for rack-mounting. These models can be installed in an EIA-standard 48.3 cm (19”) equipment rack and include a rack-mounting kit with the brackets and required hardware. To install the UPS or battery cabinet in the equipment rack: NOTE The9- and12-slotc
ページ4に含まれる内容の要旨
RACK-MOUNT INSTALLATION 4. Install six metal clip nuts (nine clip nuts for 12-slot cabinets) onto each side flange along the front of the cabinet (see Figure 1). NOTE DONOTinstallmetalclipnutsinthebottomcabinetsection. MetalClipNuts TabSlots TabSlots MetalClipNuts TabSlots MetalClipNuts Figure1.MetalClipNutandTabSlotLocations ® + 2 EATON Powerware 9170 Rail Kit (9- and 12-Slot Cabinets) Installation Guide S 164201420 Rev B www.powerware.com
ページ5に含まれる内容の要旨
RACK-MOUNT INSTALLATION 5. Install two rack-mount ears (three for 12-slot cabinets) on each side of the cabinet (see Figure 2). Insert the two offset tabs on the rear edge of the ear into the matching tab slots on the cabinet side frame (see Figure 1). Pivot the ear forward until it is flush against the cabinet side frame. Secure each ear with three 1/4-20 ×1/2” Phillips-head bolts; screw the bolts into the metal clip nuts installed in Step 4. NOTE DONOTinstallrack-mountearsinthebottomcabinetsec
ページ6に含まれる内容の要旨
RACK-MOUNT INSTALLATION 6. Select the proper holes in the rail that position the cabinet at the desired location in the rack. 7. Install one equipment rail on each side of the rack using four 10-32 ×1/2” flat-head screws per rail. 8. With one person lifting each side of the cabinet, position the cabinet onto the two equipment rails (see Figure 3). Carefully slide the cabinet into the equipment rack until the rack-mount ears of the cabinet are flush with the front vertical rails of the rack. Veri
ページ7に含まれる内容の要旨
RACK-MOUNT INSTALLATION ® 9. Secure the cabinet in the rack using 10-32 ×1/2” Torx screws or other appropriate customer-specified screws. 10. Follow the instructions in the UPS user’s guide to install the power and battery modules. Service and Support If you have any questions or problems with the UPS, call your Local Distributor or the HelpDesk at one of the following telephone numbers and ask for a UPS technical representative. United States: 1-800-356-5737 or 1-919-870-3149 Canada: 1-800-461-
ページ8に含まれる内容の要旨