ページ2に含まれる内容の要旨
© 1999 DENSO SALES CALIFORNIA, INC. All rights reserved. This book may not be reproduced or copied, in whole or in part, without the written permission of the publisher. DENSO SALES CALIFORNIA, INC. reserves the right to make changes without prior notice. MovinCool is a registerd trademark of DENSO Sales California, Inc.
ページ3に含まれる内容の要旨
SERVICE MANUAL CLASSIC PLUS 26
ページ4に含まれる内容の要旨
ページ5に含まれる内容の要旨
FOREWORD This manual has been published to service the MovinCool Classic Plus 26. Please use this service manual only when servicing the Classic Plus 26. DEFINITION OF TERMS WARNING: Describes precautions that should be observed in order to prevent injury to the user during installation or unit operation. CAUTION: Describes precautions that should be observed in order to prevent damage to the unit or its components, which may occur during installation or unit operation if sufficient care is n
ページ6に含まれる内容の要旨
ii
ページ7に含まれる内容の要旨
Table of Contents FOREWORD ............................................................................................................................... i DEFINITION OF TERMS ............................................................................................................ i GENERAL PRECAUTIONS ........................................................................................................ i GENERAL DESCRIPTION .................................................................
ページ8に含まれる内容の要旨
iv
ページ9に含まれる内容の要旨
GENERAL DESCRIPTION Generally speaking, conventional air conditioners cool the entire enclosed environment. They act as “heat exchangers”, requiring an interior unit (evaporator) to blow cool air into the interior and an exterior unit (condenser) to exhaust exchanged heat to the out- doors. Unlike conventional air conditioners, the MovinCool Spot Cooling System is a spot cooler which directs cool air to particular areas or objects. MovinCool Spot Cooling Systems have the following features: EV
ページ10に含まれる内容の要旨
GENERAL DESCRIPTION 2
ページ11に含まれる内容の要旨
CONSTRUCTION, SPECIFICATIONS & DATA Construction of Classic Plus 26 3
ページ12に含まれる内容の要旨
CONSTRUCTION, SPECIFICATIONS & DATA Side Panel High Pressure Switch Blower Housing (Evaporator) Exhaust Air Outlet Evaporator Fan Condenser Side Panel Upper Panel Cool Air Duct Modulating Tank Blower Housing Control Panel (Condenser) Fan Motor Front Panel Condenser Fan Evaporator Air Filter (Condenser) Air Filter (Evaporator) Capillary Tube Drain Pan Control Box Drain Tube Service Panel Base Panel Base Panel Base Panel Drain Switch Rear Panel Power Cord Drain Tank Caster Compressor Construction
ページ13に含まれる内容の要旨
CONSTRUCTION, SPECIFICATIONS & DATA 1. Basic Construction The MovinCool Spot Cooling System is compact in construction because the con- denser and the evaporator are enclosed in one unit. The interior is divided into three sections. The upper front face is equipped with the evaporator, while the lower front face contains the drain tank. The rear section contains the condenser, the compressor and the control box. 2. Air Flow Air drawn from the right side face passes through the condenser which
ページ14に含まれる内容の要旨
CONSTRUCTION, SPECIFICATIONS & DATA Rating Conditions o o dry bulb 95 F (35 C) o o wet bulb 83 F (28.3 C) humidity (60%) Specifications power frequency 60Hz line voltage, single phase 208/230V power consumption 3.37/3.24 Kw current consumption 16.8/14.6 Amps power factor 97% starting current 62A power cord 12 (3-core) AWG Cooling Unit cooling capability 6,500 Kcal/hr 26,000 Btu/hr cooling system direct expansion Blower type of fan centrifugal fan air volume: Evaporator (high speed) 708 cfm Conde
ページ15に含まれる内容の要旨
3.70 10.80 48.0 3.88 44.12 CONSTRUCTION, SPECIFICATIONS & DATA 10.60 2.62 3.84 7.28 29.24 23.76 12.56 2.80 21.88 3.72 16.80 28.40 19.60 Exterior Dimensions 7
ページ16に含まれる内容の要旨
CONSTRUCTION, SPECIFICATIONS & DATA Cool Air Temperature Difference Curve (high speed only) Cooling Capability Curve (high speed only) Power Consumption Curve (high speed only) 8
ページ17に含まれる内容の要旨
REFRIGERANT SYSTEM The component parts of the refrigerant system include the following: • Compressor • Evaporator • Condenser • High pressure switch • Capillary tube • Modulating tank These parts are all connected by copper piping. All the connections have been brazed. Modulating Tank Evaporator Condenser Capillary Tube Compressor High Pressure Switch Refrigerant System 9
ページ18に含まれる内容の要旨
REFRIGERANT SYSTEM 1. Compressor The compressor used for the unit is hermetically sealed. The compressor and the compressor motor are in one casing. A. Compressor Theory of Operation The scroll utilizes an involute spiral which, when matched with a mating scroll form, generates a series of crescent-shaped gas pockets between the two members. During compression, one scroll remains stationary (fixed scroll) while the other form (orbiting scroll) is allowed to orbit (but not rotate) around the fi
ページ19に含まれる内容の要旨
REFRIGERANT SYSTEM 4) By the time the gas arrives at the center port, discharge pressure has been reached. 5) Actually, during operation, all six gas passages are in various stages of com- pression at all times, resulting in nearly continuous suction and discharge. NOTE: Upon compressor shut-off, the compressor may run backward for a moment or two until internal pressures equalize. This has no effect on compres- sor durability but may cause an unexpected sound after the compressor is turned off
ページ20に含まれる内容の要旨
REFRIGERANT SYSTEM 3. Capillary Tube The capillary tube is a long thin tube and its line flow resistance serves as an expansion valve. The length and the inner diameter of the capillary tube are determined according to the capacity of refrigeration system, operating conditions and the amount of refrigerant. The capillary tube causes the high pressure, high temperature liquid refriger- ant sent from the condenser to expand rapidly as the refrigerant is sprayed out through the fixed orifice in the