Hi Delta SS™, TYPE H - MODELS HD101-HD401
Effective: 6-25-09
SUGGESTED SPECIFICATIONS
Replaces: New
DIVISION 23 52 33.13
FINNED WATER-TUBE BOILERS
PART 1 - GENERAL
1.1 SUMMARY
A. Section includes gas-fired, copper finned-tube hydronic heating boilers
B. Related Sections
Specifier Note: Use as needed
1. Building Services Piping – Division 23 21 00
2. Breeching, Chimneys, and Stacks (Venting) – Division 23 51 00
3. HVAC Instrumentation and Controls – Div
ページ2に含まれる内容の要旨
2. Product: Hi Delta SS™ copper finned-tube hydronic boiler(s) 2.2 BOILERS A. General 1. The boiler(s) shall be fired with gas at a rated input of BTU/hr. 2. The boiler(s) shall be CSA tested and certified with a minimum thermal efficiency of 84 percent at full fire. 3. The boiler(s) shall be ASME inspected and stamped and National Board registered for 160 PSIG working pressure, complete with a Manufacturer's Data Report. 4. The boiler(s) shall have a flo
ページ3に含まれる内容の要旨
1. Provide internal LED displaying the following boiler status/faults: a. Steady on – Internal control failure b. One flash – Air flow fault c. Two flashes – Erroneous flame signal d. Three flashes – Ignition lockout I. Combustion Chamber: The lightweight, high-temperature, multi-piece, interlocking ceramic fiber combustion chamber liner shall be sealed to reduce standby radiation losses, reducing jacket losses and increasing unit efficiency. J. Venting 1. When routed vertically, the bo
ページ4に含まれる内容の要旨
PART 3 - EXECUTION 3.1 INSTALLATION A. Must comply with: 1. Local, state, provincial, and national codes, laws, regulations and ordinances 2. National Fuel Gas Code, ANSI Z223.1/NFPA 54 – latest edition 3. National Electrical Code, ANSI/NFPA 70 – latest edition 4. Canada only: CAN/CSA B149 Installation Code and CSA C22.1 CEC Part I 5. Manufacturer’s installation instructions, including required service clearances and venting guidelines B. Manufacturer’s representative to verify proper