ページ1に含まれる内容の要旨
®
POWERWARE 3110
300–700 VA
User’s Guide
www.powerware.com
ページ2に含まれる内容の要旨
Class B EMC Statements FCC Part 15 NOTE This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, the
ページ3に含まれる内容の要旨
TABLE OF CONTENTS 1 Installation .................................................. 1 Inspecting the Equipment ..................................................... 1 Safety Precautions .......................................................... 1 Quick Startup ............................................................. 2 UPS Top and Side Panels ..................................................... 3 2 Features ..................................................... 5 Communication Options ......
ページ4に含まれる内容の要旨
Table of Contents ® Powerware 3110 User’s Guide Rev B www.powerware.com ii
ページ5に含まれる内容の要旨
CHAPTER 1 INSTALLATION This section explains: Equipment inspection Safety precautions UPS installation UPS top and side panels Inspecting the Equipment If any equipment has been damaged during shipment, keep the shipping cartons and packing materials for the carrier or place of purchase and file a claim for shipping damage. If you discover damage after acceptance, file a claim for concealed damage. To file a claim for shipping damage or concealed damage: 1) File with the carrier within 1
ページ6に含まれる内容の要旨
Installation To reduce the risk of fire or electric shock, install this UPS in a temperature and humidity controlled, indoor environment, free of conductive contaminants. Ambient temperature must not exceed 40°C (104°F). Do not operate near water or excessive humidity (95% max). With the exception of the user-replaceable battery, all servicing of this equipment must be performed by qualified service personnel. Before maintenance or repair, all connections must be removed. Before maintenanc
ページ7に含まれる内容の要旨
Installation 3. Start the UPS by pressing the switch as shown in Figure 2 or Figure 4 on page 4. Theµ indicator illuminates indicating that power is available from the UPS output receptacles. The unit beeps and the front panel LEDs illuminate several times. Theµ indicator remains on, indicating normal operation. If the unit continues to beep, or if theµ indicator is off even though input power is available from the wall outlet, see “Troubleshooting” on page 15. NOTE Let the unit charge the batte
ページ8に含まれる内容の要旨
ページ9に含まれる内容の要旨
CHAPTER 2 FEATURES This section covers: Using the USB or DB-9 communication port Starting the UPS on battery Communication Options The UPS is equipped with a USB and a DB-9 communication port. Either the USB port or the DB-9 communication port may be used to monitor the UPS; however, they cannot operate simultaneously. USB Port The UPS can communicate with a USB-compliant computer using LanSafe Power Management Software (v4.15 or higher). To establish communication between the UPS and a comp
ページ10に含まれる内容の要旨
Features DB-9 Communication Port Powerware offers an accessory interface kit that allows you to connect many types of computer systems to the UPS communication port. For specific information on Powerware interface kits, call your service representative. Contacts consist of open collector circuits capable of switching up to +30 Vdc, 6 mA resistive load. Table 1. Communication Port Pin Assignment Pin Signal Type Function 1 RS-232 Level Shutdown +12 Vdc signal held for 5 seconds on this pin shuts t
ページ11に含まれる内容の要旨
Features Battery Start Feature The Battery Start feature allows you to turn on the UPS when utility power is not available. The battery-start range is up to about 40% of nominal input; otherwise, the UPS displays an input voltage fault and the alarm beeps. RJ-11 or RJ-45 Surge Protectors The RJ-11 or RJ-45 surge protectors are located on the side panel and are labeled IN and OUT. This feature accommodates an RJ-11 connector that provides protection for modems, fax machines, or other telecommunic
ページ12に含まれる内容の要旨
Features ® Powerware 3110 User’s Guide Rev B www.powerware.com 8
ページ13に含まれる内容の要旨
CHAPTER 3 UPS MAINTENANCE This section explains how to: Care for the UPS and batteries Replace the batteries Recycle used batteries UPS and Battery Care For the best preventive maintenance, keep the area around the UPS clean and dust-free. If the atmosphere is very dusty, clean the outside of the system with a vacuum cleaner. For full battery life, keep the UPS at an ambient temperature of 25°C(77°F). Storing the UPS If you store the UPS for a long period, recharge the battery every 6 mont
ページ14に含まれる内容の要旨
UPS Maintenance CAUTION The 230V models require replacement by qualified service personnel. 1. Contact your service representative to order a replacement battery. It must be the same type and rating as the original battery (see Table 3 on page 14). 2. Switch off and unplug the protected equipment from the UPS. 3. Turn off the UPS and disconnect the power cord. 4. Turn the UPS upside down. Battery Battery Cover Figure 5. Removing the Battery Cover and Battery 5. Remove the battery cover: Models 5
ページ15に含まれる内容の要旨
UPS Maintenance 10. Replace the battery cover by pushing the cover until it snaps into place securely. Replace any battery cover screws that were removed to access the battery. 11. Turn the UPS right side up. Reconnect the UPS power cord and turn the unit on. 12. Reconnect the equipment. Switch on the protected equipment one piece at a time. Recycling the Used Battery Contact your local recycling or hazardous waste center for information on proper disposal of the used battery. WARNING Do not d
ページ16に含まれる内容の要旨
UPS Maintenance ® Powerware 3110 User’s Guide Rev B www.powerware.com 12
ページ17に含まれる内容の要旨
CHAPTER 4 SPECIFICATIONS Powerware Corporation reserves the right to change specifications without prior notice. Table 2. Electrical 120V Model 230V Model Nominal Voltage 120V 230V Power Factor 0.6 Voltage Range Online: 90–152V Online: 176–272V On Battery: 0–100V and 152–160V On Battery: 0–192V and 272–290V Nominal Frequency 50/60 Hz auto-sensing 57–63 Hz (60 Hz) 47–53 Hz (50 Hz) Efficiency > 95% (Normal mode) Noise Filtering Full-time EMI/RFI filtering Overcurrent Protection Resettable circuit
ページ18に含まれる内容の要旨
Specifications Table 3. Battery Configuration 300 VA: (1) 12V, 4.2 Ah or (2) 6V, 4.0 Ah internal battery(s) 550 VA: (1) 12V, 7.0 or 7.2 Ah internal battery 700 VA: (1) 12V, 9 Ah internal battery Voltage 12 Vdc Type Sealed, maintenance-free, valve-regulated, lead-acid Charging 8 hours to 95% capacity with output fully loaded Monitoring Advanced monitoring for earlier failure detection and warning Backup Time 300– 550 VA: 3 minutes at full load; 5 minutes typical load 700 VA: 2.5 minutes at full l
ページ19に含まれる内容の要旨
CHAPTER 5 TROUBLESHOOTING The front panel LEDs and an audible beep indicate the UPS status (see Table 6). The UPS beeps whenever the unit is on battery power or an alarm is present. Table 6. Troubleshooting Alarm or Condition Possible Cause What to Do Normal operation. None. The UPS is operating in Normal mode. Line loss due to: Utility power outage. Wait for utility power to return. Loose plug connection. Check the power cord connections. Tripped circuit breaker. Reset the circuit b
ページ20に含まれる内容の要旨
Troubleshooting Alarm or Condition Possible Cause What to Do Power requirements exceed the Remove some of the equipment from the UPS. You may UPS capacity. need to obtain a larger capacity UPS. 1 beep every half second. Output short circuit. Turn off or unplug the equipment connected to the UPS. Input voltage is out of range Turn off the UPS until acceptable input voltage when the UPS is turned on. restored. UPS fault. Contact your service representative. Continuous beep. Service and Support If