ページ1に含まれる内容の要旨
Network
Management
Card &
Modbus/
Jbus
(66123)
Installation manual
ページ2に含まれる内容の要旨
2 - 3402230800/AC
ページ3に含まれる内容の要旨
The Network Management Card & Modbus/Jbus (66123) is recommended for central UPSs protecting entire networks or for UPS units backing up critical loads. With the card installed, the UPS has its own IP address and uses the local computer capabilities to: ◗ Supply web pages (http or https (SSL)) with information on status conditions and measurements/settings/ alarms, ◗ Integrate
ページ4に含まれる内容の要旨
. OVERVIEW Jbus/modbus port MAC address ETHERNET 10/100BT port Service port (Settings/Sensor) Orange LED: RS232 activity Green LED: communication with the UPS Catalogue number Orange LED: 10/100M Green LED: connection + activity INDICATIONS ETHERNET port LED Colour Status Description ACT Green ◗ OFF ◗ Card not connected to network ◗ ON ◗ Card connected to network, but no activity ◗ Port is sending/receiving ◗ Flash
ページ5に含まれる内容の要旨
TM TM The Network Management Card & Modbus/Jbus (66123) can be hot-plugged in MGE Galaxy 7000 equipped with a Minislot. It is not necessary to shutdown the UPS, disconnect the load or restart the UPS. ◗ Note the MAC address of the card before inserting it. ◗ Insert and secure the card with the screws. ◗ Connect the ETHERNET cable. ◗ Check the ETHERNET port indications. ◗ Wait until the UPS Data LED flashes regularly (app
ページ6に含まれる内容の要旨
Your network is equipped with a BOOTP/DHCP server (default) The card is configured by default with this service enabled. No manual configuration is required.The IP parameters are automatically collected by the card. From the main configuration menu: (see above) ◗ Press the 2 key (Network configuration). ◗ Press the 1 key(Read Network settings). The settings supplied by the server are displayed: Network configuration : MAC address : 00:06:23:00:1C:07 Mode : DHCP IP address : 172.17.23.18 Sub
ページ7に含まれる内容の要旨
ACCESS TO SUPERVISION To check whether the Network Management Card & Modbus/Jbus (66123) is operational after installation and configuration, proceed as follows. ◗ Run a browser ◗ Enter in the address bar: http://IP address/ (e.g. http://172.16.1.82/) ◗ The home page is displayed ◗ Set the time by clicking the Time command. ◗ Continue configuration via the sections in the Settings menu. USER MANUAL This manual provides all the information required to install and configure the Netw
ページ8に含まれる内容の要旨
!" #" $% SENSOR CONNECTION (option) The Environment sensor is a Network Management Card & Modbus/Jbus option. The sensor remotely monitors the UPS environment by regularly measuring the temperature and humidity, and checking the states of two external contacts. It can also send alarms (e-mail, SNMP trap) tripped by pre-set thre
ページ9に含まれる内容の要旨
JBUS/MODBUS RS232 link configuration and connection
RS485 link configuration and connection For proper operation, the polarity of EIA RS485 2-wire and 4-wire lines must be set at only one point and the lines terminated at the end. Polarity Normally, the master of the network sets the polarity of the line. The receiver inputs have a true fail
ページ10に含まれる内容の要旨
2 wires connection #$ #$
!" !" Card settings of an intermediate cabinet Link without polarity and w
ページ11に含まれる内容の要旨
4 wires connection % % % % % % % %
!
ページ12に含まれる内容の要旨
!" #" $% Configuration of the JBUS/MODBUS communication parameters Through settings port "#$ Connect the RS232 link to a terminal (Microsoft Hyper terminal) ◗ Use the cord supplied with the card ◗ Connect the card to a computer TM ◗ Use a terminal emulator such as HyperTerminal with these settings Bits per second Data bits
ページ13に含まれる内容の要旨
◗ Press the 2 key (Modifiy Jbus settings) ◗ Press «Return» key to modify the Jbus settings Setting Jbus configutration Set Slave number : 0x1* Set the Baud Rate [1:38400,2: 19200, 3:9600, 4: 4800, 5: 2400, 6: 1200] :3 Set data format[1: 8 bits, 2: 7 bits] :1 Set stop bit[1: 1 bits, 2: 2 bits] :1 Set parity [1: None, 2: Even, 3: Odd] :1 Wait during the new setting is saved ... TLS/Slave JBUS initialized The Jbus configuration is now updated. * Hex format. ◗ Press the 0 key (Exit). ◗ Press t
ページ14に含まれる内容の要旨
◗ Set the parameters. ◗ Select the «Save» button to save the new parameters. 14 - 3402230800/AC
ページ15に含まれる内容の要旨
TECHNICAL CHARACTERISTICS Physical characteristics Dimensions (W x D x H) 132 x 66 x 42 mm Weight 70 g RoHS 100% compatible Storage Storage temperature range -10°C to 70°C Ambient conditions Operating temperature range 0°C to 40°C Relative humidity 90% RH max. without condensation Card performance Supply voltage 5V ±5% Supply current (all LEDs ON and 300 mA max. Environment Sensor connected) Functions Web supervision 5 browsers max. (http), 3 browsers max. (https) Languages English, French, Ge
ページ16に含まれる内容の要旨
ELECTROMAGNETIC COMPATIBILITY When correctly installed and used in accordance with manufacturer instructions, the card complies with the following standards: ◗ ITE (Information Technology Equipment) safety: IEC/EN 60950-1 2005 ◗ EMC: EN 61000-6-2 (2005), EN 61000-6-3 (2006), IEC/EN 62040-2 (2005) In compliance with European directives: ◗ Low voltage: 2006/95/EEC. ◗ EMC: 2004/108/EEC. Federal Communication Commission (FCC) statement This equipment has been tested and found to comply with the