ページ1に含まれる内容の要旨
Low-Current 20/20 GMT Series Fuse Panels
Models 06004-01 & 06004-11
Installation Guide
Telect’s 1RU Traditional Low-Current GMT Series Fuse Panels
provide protected secondary -24 Vdc to -48 Vdc power distri-
bution to telecommunications equipment at the bay level. Fuse
panels are available for GMT outputs up to 10A per position in
dual-circuit panel configurations having 20 GMT fuse positions
per circuit.
Front
• Model 06004-01 is the standard panel containing sepa-
rate Side A and Side B GM
ページ2に含まれる内容の要旨
Electrical Specifications Operating voltages, nominal -24 Vdc to -48 Vdc Current capacity06004-01 20A per bus (40A total for both buses), max. with 20A ce- ramic input fuse (Type ABC) 06004-11 15A per bus (30A total for both buses), max, with 20A ce- ramic input fuse (Type ABC) Fuse capacity 20 (ea side) Maximum PDU input interruption device rating 25A per bus Maximum output interruption device rating 10A GMT fuse Maximum continuous output load rating 7A for a 10A fuse Alarm contact relay 2A
ページ3に含まれる内容の要旨
Plastic Caps* Alarm Pins for Circuits Screw-Tight, Wire-Clamping Output Terminals A & B CAUTION: DO NOT REVERSE POLARITY -24V FA AUX RLY TO FA AUX RLY A -48V B FA -24/48V IN A B FA +GND IN RTN FAIL RELAY NO C NC NO C NC -A -B +A +B Screw-Tight, Wire-Clamping * Plastic caps cover screw-tight terminals used by the manufacturer for installing Input Terminals interior wiring. DO NOT REMOVE CAPS or LOOSEN CLAMPING SCREWS. Models 06004-11 (Rear View) Model 06004-11 includes a fail-safe circuit. Sc
ページ4に含まれる内容の要旨
Left Bracket for 19-in. Rack Remove Screws (4) on Each Side of Panel to Remove Brackets from Stowed Position Right Bracket for 23-in. Rack Right Bracket for 19-in. Rack Left Bracket for 23-in. Rack Panel With Mounting Brackets in Stowed Position for Shipping 3. Select the proper pair of brackets and discard the other two. 4. Mount brackets to sides of panel, as shown in the following examples. Tighten screws to about 29 in.-lb (~3.3 N•m). Panel can be mounted so that panel’s face is flush or ex
ページ5に含まれる内容の要旨
WARNING ! WARNING! Failure to properly ground this equipment can create hazardous conditions to installation person- nel and to the equipment. WARNUNG! Bei unsachgemäßer Erdung besteht Gefahr für das Installationspersonal und das Gerät! ¡AVISO! La conexión incorrecta a tierra puede ser peligrosa tanto para los instaladores como para el equipo. AVERTISSEMENT! Si vous ne reliez pas correctement cet équipement à la terre, son utilisation présente des dangers pour la personne qui l'installe ainsi
ページ6に含まれる内容の要旨
13. Make sure power is off [open breaker, dummy fuse, or vacant fuse holder at power distribution unit (PDU)] before connecting this panel’s cables to PDU. 14. Make sure that only dummy GMT fuses are install in this panel or that the GMT fuse holders are vacant. 15. Enable fuse or breaker at PDU (25A max. for Model 06004-01; 35A max. for Model 06004-11 which contains a fail-safe circuit) to turn on Feed A to Side A of panel. 16. Check voltage and polarity at input connectors of panel. Also, ch
ページ7に含まれる内容の要旨
WARNING ! WARNING! Use only UL-listed or UL-recognized component secondary protection devices. 24. Insert the proper sizes of GMT fuses in designated fuse holders using the designation card to identify circuits. Check voltage and polarity at input of loads. 25. After all designated GMT fuses have been installed, check that the A and B LEDs are still green. If an output fuse blows, the corresponding A or B LED will turn red; if an input fuse blows, the corresponding A or B LED will be orange
ページ8に含まれる内容の要旨
—— Auxiliary Alarms Auxiliary alarms are triggered from either an external CO or site source or by the standard alarm relay. Like the standard relay, when triggered, the auxiliary relay is de-energized causing the normally open contacts to close and the normally closed contacts to open. External External Alarm Device Alarm Device External External Alarm Device Alarm Device +GND (or POS) NEG (or -GND) +GND (or POS) NEG (or -GND) Auxiliary Relay FA AUX RLY Contacts FA AUX RLY A B FA -24/48V IN*
ページ9に含まれる内容の要旨
PARTS & ACCESSORIES 1 GMT FUSES Part Numbers Part Numbers GMT Fuse GMT Fuse GMT Fuse GMT Fuse .18A Yellow (YEL) 130781 2.5A White/Orange (WHT/ORN) 130783 ¼A Violet (VIO) 100151 3A Blue (BLU) 004012 ½A Red (RED) 004001 3.5A White/Blue (WHT/BLU) 130782 ¾A Brown (BRN) 004008 4A White/Brown (WHT/BRN) 004013 1A Gray (GRY) 100991 5A Green (GRN) 004014 1 004006 7½A Black/White (BLK/WHT) 004010 1 /3A White (WHT) 1½A White/Yellow (WHT/YEL) 004011 10A Red/White (RED/WHT) 004015 2A Orange (ORN) 004002 NOTE
ページ10に含まれる内容の要旨
DRAWING -24V TO -48V A B A B RTN FAIL RELAY NO C NC NO C NC Model 06004-01 -24V FA AUX RLY TO FA AUX RLY -48V A B FA -24/48V IN A B FA +GND IN RTN FAIL RELAY NO C NC NO C NC Model 06004-11 #10-32 Panhead Screw R0.21 [R5.4] Min. length of lug tongue is 0.43 in. (10.8 mm) REAR VIEWS (ROTATED) 0.77 [19.7] Face of panel can be extended beyond rack flange by as much as 2.50 in. (63.5 mm) in 0.5 in. 8.17 [207.5] (12.7 mm). 2.50 [63.5] 0.19 [4.9] TOP VIEW "FAIL SAFE" Applies only to Model 06004-11 POWE
ページ11に含まれる内容の要旨
U.S. Conformity Assessment Body Certificate of Conformity No. 174-0923-1-0 ® Upon assessment of Technical Construction File 174-0923-1-0-TCF it has been determined that the Hendry Telephone Products Power Distribution and Fan Panels conform to the protection requirements set out in article 4 of EMC Directive 89/336/EEC as per EN 55022 :94 with A1 :95 & A2 :97 (class A), EN 61000-3-2 :95, EN 61000-3-3 :95, EN 300 386 V1.2.1 :00-03, and ETS 300 132-2; and in accordance with the Agreement on Mutua
ページ12に含まれる内容の要旨