ページ1に含まれる内容の要旨
Quick Start Guide
™
FieldPoint cFP-20xx
What You Need to Get Set Up
•cFP-20xx LabVIEW RT controller � 11–30 VDC power supply
� Mounting hardware (DIN rail, � Accessories: Ethernet cable,
panel-mount, or rack-mount number 2 Phillips screwdriver
accessory)
� PC running Windows
� I/O module(s)
� FieldPoint software 3.0.2 or later
�cFP-BP-x backplane, connector
�LabVIEW RT
blocks, cables
ページ2に含まれる内容の要旨
1. Mount the Compact FieldPoint Backplane You can mount the cFP-BP-x backplane on a 35 mm DIN rail, on a panel, or in a standard 19 in. rack. Before using any of these mounting methods, record the serial number from the back of the backplane. Each set of mounting instructions in this document includes an instruction to connect the protective earth (PE) ground terminal on the cFP-BP-x backplane to the system safety ground. The backplane PE ground terminal has the following symbol stamped bes
ページ3に含まれる内容の要旨
4 slots = 246 mm (9.68 in.) 8 slots = 441 mm (17.4 in.) Cabling Clearance Cabling Cooling Outline Clearance 51 mm (2 in.) All Around 4 slots = 246 mm (9.68 in.) 8 slots = 441 mm (17.4 in.) Cooling Outline Cooling Outline 51 mm (2 in.) 51 mm (2 in.) © National Instruments Corporation 3 cFP-20xx Quick Start Guide Min. 182 mm (7.18 in.) 106 mm (4.18 in.) Min. 165 mm (6.50 in.) 127 mm (5.00 in.)
ページ4に含まれる内容の要旨
Mounting the Backplane on a Panel 1. Fasten the panel-mount plates to the back of the cFP-BP-x using a number 2 Phillips screwdriver and the 8-32 × 5/16 in. countersink screws shipped with the kit. Caution Do not use screws longer than 5/16 in. to fasten the panel-mount plates to the backplane. 102 mm (4 in.) 457 mm (18 in.) cFP-20xx Quick Start Guide 4 ni.com IN N ST AR TU IO M NE AN L TS
ページ5に含まれる内容の要旨
104.78 mm (4.1 in.) 127.00 mm 63.50 mm (5.0 in.) (2.5 in.) 22.23 mm (0.9 in.) 440.94 mm (17.4 in.) 102 mm (4 in.) 260 mm (10.25 in.) © National Instruments Corporation 5 cFP-20xx Quick Start Guide 33.15 mm (1.3 in.) 129.54 mm (5.1 in.) 311.40 mm (12.3 in.) 387.60 mm (15.3 in.) 407.80 mm (16.1 in.)
ページ6に含まれる内容の要旨
104.74 mm (4.1 in.) 63.46 mm 127.00 mm (2.5 in.) (5.0 in.) 22.19 mm (0.9 in.) 245.87 mm (9.6 in.) 2. Bolt or screw the panel-mount accessory to a panel. 3. Connect the PE ground terminal on the cFP-BP-x to safety ground. Caution Disconnect power before removing the backplane from the panel. Mounting the Backplane on a DIN Rail NI recommends DIN rail mounting for the cFP-BP-4 only. Use panel mounting or rack mounting for the cFP-BP-8. The DIN rail mounting kit is NI part number 778614-01. 1.
ページ7に含まれる内容の要旨
Caution Do not use screws longer than 5/16 in. to fasten the DIN rail clip to the backplane. 2. Insert one edge of the DIN rail into the deeper opening of the DIN rail clip. 3. Press down firmly on the backplane to compress the spring until the clip locks in place on the DIN rail. 4. Connect the PE ground terminal on the cFP-BP-4 to safety ground. Caution Disconnect power before removing the backplane from the DIN rail. © National Instruments Corporation 7 cFP-20xx Quick Start Guide IO L IN
ページ8に含まれる内容の要旨
Mounting the Backplane in a Standard 19-in. Rack 1. Fasten the rack-mount bracket to the back of the cFP-BP-x using the captive screws on the bracket. 2. Bolt the rack-mount accessory to a standard 19-in. rack. cFP-20xx Quick Start Guide 8 ni.com NATIONAL INSTRUMENTS
ページ9に含まれる内容の要旨
3. Connect the PE ground terminal on the cFP-BP-x to safety ground. Caution Disconnect power before removing the backplane from the bracket. © National Instruments Corporation 9 cFP-20xx Quick Start Guide NATIONAL INSTRUMENTS
ページ10に含まれる内容の要旨
2. Install the cFP-20xx Controller on the Backplane 1. Make sure that no power is connected to the controller. 2. Make sure that the cFP-20xx controller is right side up with the NI logo at the top, and align the captive screws on the controller with the holes on the backplane. 3. Seat the card edge at the back of the controller in the card-edge connector on the backplane. 4. Press the controller firmly to seat it on the backplane. 5. Using a number 2 Phillips screwdriver with a shank of at l
ページ11に含まれる内容の要旨
NATIONAL INSTRUMENTS © National Instruments Corporation 11 cFP-20xx Quick Start Guide
ページ12に含まれる内容の要旨
3. Install I/O Modules on the Backplane 1. Align the captive screws on the I/O module with the holes on the backplane. 2. Press firmly to seat the I/O module on the backplane. 3. Using a number 2 Phillips screwdriver with a shank of at least 64 mm (2.5 in.) length, tighten the captive screws to 1.1 N · m (10 lb · in.) of torque. 4. Repeat this procedure to install additional I/O modules on the backplane. cFP-20xx Quick Start Guide 12 ni.com
ページ13に含まれる内容の要旨
4. Install Connector Blocks on the Backplane In order to connect I/O modules to input signals or to external loads, you need to install a cFP-CB-x connector block or other connectivity accessory for each I/O module on the backplane. Use the connector socket to the right of each I/O module socket. Caution Do not insert or remove connector blocks or other connectivity accessories while power is applied to them. 1. Wire field devices as described in the I/O module and connector block operatin
ページ14に含まれる内容の要旨
5. Connect the cFP-20xx to Your Network Connect the cFP-20xx controller to an Ethernet network using the RJ-45 Ethernet port on the controller. Use a standard Category 5 Ethernet cable to connect the cFP-20xx to an Ethernet hub, or use an Ethernet crossover cable to connect the controller directly to a computer. Caution To prevent data loss and to maintain the integrity of your Ethernet installation, do not use a cable longer than 100 m. If you are using a 100 Mbps Ethernet, National Instru
ページ15に含まれる内容の要旨
6. Wire Power to the Compact FieldPoint System Each cFP-20xx on your network requires an 11–30 VDC power supply. 1. Connect the positive lead of the primary power supply to one of the V1 terminals and the negative lead to one of the 11–30 VDC Backup C terminals. Power Supply (optional) 2. If you are using a backup power supply, – – + + connect the positive lead to V2 and the 11–30 VDC negative lead to one of the C terminals. Primary Power Supply The cFP-20xx uses the power supply with the
ページ16に含まれる内容の要旨
7. Powering Up the cFP-20xx Check the DIP switches on the controller, making sure that the RESET IP switch is not enabled. Plug in each power supply to the Compact FieldPoint system. The cFP-20xx runs a power-on self test (POST) that takes several seconds. You should see the POWER and STATUS LEDs come on. After about five seconds, the STATUS LED begins flashing steadily. The cFP-20xx is ready to be configured. If you have already assigned an IP address to the cFP-20xx, the STATUS LED turns
ページ17に含まれる内容の要旨
8. Install Software on the Host PC 1. Install the software packages you plan to use, such as LabVIEW, ™ ™ LabVIEW RT, Measurement Studio, VI Logger, or LabWindows /CVI , before you install the FieldPoint software. The FieldPoint software installation installs the LabVIEW VIs and examples and the LabWindows/CVI instrument driver only if it finds the corresponding development software installed. 2. Close all other applications. 3. Insert the National Instruments FieldPoint Software CD into th
ページ18に含まれる内容の要旨
Specifications Network Network interface .............................10BaseT and 100BaseTX Ethernet Compatibility ....................................IEEE802.3 Communication rates........................10 Mbps, 100 Mbps, auto-negotiated Maximum cabling distance...............100 m/segment Maximum power to connected I/O modules .................9 W Maximum number of banks..............Determined by network topology Memory cFP-2000...........................................16 MB nonvolatile; 16
ページ19に含まれる内容の要旨
Power Requirement Power supply range...........................11 to 30 VDC Recommended power supply cFP-BP-4 system........................15 W cFP-BP-8 system........................20 W Power consumption cFP-2000 ....................................4.8 W + 1.1(I/O module power requirements) cFP-2010 ....................................5.0 W + 1.1(I/O module power requirements) cFP-2020 ....................................6.1 W + 1.1(I/O module power requirements) Physical Characteristics S
ページ20に含まれる内容の要旨
Humidity...........................................10 to 90% RH, noncondensing Maximum altitude.............................2,000 m; at higher altitudes the isolation voltage ratings must be lowered Pollution Degree ...............................2 Shock and Vibration Operating vibration Random (IEC 60068-2-64).........10–500 Hz, 5 g rms Sinusoidal (IEC 60068-2-6) .......10–500 Hz, 5 g Operating shock (IEC 60068-2-27)..............................50 g, 3 ms half sine, 18 shocks at 6 orientati