Installing the Cisco ONS 15600 OC48/STM16
LR/LH 16 Port 1550 Card
Note The terms "Unidirectional Path Switched Ring" and "UPSR" may appear in Cisco literature. These terms
do not refer to using Cisco ONS 15xxx products in a unidirectional path switched ring configuration.
Rather, these terms, as well as "Path Protected Mesh Network" and "PPMN," refer generally to Cisco's
path protection feature, which may be used in any topological network configuration. Cisco does not
recommend using its path p
ページ2に含まれる内容の要旨
OC48/STM16 LR/LH 16 Port 1550 Card Warning Read the installation instructions before you connect the system to its power source. Warning This unit is intended for installation in restricted access areas. A restricted access area is where access can only be gained by service personnel through the use of a special tool, lock and key, or other means of security, and is controlled by the authority responsible for the location. Warning Voltage is present on the backplane when the system is operating.
ページ3に含まれる内容の要旨
OC48/STM16 LR/LH 16 Port 1550 Card Table 1 OC48/STM16 LR/LH Card Performance Monitoring Thresholds (continued) Performance Monitoring Thresholds (15 min./1 day) UAS-L 3/10 PSC 1/5 PSD 300/600 Near-End Section PMs for the OC48/STM16 LR/LH Card CV-S 10000/100000 ES-S 500/5000 SES-S 500/5000 SEFS-S 500/5000 Near-End Path PMs for the OC48/STM16 LR/LH Card CV-P 75/750 ES-P 60/600 FC-P 10/10 SES-P 3/7 UAS-P 10/10 PPJC-Pdet 0/0 NPJC-Pdet 0/0 PPJC-Pgen 0/0 NPJC-Pgen 0/0 Far-End Line PMs for the OC48/STM
ページ4に含まれる内容の要旨
OC48/STM16 LR/LH 16 Port 1550 Card Table 1 OC48/STM16 LR/LH Card Performance Monitoring Thresholds (continued) Performance Monitoring Thresholds (15 min./1 day) OPR-High 200% OPR-Low 50% Note SONET path PMs will not count unless IPPM is enabled. For additional information, see the Enabling Intermediate-Path Performance Monitoring section in the Cisco ONS 15600 Procedure Guide. To monitor the SONET path PMs log into the far-end node directly. Installing the Cisco ONS 15600 OC48/STM16 LR/LH 16 Por
ページ5に含まれる内容の要旨
OC48/STM16 LR/LH 16 Port 1550 Card OC48/STM16 LR/LH 16 Port 1550 Faceplate and Block Diagram Figure 1 shows the OC48/STM16 LR/LH 16 Port 1550 faceplate and a block diagram of the card. Figure 1 OC48/STM16 LR/LH 16 Port 1550 faceplate and block diagram OC48/STM16 LR/LH 16 PORT 1550 STAT SRV SD SF LASER ON 16 C-STS-48 copy 0 16 OC48 C-STS-48 copy 1 16 x OC-48 16 x OC-48 16 C-STS-48 copy 0 16 C-STS-48 copy 1 Installing the Cisco ONS 15600 OC48/STM16 LR/LH 16 Port 1550 Card 78-15182-01 5 sync 0 sync
ページ6に含まれる内容の要旨
OC48/STM16 LR/LH 16 Port 1550 Card OC48/STM16 LR/LH 16 Port 1550 Card-Level Indicators Table 2 describes the functions of the card-level LEDs on the OC48/STM16 LR/LH 16 Port 1550 card. Table 2 OC48/STM16 LR/LH 16 Port 1550 Card-Level Indicators Indicators Color Description STAT LED Red Indicates a hardware fault; this LED is off during normal operation. Replace the card if the STAT LED persists. During diagnostics, the LED will flash quickly during initialization and flash slowly during configur
ページ7に含まれる内容の要旨
OC48/STM16 LR/LH 16 Port 1550 Card OC48/STM16 LR/LH 16 Port 1550 Specifications Table 4 shows the OC48/STM16 LR/LH card specifications. Table 4 OC48/STM16 LR/LH 16 Port 1550 Card Specifications Specification Type Description Line Bit Rate: 2.49 Gbps Code: Scrambled NRZ Fiber: 1550 nm single-mode Loopback Modes: Facility Connectors: OGI Compliance: Telcordia SONET, GR-253 Transmitter Max. Transmitter Output Power: +3 dBm Min. Transmitter Output Power: –2 dBm Center Wavelength: 1520 nm to 1580 nm N
ページ8に含まれる内容の要旨
Replace an OC-48 Card OC48/STM16 LR/LH 16 Port 1550 Card OGI Connector Pinout Table 5 shows the OC48/STM16 LR/LH card OGI connector pinouts. Table 5 OC48/STM16 LR/LH 16 Port 1550 Card OGI Connector Pinout Connector OGI Pin and Card Port 112345678 Transmit 4 Receive 4 Transmit 3 Receive 3 Transmit 2 Receive 2 Transmit 1 Receive 1 212345678 Transmit 8 Receive 8 Transmit 7 Receive 7 Transmit 6 Receive 6 Transmit 5 Receive 5 312345678 Transmit 12 Receive 12 Transmit 11 Receive 11 Transmit 10 Receive
ページ9に含まれる内容の要旨
Replace an OC-48 Card Step 3 Ensure that the card you are replacing does carry path protection circuit traffic. Note A port can be part of a 1+1 protection group or part of a path protection, but it cannot be configured for both. However, different ports on one card can be configured in different ways. If you move all of the traffic off some 1+1 ports, you still need to check whether the remaining ports are carrying path protection traffic. a. In the CTC node view, click View > Go to Parent View
ページ10に含まれる内容の要旨
Replace an OC-48 Card Force-Switch 1+1 Ports Purpose This procedure forces 1+1 protection group traffic from one port in the group to the other. It is used to remove traffic from a card for replacement. Tools/Equipment Installed OC-N cards Prerequisite Procedures Installed OC-48 card Required/As Needed As needed Onsite/Remote Onsite or remote Note The Force switch is performed even if the destination path is degraded. Step 1 In the CTC node view, click the Maintenance > Protection tabs. Step 2 S
ページ11に含まれる内容の要旨
Replace an OC-48 Card Step 4 In the network map, right-click a circuit connected to the node where you are performing the Force switch. Choose Circuits from the shortcut menu. The Circuits window is displayed. Step 5 Verify that this list contains the same circuits that you marked in the list. Step 6 Choose Force from the pull-down menu at the bottom of the window. If the switch was successful, all circuits will show FORCE in the Switch State column. Step 7 Return to the“Replace an OC-48 Card” p
ページ12に含まれる内容の要旨
Related Documentation Clear a Path Protection Force Switch Purpose This procedure clears a path protection circuit Force switch. It is used to revert traffic to the original circuits after the card has been serviced. Tools/Equipment None Prerequisite Procedures “Force-Switch Path Protection Paths” section on page 10 Required/As Needed As needed Onsite/Remote Onsite or remote Step 1 In the CTC node view, click View > Go to Network View if this view is not already displayed. Step 2 In the network
ページ13に含まれる内容の要旨
Obtaining Documentation World Wide Web You can access the most current Cisco documentation on the World Wide Web at the following URL: http://www.cisco.com Translated documentation is available at the following URL: http://www.cisco.com/public/countries_languages.shtml Documentation CD-ROM Cisco documentation and additional literature are available in a Cisco Documentation CD-ROM package, which is shipped with your product. The Documentation CD-ROM is updated monthly and may be more current than
ページ14に含まれる内容の要旨
Obtaining Technical Assistance Obtaining Technical Assistance Cisco provides Cisco.com as a starting point for all technical assistance. Customers and partners can obtain documentation, troubleshooting tips, and sample configurations from online tools by using the Cisco Technical Assistance Center (TAC) Web Site. Cisco.com registered users have complete access to the technical support resources on the Cisco TAC Web Site. Cisco.com Cisco.com is the foundation of a suite of interactive, networked
ページ15に含まれる内容の要旨
Obtaining Technical Assistance Cisco TAC Web Site The Cisco TAC Web Site allows you to resolve P3 and P4 issues yourself, saving both cost and time. The site provides around-the-clock access to online tools, knowledge bases, and software. To access the Cisco TAC Web Site, go to the following URL: http://www.cisco.com/tac All customers, partners, and resellers who have a valid Cisco services contract have complete access to the technical support resources on the Cisco TAC Web Site. The Cisco TAC
ページ16に含まれる内容の要旨
Obtaining Technical Assistance Installing the Cisco ONS 15600 OC48/STM16 LR/LH 16 Port 1550 Card 16 78-15182-01