ページ2に含まれる内容の要旨
dIXEL
Operating Instructions XWA11V 1598003200 2.2 SAFETY PRECAUTIONS • Check if the supply voltage is correct before connecting the instrument. • Do not expose the back of the instrument to water or moisture: use the controller only within the operating limits avoiding sudden temperature changes with high atmospheric humidity to prevent the formation of condensation. • Warning: disconnect all electrical connections before performing any maintenance operation. • Fit the probe where
ページ3に含まれる内容の要旨
dIXEL
Operating Instructions XWA11V 1598003200 To exit the Programming Mode. + To enter a new value for the HIGH Temp ALARM (ALU). HIGH + To enter a new value for the LOW Temp ALARM (ALL). LOW + 3.1 USE OF LEDS Each LED function is described in the following table: LED MODE Function ON ALARM signaling ON The light is on °C ON Celsius degrees operation °F ON Fahrenheit degrees operation 4. TEMP ALARMS SETTING 4.1 HOW TO SET THE MIN TEMPERATURE ALARM LOW
ページ4に含まれる内容の要旨
dIXEL
Operating Instructions XWA11V 1598003200 5.2.2 HOW TO MOVE A PARAMETER FROM THE HIDDEN MENU TO THE FIRST LEVEL AND VICEVERSA Each parameter present in the HIDDEN MENU can be removed or put into “THE FIRST LEVEL” (user level) by pressing “SET + down”. In HIDDEN MENU when a parameter is present in First Level the decimal point LED is on. 5.3 HOW TO LOCK THE KEYBOARD 1. Keep pressed for more than 3s the UP and DOWN keys. 2. The “POF” message will be displayed and the keyboa
ページ5に含まれる内容の要旨
dIXEL
Operating Instructions XWA11V 1598003200 instrument requirements. Separate the probe cables from the power supply cables, from the outputs and the power connections. Do not exceed the maximum current allowed on each relay and in case of heavier loads use a suitable external relay. N.B. Maximum current allowed for all the loads is 15A. 8.1 PROBE CONNECTIONS The probe shall be mounted with the bulb upwards to prevent damages due to casual liquid infiltration. It is recommended to
ページ6に含まれる内容の要旨
dIXEL
Operating Instructions XWA11V 1598003200 11. TECHNICAL DATA Housing: self extinguishing ABS Case: face 100x64 mm; depth 45.5mm Mounting: J-box or wall-mount option Frontal protection: IP65 Connections: ¼” fast-on for power, 1/8” fast-on for probes and Digital Inputs Power supply: 120Vac ± 10%, optional 230Vac ± 10% Power absorption: 4VA max. Display: 3 digits, red LED, 14,2 mm high. Inputs: 1 NTC probe Digital inputs: 2 free voltages Relay outputs: Dry Contacts Light: re
ページ7に含まれる内容の要旨
dIXEL
Operating Instructions XWA11V 1598003200 13. PARAMETER MAP COOLER ** VALUES FREEZER LABEL DESCRIPTION DEFAULT VALUES LEVEL RANGE [-12,0°C <> 12,0°C] [- ot Thermostat probe calibration 0 0 Pr2 21°F <> 21°F] CF Temp measurement unit F F Pr2 °C - °F rES Resolution (only °C) in in Pr2 dE - in UT Display update 60 60 Pr2 0 <> 255 (sec) OnF Off function enabling Y Y Pr2 N - Y °C[ ALL <> 150,0°] ALU High Temp alarm setting ** 50 30 Pr1 °F[ ALL <> 302°] °C[ -50.0° <
ページ8に含まれる内容の要旨
dIXEL
Operating Instructions XWA11V 1598003200 14. PARAMETER LIST Ot Thermostat probe calibration: (-12.0÷12.0°C/ -21÷21°F) allows to adjust possible offset of the thermostat probe. CF T measurement unit: °C = Celsius; °F = Fahrenheit. When the measurement unit is changed the Set Point and the values of some parameters have to be modified. rES Resolution (for °C): (in = 1°C; dE = 0.1 °C) allows decimal point display. Ut Display update: The time delay of the T readout (0÷255s) on
ページ1に含まれる内容の要旨
dIXEL
Operating Instructions XWA11V
1598003200
XWA11V
Walk-In Temp / Door /Alarm / Light Module
1. GENERAL DESCRIPTION
Model XWA11V, 100x64 mm format, is a microprocessor-based controller, suitable for temperature
monitoring and alarming in a walk-in cooler or freezer. It is provided with two (2) Dry Contacts to control lights
and an external alarms. It is provided with one (1) NTC probe input for temperature measurement. The unit
nd
has 2 Digital Inputs, one for a Door Switch and