HQ-006 ¼ Turn Actuator
Installation & Maintenance Manual
Installation & Maintenance Manual
HQ-006 I&M Manual HQ-402-0606 1
ページ2に含まれる内容の要旨
Table of Contents General 1.0 Actuator Mounting 2.0 External Construction 3.0 Standard Wiring Diagrams 4.0 Manual Override 5.0 Electrical Connection 6.0 Limit Switch Setting Instructions 7.0 Lubrication 8.0 MDPI (Mechanical Dial Position Indicator) ____________________9.0 Maintenance and Storage 10.0 Trouble Shooting 11.0 Standard Specifications 12.0 EIM Office Locations 13.0 1.0 General HQ serie
ページ3に含まれる内容の要旨
2.0 Actuator Mounting The actuator may be mounted in any position The HQ-006 Actuator is supplied with a female output drive and adaptor bushings. ISO5211 FO3/FO5 and FO7 Bolt patterns are provided for actuator mounting. 3.0 External Construction HQ-006 I&M Manual HQ-402-0606 3
ページ4に含まれる内容の要旨
4.0 Standard Wiring Diagram 5.0 Manual Override The HQ-006 actuator comes standard with a manual override nut. This is located on the bottom of the unit, and can be easily operated with a 5M wrench . HQ-006 I&M Manual HQ-402-0606 4
ページ5に含まれる内容の要旨
6.0 Electrical Connection Move valve to mid-position by override nut. This will allow sufficient time to stop actuator in case of improper hook-up Identify means of removing power during hook-up Be sure no erroneous remote control signals can be received causing actuator to energize Electrically operate the valve in the open direction. If the valve closes, actuator must be stopped and checked for improper field wiring Set all field conduit entries in accordance with National
ページ6に含まれる内容の要旨
10.0 Maintenance and Storage At least once a year a check should be made of your EIM HQ Series Actuator Disconnect all power to actuator. Open Electrical Enclosure. Inspect and tighten all electrical connections Visually inspect for any electrical or mechanical damage. Replace worn or damaged components. Check lubrication consistency and levels. Fill or replace if required. Actuators must be stored in a clean, cool and dry area. The unit shall be stored with the cover inst
ページ7に含まれる内容の要旨
12.0 HQ Standard Features Enclosure Rated Weatherproof IP67 Enclosure High grade aluminium alloy, corrosion coated Power Supply 110/220 VAC, 1 PH, 50/60Hz Motor Reversible Motor Limit Switches 4 x open/close SPDT, 250VAC 3A rating Stall Protection Built –in thermal protection Indicator MDPI (Mechanical Dial Position Indicator) Manual Override Manual Override Nut Space Heater 2W Anti-condensation Conduit Entries (2) x PG13.5 Lubrication Grease