Résumé du contenu de la page N° 1
Commercial Self-Contained
®
IntelliPak Signature Series
20-80 Ton Water-Cooled Air Conditioners
20-60 Ton Air-Cooled Air Conditioners
Remote Air-Cooled Condensers
December 2001 PKG-PRC002-EN
Résumé du contenu de la page N° 2
Introduction Affordable Self-Contained Value from Trane… Signature Series Self-Contained Units Trane’s advanced technology brings unmatched reliability, high performance, and affordable cost! Hinged and removable control panel door for easy access Waterside economizer Sight glasses with (cleanable option shown) ports for viewing Unit mounted microprocessor while unit is running control with easy-to-read human interface panel 2-inch flat filter box inside unit Energy saving single fan casing with
Résumé du contenu de la page N° 3
Contents Introduction 2 Features and Benefits 4 Application Considerations 8 Selection Procedure 12 Model Number Description 14 General Data 17 Performance Data 22 Airside Pressure Drops 22 Waterside Pressure Drops 29 Water-Cooled Units 31 Air-Cooled Units 60 Heating Coils 68 Controls 69 Electrical Data 79 Dimensions and Weights 81 Mechanical Specifications 95 Options 97 PKG-PRC002-EN 3
Résumé du contenu de la page N° 4
Features and Benefits Lower Installed Cost • Multiple compressor design reduces Why consider the • Single point power connection acoustical levels. Scroll compressor Signature Series • Single point water connection design smooths gas flow for quieter self-contained floor-by-floor • Factory commissioned and tested operation systems? controls • Factory installed options Indoor Air Quality (IAQ) Features • Internally trapped drain connection Improved Cash Management • Sloped drain pan • Factory-ins
Résumé du contenu de la page N° 5
Features and Benefits Standard Features • Condensing pressure control on all FC Fans With Inlet Guide Vanes • 20 through 80 ton industrial/commercial variable water flow systems with valves Trane’s forward-curved fans with inlet water-cooled self-contained units • Programmable water purge during guide vanes pre-rotate the air in the • 20 through 60 ton industrial/commercial unoccupied mode direction of the fan wheel. This decreases remote air-cooled self-contained units • High entering air tempe
Résumé du contenu de la page N° 6
Features and Benefits Integrated Self-Contained Systems ™ Integrated Comfort System (ICS) ™ Trane’s Integrated Comfort system (ICS) increases job control by combining ® IntelliPak Signature Series self- ® contained units and a Tracer building management system. This integrated system provides total building comfort and control. Building owners and managers not only save energy when using ICS—they have the ability to automate their facilities and the convenience of a control system interface. Si
Résumé du contenu de la page N° 7
Features and Benefits ® Trane 3-D Scroll Compressor Simple Design with 70% Fewer Parts Fewer parts than an equal capacity reciprocating compressor means significant reliability and efficiency benefits. The single orbiting scroll eliminates the need for pistons, connecting rods, wrist pins, and valves. Fewer parts lead to increased reliability. Fewer moving parts, less rotating mass, and less internal friction means greater efficiency than reciprocating compressors. Patented 3-D Scroll Compliance
Résumé du contenu de la page N° 8
Application Considerations Self-Contained Return Air Ductwork transmit sound. In addition, small aspect Self-Contained Acoustical ratios will minimize potential “oil canning” Duct the return air into the mechanical Recommendations of the duct due to flow turbulence. equipment room. Connect ductwork to Successful acoustical results are the unit if local code dictates. The return The flexible horizontal discharge plenum dependent on many system design air ductwork must have an elbow inside option
Résumé du contenu de la page N° 9
Application Considerations Self-Contained Equipment Room Construction Options The preferred equipment room wall construction is concrete block. If this is not feasible then a double stud offset wall is suggested (See figure). This removes physical contact that would transmit sound through the equipment room wall to the occupied space. Interweave fiberglass insulation between the wall studs. Use two layers of sheetrock on each side of the wall. Workmanship details are critical to acoustical perfo
Résumé du contenu de la page N° 10
Application Considerations Self-Contained Recommended Pump Location strainer while allowing other units in the utilize this feature, the building water Locate pump downstream of the cooling system must be capable of operating at system to remain in operation. tower and upstream of the self-contained reduced water flow rates through the Pressure Gauges unit. This provides smoother and more self-contained units. It is imperative to Install pressure gauges on the inlet and stable unit operation. in
Résumé du contenu de la page N° 11
Application Air Cooled Considerations Condenser Ambient Limitations Remote Air-Cooled Condenser Clearance Standard ambient control allows Ensure vertical condenser air discharge Unit Location operation down to 45 F (7.2 C) with is unobstructed. While it is difficult to Unobstructed condenser airflow is cycling of condenser fans. Units with the predict the degree of warm air essential to maintaining capacity and low ambient option are capable of recirculation, a unit installed with a ceiling oper
Résumé du contenu de la page N° 12
Selection Procedure Self-Contained Following is a sample selection for a 8 standard applied water-cooled self- Refer to Trane psychometric chart to determine leaving air temperatures. contained at particular operating conditions. Use Trane Official Product Waterside Economizer Capacity ™ Selection System, TOPSS , for making 1 all final selections or contact your local After determining that the unit will meet Trane representative. the required mechanical cooling capacity, Unit Capacities determ
Résumé du contenu de la page N° 13
Selection Procedure Self-Contained Selection Example Refer to Table PD-1 on page 31 to obtain Determine net capacities by subtracting the capacity correction factors for +6% of fan motor heat from gross capacities: Design Conditions nominal cfm: 2.8 x 16 bhp = 44.8 MBh Total gross capacity required = Cooling capacity multiplier = 1.009 Net total capacity = 422.8 MBh - 420 MBh = 35.2 Tons Sensible capacity multiplier = 1.027 44.8 MBh = 378.0 MBh Total sensible capacity required = Net sensible cap
Résumé du contenu de la page N° 14
Selection Model Number Procedure Description Self-Contained Model Number Description S C W F N 20 4 2 BO A B 2 10 065 B A 1 0 1 0 A A C F A 1 1 0 T 2 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 Digit 1 - Unit Model Digit 10, 11 - Design Sequence Digit 17, 18, 19 - Fan RPM S = Self Contained BO = “B” Design
Résumé du contenu de la page N° 15
Selection Model Number Procedure Description Self-Contained Model Number Continued — Digit 25 - Industrial Options H = GBAS and RHI Digit 29 - Water Piping A = Protective Coating Evaporator Coil J = VOM and RHI D = Left Hand Basic Piping B = Silver Solder K = TCI and RHI F = Left Hand Intermediate Piping C = Stainless Steel Screws L = GBAS, VOM, and TCI K = Left Hand Basic w/ Flow Switch D = A and B M = GBAS, VOM, and RHI M = Left Hand Intermediate E = A and C N = GBAS, TCI, and RHI w/ Flow Swit
Résumé du contenu de la page N° 16
Selection Model Number Procedure Description Remote Air-Cooled Condenser Model Number Description C C R C 020 4 A AO 1 A 0 0 T 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Digit 1 - Unit Model 3 = Protective Coating with Digit 8 - Unit Voltage C = Condenser Finish Coat 4 = 460 Volt/60 Hz/3 ph 5 = 575 Volt/60 Hz/3 ph Digit 2 - Unit Type Digit 13 - Coil Options 6 = 200 Volt/60 Hz/3 ph C = Commercial A = Non-Coated Aluminum I = Industrial C = Protective Coating Aluminum Digit 9 - Control Opt
Résumé du contenu de la page N° 17
SCWF/SIWF General Data 20-38 Tons Table GD-1. SCWF/SIWF Water-Cooled Self-Contained, 20-38 Tons Unit Size 20 22 25 29 32 35 38 Compressor Data Quantity 2 2 2 1/1 1/1 3 3 NominalTon/Comp 10 10 10 15/10 15/10 10 10 Circuits 2 22223 3 Evaporator Coil Data Rows 2 23243 4 Sq. Ft. 21.81 21.81 21.81 29.98 29.98 31.35 31.35 Sq. m (2.03) (2.03) (2.03) (2.79) (2.79) (2.91) (2.91) FPF 144 144 144 144 144 120 144 Condenser Data Minimum GPM w/o Econ 36 36 36 46 46 54 54 Minimum liters / sec. w/o Econ (2.27)
Résumé du contenu de la page N° 18
SCWF/SIWF General Data 42-80 Tons Table GD-3. SCWF/SIWF Water-Cooled Self-Contained, 42-80 Tons Unit Size 42 46 52 58 65 72 80 Compressor Data Quantity 2/1 2/1 3 3 3/1 3/1 4 NominalTon/Comp 10/15 10/15 15 15 15/10 15/10 15 Circuits 3 33344 4 Evaporator Coil Data Rows 3 42434 6 Sq. Ft. 38.57 38.57 49.09 49.09 49.09 49.09 49.09 Sq. m (3.58) (3.58) (4.56) (4.56) (4.56) (4.56) (4.56) FPF 144 144 144 144 144 144 144 Condenser Data Minium GPM w/o Econ 64 64 84 84 102 102 112 Minium liters / sec. w/o
Résumé du contenu de la page N° 19
SCRF/SIRF General Data 20-60 Tons Table GD-4. SCRF/SIRF Air-Cooled Self-Contained Unit Size 20 25 29 30 35 40 50 60 Compressor Data Quantity 2 1/1 1/1 3 3 2/1 3 4 NominalTon/Comp 10 15/10 15/10 10 10 10/15 15 15 Circuits 2 2 2 2 2 2 2 2 Evaporator Coil Data Rows 3 2 4 3 4 4 4 6 Sq. Ft. 21.81 29.98 29.98 31.35 31.35 38.57 49.09 49.09 Sq. m (2.03) (2.79) (2.79) (2.91) (2.91) (3.58) (4.56) (4.56) FPF 144 144 144 120 144 144 144 144 Evaporator Fan Data Quantity 1 1 1 1 1 1 1 1 Size (Dia. - inches) 1
Résumé du contenu de la page N° 20
General Data CCRC/CIRC Table GD-6. CCRC/CIRC Remote Air-Cooled Condenser Unit Size 20 29 35 40 50 60 Gross Heat Rejection (MBH) 493 538 640 725 1040 1122 Gross Heat Rejection (kW) (144.5) (157.7) (187.6) (212.5) (304.8) (328.8) Condenser Fan Data Number/Type 4/Prop 4/Prop 6/Prop 6/Prop 8/Prop 8/Prop Size (inches) 26 26 26 26 26 26 Size (mm) (660.4) (660.4) (660.4) (660.4) (660.4) (660.4) Fan Drive Direct Direct Direct Direct Direct Direct No. of Motors/HP ea. 4/1 4/1 6/1 6/1 8/1 8/1 Nominal CFM